Text

________-_____--_ __-_ _ - _ - -

W Entergy Op3rstions,Inc.

ENTERGY

==

lv! G t wn Mil 3360 fe10 31437 bG W. T. Cottle e rw w (4 0f,6 oj May 28, 1992 o

  • N" -

U.S. Nuclear Regulatory Commission

!iall Station P1-137 Washington, D.C.

20555 Attention:

Document Control Desk

Subject:

Grand Gulf Nncicar Station Unit 1 Docket No.-50-416 License No NPF-29 Emergency Responso Data System Information Update GNRO-92/00062 Gentlemen:

On Janunty 14, 1992, the Grand Gulf Nuclear Station submit t ed its Emergency Responsn Data System (ERDS) Plant Attribute leibrary and the ERDS Data, Point I.lbrary in accordance with the ERDS Implementation Plan.

During subsequent telephono cor.versatjons with Mr. John Joliconur of the Analysis & Evaluation of Operational Data / Incident Response Branch (AEOD/lRB), it was agreed tnat-cortain data points _would -be provided.. lf availablo, for those parameters-omitted.in our original subm1ttal.

In rnsponse to Mr. Jolicoeur's request, the attached Data Point Library Refernnen Files are provided to reflect additionn1 GGNS data points and other related Information. We are also providing corrections and clarifications to several other data reference files discussed with.

Mr. Jolicoeur.

Pleaso contact this of fice or Hs. Jewel Summers at extension 2149 should you havn any questions or require additional information.

Yours truly, w ;-~~ c. n WTC/JS/mtc attachments: 1.

ERDS Data Point Library Updates 2.

Clarif1 cations / Corrections to Previously' Submitted Reference Files

. v v, 41 (See Next Page).

\\.

rpo
a

(.y y

G92'05152/SNLICFLR - 1 7 U-I 9206020009.9 '0528 i

~

DR ADOCK O h 416

-PDR

[-

i May 28, 1992 GNRO-92/00062 Page 2 of 3 cc:

Mr. D. C. llintz (w/a)

Mr.

. L. Mathis (w/a)

Mr. R. B. McGehen (w/a)

Mr. N. S. Reynol.1s (w/a)

Mr. II. L. Thomas (w/o)

Mr. Stewart !). F.hueter (w/a)

Regional Administintor U.S. Nuclear Regulat.ory CommissJon Region 11-.

101 Harletta St., N.W.,-..ite 2900 Atlanta, Georgiz. 30323 Mr. P. W. O'Connor, Project Manoger (w/2)

Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission-Hall Stop 13113 Washington, D.C.

20555 Nr. John R. Jolf coeur (w/a)

U.S. Nuclear Reg:Oatory Commisnion Mail Stop HNBB-3206 Washington, D.C.

20555 Mr. Tony P. Laron (w/c) italliburton NUS/F.nergy Or y P. O. Box 50736-Idaho Falls. ID 83405 s

G9205152/SNLICFLR - 2

.... - ~ -.

. to GNRO-92/00062 e

f f

I h

r I

DATA POINT LIBRARY (DPL) k

(

l G9205152/SNLICFl.R l

~

^

.m

l l

I l

Computer Point to Parameter Cross Reference The following table cross references.he N'tC Safety Function Parameters to GONS computer points. Computer points are not available for all parameters. These are denoted with N/A in the GGNS computer point column.

  • Denotes points which have been added to original list.

NRC Paraincitts GGNS computer pointa Reactivity Control NI POWER RNO.................... C51J807A C51J80713 C51J807C CSIJ807D-C51J807E CSI1807F CSI18070 CSIJ80711 N1 INTER RNO.................... C51J700

  • C51J701
  • NI SOURC RNG.................... C51 L609
  • C51J705
  • Core Coollny REAC VES LEV.................... C34N017 M AIN FD FLOW................... - C34N002 A C34N002B RCIC FLOW...................... E51L603 l

RCS Integrity RCS PRESSURE.................... C34N(X)5 llPCI FLOW

...................... N/A' (Control Room indicators are used to monitor flow).

