i P.O. box 5000 - CLEVELAND, OHIO 44101 - TELEPHONE (216) 622-9800 - ILLUMINATING BLDG. - 55 PUBLIC SOUARE Serving The Best Location in the Nation MURRAY R. EDELMAN VICE PRESIDENT NUCEAR February 27, 1985 Mr. James G. Keppler Regional Administrator, Region III Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 RE: Perry Nuclear Power Plant Docket Nos. 50-440; 50-441 Engine Control Panel Air Filters
[RDC 126(85)]
Dear Mr. Keppler:
This letter serves as the final report pursuant to 10CFR50.15(e) concerning the potential problem with engine control panel air filters supplied by Transamerica Delaval Incorporated (TDI) to Perry Nuclear Power Plant.
Mr. R. C. Knop of your office was notified on January 31, 1985, by Mr. E. Riley of The Cleveland Electric Illuminating Company that this problem was being evaluated per our Deviation Analysis Report 225.
This report contains a description of the deficiency, an analysis of safety implication, and corrective action taken.
Description of Deficiency On January 22, 1985, TDI notified the Nuclear Regulatory Commission under 10CFR21 that a potential problem had been identified concerning the air filter for engine control panels. On November 5, 1978, the purchase specification was changed from the polycarbonate transparent bowl to a metal bowl. The polycarbonate bowl is now rated at 150 psig at 125 F and the metal bowl is rated 250 psig at 175 F.
When the specification was originally issued, the vendor rated the polycarbonate bowl at 250 psi. The air pressure which the filter will see in operation cycles between 200 and 250 psig at room temperature.
8503150254 850227 PDR ADOCK 05000440 PDR
$@ 1 S
\\1 IE. 4 'l 5
Mr. James G. Kcppisr Fabruary 27, 1985 4
Analysis of Safety Implication 3
Failure of the air filter in the engine control panel could cause damage to a
surrounding components, loss of starting air pressure and/or loss of field fisshing. Any one of these conditions could affect the availability of the Standby Diesel Generator.
Corrective Action Transamerica Delaval Incorporated has supplied The Cleveland Electric Illuminating Company with new metal bowl filters rated at 250 psig, TDI P/N F527-002. These new filters have been installed on the Unit 1 and Unit 2 engine control panels. Nonconformance Reports OQC 1616 and OQC 1713 issued to track filter replacement for Units 1 and 2 respectively are closed.
i Please es11 if'there are any questions.
Sincerely,pW Murray. Edelman Vice President Nuclear Group i
MRE:pab cc:
Mr. J. A. Grobe i
USNRC, Site Office (SBB50) l Mr. D. E. Keating i
USNRC, Site Office (SBB50)
Director Office of Inspw tion and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.
20555 I
U.S. Nuclear Regulatory Commission c/o Document Management Branch Washington, D.C.
20555 Records Center, SEE-IN Institute of Nuclear Power Operations 1100 circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 i
s I
"' A yL