Forwards NPDES Discharge Monitoring Rept for Aug 1984. Comments & Rept of Noncompliance W/Conditions of NPDES Encl
ML20098A163
Person / Time
Site: Oyster Creek
Issue date: 09/11/1984
From: Fiedler P
GENERAL PUBLIC UTILITIES CORP.
To: Gaston J
NEW JERSEY, STATE OF
Shared Package
ML20098A164 List:
References
NUDOCS 8409240332
Download: ML20098A163 (4)


Text

I--

60-a 19 GPU Nuclear Corporation NUQIgf Post Office Box 388 Route 9 South Forked River New Jersey 08731-0388 6o9 971-4000 Writer's Direct Dial Number:

September 11, 1984 Mr. John Gaston, Director Division of Water Resources Department of Environmental Protection P.O. Box CN-029 Trenton, NJ 08625

Dear Mr. Gaston:

Subject:

GPU Nuclear Corporation Oyster Creek Nuclear Generating Station NJPDES Permit No. NJ 000 5S50 Enclosed is the Discharge Monitoring Report for the subject permit for the month of August 1984.

Please note that there was a possible r

noncompliance with a maximum effluent limitation during this reporting period. A copy of Noncompliance Report No. 000 5550/84/03 is attached.

If you have any further questions concerning this report, please contact Mr. Douglas Moore of our Licensing and Regulatory Affairs Department at (609) 971-4630.

Very truly yours,

~

Pettr B. Fiedler Vice President & Director Oyster Creek PDF:DFM: dam Enclosures (cc: Page 2) t 8409240332 840911 PDR ADOCK 05000219 R

PDR

/>'

I GPU Nuclear Corporation is a subsidiary of the General Public Utilities Corporation

)

To: John Gaston, Director Dept. of Environmental Prot ction Re: Discharge Monitoring Report Page 2 cc:

U.S. Environmental Protection Agency Room 432 26 Federal Plaza New York, NY 10278 Attn: Permits Administration Branch Marion Burger U.S. Army Corps of Engineers Custom House Second & Chestnut Streets Philadelphia, PA 19106 Dr. Thomas E. Murley, Administrator Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406

. Director _

r Office ~ of Nuclear Reactor Regulations *'

U.S. Nuclear Regulatory Commission Washington, DC 20555 c/o Distribution Services Branch, DDC, ADM 1

h t

i

NJPDES PERMIT 000 5550 GPU Nuclear Corporation Comments for Oyster Creek - August 1984 1.

The Oyster Creek Nuclear Generating Station did not operate during the month of August 1984 as a result of the maintenance / refueling outage currently in progress.

2.

Circulating water pumps 1-1 was operated on August 14-24, 1984.

Cir. ulating water pump 1-2 was operated on August 14-17, 31, 1984.

Circulating water pump 1-3 was operated on 1-5,16,17, and 24-31, 1984.

Circulating water pump 1-4 was operated on Augus* 17-31, 1984.

3.

Dilution pump 1-1 was operated on August 3, 4, 5, 9,10 and 17, 1984.

Dilution pump 1-2 was operated on August 4, 5, 9--17, 1984.

l Dilution pump 1-3 was operated on August 3-5, 10-12, 14, 16, dnd 17,1984.

4.

Tne main condensers were chlorinated August 10-31,1984 with a maximum chlorine value of.06 mg/1.

5.

The dilution factar for Oyster Creek was six for all days during the month.

6.

Due to operating and calibrating problems with the Continuous Chlorine Monitor, daily grab samples are taken with the analytical results determined by amperometric titration have resumed. This data is supplied with the monthly monitoring report as detailed in the letter to your office dated July 25,1977.

7.

Tne value reported for total suspended solids, discharge DMW is the average value of the analysis of two aliquots of the same sample.

8.

Possible noncompliance with item 10(b), exceeded two hour cnlorination time limit.

m 1

Initial Telepnone Date of Report Date:

August 20, 1984 Occurrence: August 20, 1984 REPORT OF NONCOMPLIANCE WITH CONDITIONS OF NJPDES PERMIT N0. NJ 000 5560 REPORT NUMBER 000 5550/84/03 IDENTIFICATION OF OCCURRENCE:

Possible nonccmpliance with item 10(b), page 7 of 20.

CAUSE OF NONCOMPLIANCE:

Possibility of the discnarge of chlorine from the 8 Soutn Condenser section.

DESCRIPTION OF NONCOMPLYING DISCHARGE:

The timer which controls the chlorinetion cycle in eacn condenser section was out of service. An automatic switch used to control chlorine discharge per condenser was inadvertently placeu in the'on' mode ratner than the skip mode, which may have caused the 8 South Condenser section to discnarge chlorine for greater than a two hour period on August 20, 1984.

DURATION OF NONCOMPLIANCE:

Unknown CORRECTIVE ACTION TO REDUCE THE NONCOMPLYING DISCHARGE:

The automatic switch was reset to the skip mode.

CORRECTIVE ACTION TO PREVENT RECURRENCE:

The timer was repaired on August 21, 1984.

Date: August 21, 1984 i --