LPCI FLOW

...................... E21L605 CR SPRAY FL...................... P41N016C DW FD S M P LV.................... P45N003

Radjunctivity Conttul EFF G A S R A D..................... D 17 K 602 E FF L I Q R A D...................... N/A (Samples taken manually by Chemistry dept.)

CN D A/E R AD...................., N/A (Samples taken manually by Chemistry dept.)

DW R A D.......................... D23 K 60 l l

  • D23K6021
  • D23K6031
  • M N STE A M RA D................... D 17L634 A CL W"C'1LCunditiesii DW PnuSS........................ M71 N001 A M71N001B DW TE M P.........................

N605A M71N605B M71N605C M71N605D S P TEM P,......................... M 71 N606U O

M71N613C G

M71N615C M71N616C S P LEVEL........................ E30N003 A E30N003B E30N003C E30N003D H 2 CONC.......................... E61 K001 A E6tK001B O2 CONC.........

N/A- (Computer Points not currently available)

Miscellaneous _Earameters CST LEVEL....................... P i l N003 WIND SPEED...................... C84J009 i

WIND DIR........................ C84J006 -

1 STAB CLASS..................... N/A (Computer Points not currently available) t No

)'

is

____.______,__m

ENCLOSURE 2 IlWR DATA POINT LIBR ARY REFERENCE FILE DATE:

4 / 21

[ 92 REACTOR UNIT:

GUI DKTA FEEDER:

IEl^

NRC ERDS PARAh1ETER:

NI SOURCE RNG T ID:

C5iL609 i ANT SPEC POINT DESC.:

SRh1 DOWNSCALE GENERIC /COND DESC.:

, Source Hange Monitor Downse :.e ANALOO/ DIGITAL:

D 4

ow as

..t ~.?

ENOR UNITS /DIO STATES:

(RESET) (ALARhl)

" M

's ENGR UNITS CONVERSION:

N/A e

.g;;6 i k.

MINIMUM INSTR RANGE:

N/A

~,.

MAXIMUM INSTR RANGE:

N/A j

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

)

IlOW PROCESSED:

N/A SENSOR LOCAflON:

Containpent Illdg 93' el. Area 11 ALARM / TRIP SET POINTS:

ALARM at.7 counts / see NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

Point is always active.

N1 DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

Point is always active.

INSTRUMENT FAILURE MODE:

Indeterniinate O

Rev. 0.A NRC-314 N-19

I ENCLOSURE 2

{

O TEMPERKFURE COMPENS ATION N/A FOR DP TRANSMllTER:

LEVEL REFERENCE LEO:

N/A UNIQUE SYSTEM DESC.:

This alarm could indicate a possible channel n gunction or insufficient source neutron levels.

Y

- k.?

?? f v yyyq

,,g bg O

9 Rev. 0.A NRC-314 N-19

- - - - - - - - - - - - - - - - - - - - - - - - - ^ - - ' - - - - - ^ - ^ ~ "

ENCLOSURE 2 t

.~

BWR DATA POINT LIBRARY REFERENCE FILE O

DATE:

4 / 21

/ 92 REACTOR UNIT:

GGI DATA FEEDER:

N/A NRC ERDS PARAMETER:

NIINTER RNG POlNTID.

C51J700 PLANT SPEC POINT DESC.:

IRM UPSCALE ALARM GENERIC /COND DESC.:

Intermediate Range Monitor Upscale Alarm ANALOG / DIGITAL:

D OlY -

oN ENGR UNITS /DIO STATES:

(NO}(31 AL) (ALM)

ENOR UNITS CONVERSION:

N/A MINih1UM INSTR RANGE:

N/A-MAXIMUM INSTR RANGE:

N/A ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A-PROC OR SENS:

-S NUMBER OF SENSORS:

1 ilOW PROCESSED:

N/A SENSOR LOCATION:

Containment Hldg 93' el. Area 11 ALARM / TRIP SET POINTS:

Any IRM at greater than 198/125 of scale on any range NI DETECTOR POWER SUPPLY CUT-OFF POWER i

LEVEL:

Point is always active, r

-)

NI DETECTOR POWER -

SUPPLY TURN-ON POWER LEVEL:

Point is always active.

