-l TENNESSEE VALLEY AUTHORITY Sequoyah Nuclear Plant Post Of fice Box 2000 Soddy Daisy, Tennessee 37379 l

1 l

September 18, 1984 U. S. Nuclear Regulatory Commission Document Control Desk

TENNESSEE VALLEY AUTHORITY - SEQUOYAH NUCLEER PLANT UNIT 1 - DOCKET NO.

50-327 - FACILlTY OPERATING LICENS' DPR SPECIAL REPORf 84-04 The enclosed special report provides details concerning the inoperability of a fire door in excess of seven days. This report is submitted in accordance with Sequoyah Unit 1 Technical Specification 3.7.12 and 6.9.2.

Very truly yours, TENNESSEE VALLEY AUTHORITY OR. A P. R. Wallace Plant Manager Enclosure cc (Enclosure):

James P. O'Reilly, Director U.S. Nuclear Regulatory Commission Suite 2900 101 Marietta Street, NW Atlanta, Georgia 30323 Records Center Institute of Nuclear Power Operations Suite 1500 1100 circle 75 Parkway Atlanta, Georgia 30339 NRC Inspector, NUC PR, Sequoyah i

8409280154 840918 PDR ADOCK 05000327 S PDR

>t- t 1

3

' l 1983-TVA 50m ANNIVERSARY An Equal Opportunity Employer

(*

SEQUOYAH NUCLEAR PLANT UNIT 1 SPECIAL REPORT 84-04 ve Event Description and Probable Cause A penetration fire barrier breaching permit was issued on 08/16/84 for fire door A-33 due to the door panel splitting at the welded seam. This door is located on elevation 669 between the refueling water purification

pump and filter area (safety related area) and the cask decon collector tank, pump, and filter area (non-safety related) . The cause of the split panel has been attributed to hard closing forces due to the high differential pressure across the door.

Corrective Actions A roving fire watch was established per Technical Specification 3.7.12 on 08/16/84 when the permit was issued. .A new door panel was received on 09/10/84 and installation of the new panel was completed on 09/12/84.