AffM

.:_r_______________________________.

c+JPOWER R2 ACTOR l

l EVENT NUMBER:

24033 l

__________________________________+

+_______________________+

4__________________________________________.___..+_____________________________+

FACILITY: COMANCHE PEAK REGION:

4 NOTIFICATION DATE: 08/12/92 UNIT:

( ) (2)-[ ]

STATE: TX NOTIFICATION TIME: 15:26-(ET)

RX TYPE:'[1] W-4-LP,[2] W-4-LP EVki1T DATE:

08/12/92

+_______..__._____________._______-------,--------+ EVENT TIME:

00:00(CDT)

NRC NOTIFIED BY:

lLAST UPDATE DATE:

08/12/92 HQ OPS OFFICER:

JEFF HAROLD

+-----------------------------+

+------------------------------------------------+

NOTIFICAT10NS l

EMEFGENCY CLASS: NOT APPLICABLE

+-----------------------------+

10 CFR SECTION:

GCON 50.5E (c) (1)

CONSTRUCT DEFICIENCY CCCC 21.21 UNSPECIFIED PARAGRAPH C

l

._____+__________+_______+________+______________+__+________+_________________.

l UNIT l SCRAM CODE lRX CRIT lINIT_PWRl INIT RX MODE lCURR PWRl CURR RX MODE l

+ ____+ _________+-______+________+_________________+________+-________________+

'2 N

N O

UNDER CONSTRUCT 0

UNDER CONSTRUCT

+.____+_____________.._-_____.______________________,__________________________+

EVENT TEXT

+___________.______________________________,________________________________.._+

A FACSIMILE,- LICENSEE REPORT #TSL-92116, WAS RECEIVED FROM TEXAS UTILITIES EL2CTRIC DOCKET #50-446,"ON JUNE 29, 1992, A THIN STAINLESS STEEL BLANK WAS FOUND IN THE UNIT 2 TRAIN "B" DIESEL GENERATOR GEAR CASE LUBE OIL SUPPLY LINE.

THE ENGINE WAS RUN IN THIS CONDITION FOR A TOTAL OF APPROXIMATELY 82 MINUTES AT VARIOUS RPMs AND LOAD CONDITIONS.

THE BLANK WILL BE REMOVED.

THE ENGINE JACKET WATER PUMP, CAM SHAFT GEAR OUTBOARD SUPPORTS, OVERSPEED GOVERNOR DRIVE,- _OVERSPEED GOVERNOR, AND IDLER GEAR BUSHTMG ASSEMBLY WILL BE INSPECTED FOR DISTORTION, DISCOLORATION, AND DAMAGE, COMPONENTS WILL BE REPLACED AS-NECESSARY.

kOOT CAUSE AMD PREVENTATIVE ACTION WILL BE

+_______.____"_______________________________________

DETERMINED.

92001kO1k1 920812

[g)4{ U

/

PDR ADOCK 05000446

/ j &s s

PDR o'

-