INSTRUMENT FAILURE MODE:

Indeterminate d(n Rev, 0. A NRC-314 N-19

ENCLOSURE 2

(

O TEMPERAT 'E COMPENSATION N/A FOR DP TR ANSMITTER:

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC.:

This point indicates that an IRM is ou* nf range and warns of operating conditions that could lead to fuel darnage.

O O

Rev. 0. A NRC-314 N-19

ENCLOSURE 2-BWR DATA POINT LIBRARY REFERENCE FILE f~

DATE:

4 / 21

/ 92 REACTOR UNIT:

GG1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

- NI INTER RNG POINT ID:

CSIJ701_

' PLANT SPEC POINT DESC :

IRM DOWNSCAIE ALARM GENERIC /COND DESC.:

Intermediate Range Monitor Downscale Alarm ANALOG / DIGITAL:

D oir os ENGR UNITS /DIO STATES:

(NORMAL) (ALM)

ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

N/A MAXIMUM INSTR RANGE:

N/A ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A

]

PROC OR SENS:

S-I NUMBER OF SENSORS:

1 IlOW PROCESSED:

'N/A 1

SENSOR LOCATION:

Coniainmeist Bldg 93' el. Area 11 ~

i ALARM / TRIP SET POINTS:

Any IRM at less than 5/125 of scale on any range N1 DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

Point is always active.

NI DETECTOR POWER SUPPLY TURN-0.N POWER LEVEL:

Point is always active.

. INSTRUMENT FAILURE 1

MCDE:

Indeterminate O

Rev. 0.A NRC-314 N-19

_ = _ _

-j

ENCI OSURE 2 t

4

[1 V

TEMPERATURE COMPENSATION N/A FOR DP TRANSMITTER:

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC.:

This point indicates a possihie channel malfunction or power level that is below the range of indication of the IRMs.

(

(n)

('~h G

Rev. 0.A NRC-314 N-19 A

1 ENCLOSURE 2 BWR DATA POINT LIBRARY REFERENCE FILE e

i r~

DATE:

4 / 1 21

[ - 92 REACTOR UNIT:

GG1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

NI SOURCE RNG POINT ID:

CSIJ705 PLANT SPEC POINT DESC.:

SRM UPSCALE ALARM GENERIC /COND DESC,:

_ Source Range Monitor Upscale Alarm ANALOG / DIGITAL:

D-orF ON ENGR UNITS / DIG STATES:

(NORM) (ALM)

ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

N/A MAXIMUM INSTR RANGE:

N/A ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:,

IIOW PROCESSED:

N/A SENSOR LOCATION:

Containment Bldg 93' el. Area 11 5

ALARM / TRIP SET POINTS:

ALM at 10 counts / sec

- NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

Point is always active.

)

NI DETECTOR POWER 1

. SUPPLY TURN-ON POWER

. LEVEL:

Point is always active.

INSTRUMENT FAILURE MODE:

Indeterminate Rev. 0. A

. NRC-314 N-19

ENCLOSURE 2 O

O TEMPERATURE COMPENSArlON N/A FOR DP TRANSMITTER:

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC.:

Normally this alarm will cause a rod block unless associated IRM channels are on range 8 or above.

O V

l'~h

()

1' Rev. 0. A NRC-314

- N-19 l

"m

.4.+d q~--A A.

a

,g,,

_ ENCLOSURE 2 BWR DKl'A POINT LIBRARY REFERENCE FILE -

O DATE:

4 /-21

-/ 92 ~

r REACTOR UNIT:-

GGI N/A DATA FEEDER:

NRC ERDS PARAMETER:

LPCI FLOW POINTID:

E2iL605 PLANT SPEC POINT DESC.:

1,PCS SYSTEM ACTIVATION GENERIC /COND DESC.:

Low Pressure Core Spray Actuated -

ANALOG / DIGITAL:

D 017 ON g

ENGR UNITS / DIG STATES:

(OFF) (OPERATE)

ENGR UNITS CONVERSION:

N/A.

MINIMUM INSTR RANGE:

- N/A-MAXIMUM INSTR RANGE:

N/A ZERO POINT

REFERENCE:

N/A--

REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 IlOW PROCESSED:

N/A:

SENSOR LOCATION:

Control Hldg 166' el. Room OC504 '

ALARM / TRIP SET POINTS:

OPERATE is alarm -

- N1 DLTECTOR POWER -

SUPPLY CUT-OFF POWER

- LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE -

MODE:

Indelerminate Rev.0.A NRC-314 N-19 I

m ENCLOSURE 2 I

1 he j

TEMPER ATURE COMPENSATION N/A FOR DPTR ANSMITTER:

LEVEL REFERENCE LEO:

N/A UNIQUE SYSTEM DESC.:

Point indicates that the LPCS system is in operation. LPCS is automatically initiated when reactor water level lowers to -150.3 inches or Drywell pressure increases to +1.39 psig. Reactor pressure must be at 300 psi or below before LPCS can provide core spray.

%/

l q)

Rev. 0.A NRC-314 N-19

l ENCLOSURE 2 BWR DATA POINT LIBRARY REFERENCE FILE 1

1 DATE:

~4 / 21 / 92 REACTOR UNIT:

CGI DATA FEEDER:

N/A NRC ERDS PARAhtETER:

DW RAD POINT ID:

D23K60ll PLANT SPEC POINT DESC.:

DRYWELL PARTICULATE RADN GENERIC /COND DESC.:

Drywell Particulate Ratliation Monitor ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

C?M ENGR UNITS CONVERSION:

Exponential (0-SV)

MINIMUM INSTR RANGE:

10 MAXlMUM INSTR RANGE:

1,(MN),(MM)

ZERO POINT'

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 IlOW PROCESSED:

N/A SENSOR LOCATION Drywell 166' el.

ALARM / TRIP SET POINTS:

100 (Low) 1000 (Iligh)

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

LOW

('

(

Rev. 0.A NRC-314 N-19

ENCLOSURE 2 t' 3 V

TEMPER ATURE COMPENSATION gjg FOR DPTRANSM11TER:

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC.:

The system is located in the Auxilary building but has tubing which draws air from the drywell, monitors the air, and then returns the air to the drywell.

O\\O

,a~

\\

Rev. 0.A NRC-314 N-19 l'

ENCLOSURE 2 BWR DATA POINT LIBRARY RE ERENCE FILE O

D KrE:

4 /_ 21

/ 92 REACTOR UNIT:

GGI DATA FEEDER:

N/A NRC ERDS PARAMETER:

DW RAD-POINT ID:

D23K6021 -

PLANT SPEC POINT DESC.:

DRYWELL IODINE RADN GENERIC /COND DESC :

Drywell lodine Radiation Monitor ANALOG / DIGITAL:

A ENGR UNITS /DIO STATES:

CPM ENGR UNITS CONVERSION:

Exponential (G-SV)

MINIMUM INSTR RANGE:

10 MAXIMUM INSTR RANGE:

1,(MM),lMM)

ZERO POINT

REFERENCE:

-N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 IlOW PROCESSED:

N/A SENSOR LOCATION:

Drywell 166' cl.

ALARM / TRIP SET POINTS:

100 (Low) 1000 (High)

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER.

SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

LOW Rev. 0.A NP,C-314 N-19 l

a ENCLOSURE 2 O

TEMPERATURE COMPENSATION N/A FOR DP TRANSMllTER:

LEVEL REFERENCE LEO:

N/A UNIQUE SYSTEM DESC.:

The system is located in the Auxilary building but has tubing that draws air from the drywell, monitors the air, and then returns the air to the drywell.

h 9

O Rev. 0.A NRC-314 N-19 i

' - - - ^ ' ^ ^ ^ ~ ^ ^ " ~ " ' ^ ^ ~ ^ ^ ^ ~ ^ ~ ~ ' ~ ~ ~ ~ ~ ~ ' " ~ ~ ~ ~ ' ~ ~ ~ ~ ~ ~~

= ENCLOSURE '2 -

DWR DATA POINT LIBRARY REFERENCE FILE O

DATE:

4 [L 21

/ 92 REACTOR UNIT:

GG1 DATA FEEDER:

N/A-NRC ERDS PARAMETER:

DW RAD POINT ID:

D23K6031 PLANT SPEC POINT DESC.:

DRYWELL G ASEOUS RADN GENERIC /COND DESC.:

Drywell Gaseous Radiallon Monller ANALOG / DIGITAL:-

A ENGR UNITS / DIG STATES:

CPM ENGR UNITS CONVERSION:

Exponential (0-5V)

MINIMUM INSTR RANGE:

10-M AXIMUM INSTR RANGE:

1,(MM),(MM)

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1-IlOW PROCESSED:

N/A SENSOR LOCATION:

- Drywell 166' el.

ALARM / TRIP SET POINTS:

100(Low) 1000(Iligh)-

4 NI DETECTOR POWER SUPPLY CITT-OFF POWER LEVEL:

N/A NI DETECTOR POWER

- SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FA.lLURE MODE:

_, LOW Rev. O.A -

NRC-314 N-19 i

ENCLOSURE 2 c

O TEMPERATURE COMPENSATION N/A FOR DPTRANSMITTER:

LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC.:

The system is located in the Auxilary building but has tubing which draws air from the drywell, monitors the air, and then returns the air to the drywell.

OV O

Rev. 0.A NRC-314 N-19

i

. to GNRO-92/00062 h

i CLARIPICATIONS/ CORRECTIONS.

TO-PREVIOUSLY SUBMITTED REFERENCE FILES--

G9205152/SNLICFLR

- ENCLOSURE 2 BWR DATA POINT LIBRARY REFERENCE FILE DATE:

08 /

29 /_ 91 REACTOR UNIT:

GGl DATA FEEDER:

N/A NRC ERDS PARAhiETER:

REAC VES 1.EV POINT ID:

C34N017 -

PLANT SPEC POINT DESC.:

_ Rx WATER LEVEL (WIDE R ANGE)

GENERIC /COND DESC.:

Reactor Water Level ANALOG / DIGITAL:

A ENGR UNITS /DIO STATES:

INil2O ENGR UNITS CONVERSION:

I incar (32-160mv) hilNih1UM INSTR RANGE:

0 MAXIMUM INSTR RANGE:

180 ZERO POINT

REFERENCE:

COMPL REFERENCE POINT NOTES:

INSTRUMENT 0 is 533" above Vessel O PROC OR SENS:

S NUMBER OF SENSORS:

1 IIOW PROCESSED:

-N/A SENSOR LOCATION:

-Inside Cntml 135' el. Az 20. oni lll22P027 ALARM / TRIP SET POINTS:

(151,0W) 020 IIIGil)

N1 DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:-

.N/A INSTRUMENT FAILURE MODE:

(Mech. IliGil) (Elect. LOW) ~

Rev. 0.A NRC-314 -

. N-19

ENCLOSURE 2 f

~%

TEMPERATURF OMPENS ATION FOR DP'ITIANSntrITER:

Y LEVEL REFERENCE LEG:

WET UNIQUE SYSTEM DESC.:

Instrument calibrated for saturated water amd steam conditioner at 1025 psig in vessel and 135 degrees in drywell. Although, part of the feedwater control system provides no logic functions but only as a vessel level recorder indicator on P680 panel.

Top of retive fuel is 167 inches below instrument 0, instrument 0 is 533 inches above vessel 0.

rs b

f~)

~ ~)

Rev. 0.A NRC-314 J

N-19 I

- ENCLOSURE 2 BWR DATA POINT LIBRARY REFERENCE FILE -

D (V

Dure:

Os /

29- / 9i REACTOR UNIT:

GGl DATA FEEDER:

J/A NRC ERDS PARAMETER:

M AIN FD FI,0W POlNT ID:

C34N002H PLANT SPEC POINT DESC.:

RTR FW 1,00P H F1,0W GENERIC /COND DESC.:

1,00011 Feedwater Flow ANALOG / DIGITAL:

_A ENGR UNITS / DIG STATES:

Mt.H/IIR ENGR UNITS CONVERSION:

Sauare Root (32-160mv)-

MINIMUM INSTR RANGE:

0 MAXIMUM INSTR RANGE:

10 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 IlOW PROCESSED:

N/A SENSOR LOCATION:

'Ibrbine Hide.113' el. on! III22PO43 in Rm IT226

- ALARM /rRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A N1 DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

'N/A

)

INSTRl: MENT FAILURE MODE:

1,0W Rev. 0.A NRC-314 N-19 y

=

u

\\

l ENCLOSURE 2

'a

(&)

TEMPERATURE COMPENSATION FOR DP TRANSMllTER:

N/A LEVEL REFERENCE 1.EO:

N/A UNIQUE SYSTEM DESC.:

Part of feedwater control system but only function is to display loop flow and in conjunction with 'A' loop flow instrumentation displays total FW flow on P680 panel.

AV (D,

V Rev. 0.A NRC-314 N-19

ENCLOSURE 2

.l BWR DATA POINT LIBRARY REFERENCE FILE D KfE:

08 /

29 / 91 REACFOR UNIT:

GGI DATA FEEDER:

N/A--

NRC ERDS PARAMETER:

WIND DIR POINT ID:

CM4J006 PLANT SPEC POINT DESC.:

WIND DIRECTION El,162 GENERIC /COND DESC.:

Wind Direction @ Elevation 162' ANALOG / DIGITAL:

A ENGR UNITS /DIO STATES:

DEG ENGR UNITS CONVERSION:

1,inear (0-Sv)

MINIMUM INSTR RANGE:

_0 MAXIMUM INSTR RANGE:

540 ZERO POINT REFERF.NCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

I llOW PROCESSED:

N/A SENSOR LOCATION:

Mel Tower 162' el.5 miles north of olant ALARM /fRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:.

N/A INSTRUMENT FAILURE MODE:

LOW O

Rev. 0.A NRC-314 N-19 1

ENCLOSURE 2 -

,[*

. f")

c TEMPERATURE COMPENSATION FOR DP TRANSMTITER:

N/A LEVEL REFERENCE LEG:

N/A UNIQUE SYSTEM DESC.:

The degree reading of this parameter indicates the direction from which the wind is coming from.

'w]'

()

V l

Rev. 0.A NRC-314 N-19

ENCLOSURE 2 -

  • ['

BWR DATA POINT LIBRARY REFERENCE FILt:,

f" DATE:

08 /

29 /- 91 REACTOR UNIT:

GGl DATA FEEDER:

N/A NRC ERDS PARAMETER:

CST I,EVEI, POINT ID:

P1iNW3 PLANT SPEC POINT DESC.:

CNDS STOH AGE TK 1.EVEl, GENERIC /COND DESC.:

Condensale Storace Tank Level ANALOG / DIGITAL:

A ENGR UNITS /DIO STATES:

l*T ENGR UNITS CONVERSION:

Linear (1-5v)

MINIMUM INSTR RANGE:

0 MAXIMUM INSTR RANGE:

40 ZERO POINT

REFERENCE:

COMPLX REFERENCE POINT NOTES:

8" Almve Tank llottom PROC OR SENS:

S NUMBER OF SENSORS:

1 IlOW PROCESSED:

_N/A SENSOR LOCATION:

_ yard 122' el ALARM / TRIP SET POINTS:

(22.8 LOW)(25.5 tilGil)

NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A i

i NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A

. INSTRUMENT FAILURE MODE:

LOW I

a Rev. 0.A NRC-314 N-19

- - - - ~

ENCLOSURE 2 a

e 9

\\g TEMPERATURE COMPENS ATION FOR DP TH ANSMITTER:

N/A LEVEL REFERENCE LEO:

DRY UNIQUE SYSTEM DESC.:

Nonnal level is 25 feet but varies significantly depending on current water usage. One foot of level is equivalent to 9677 gallons of water.

D(v

[)

'O Rev. 0 A NRC-314 i

N-19 i

e.........