ML20097J606
| ML20097J606 | |
| Person / Time | |
|---|---|
| Site: | Crystal River |
| Issue date: | 01/26/1996 |
| From: | FLORIDA POWER CORP. |
| To: | |
| References | |
| PROC-960126, NUDOCS 9602050055 | |
| Download: ML20097J606 (48) | |
Text
.
Document Transmittal #: 39966 Dats: 1/29/96 To:
NRC (DC DESK)
MAC: N/A Destination:
==
Description:==
Copy Copy Totals Document:
Revision:
Comment:
INFO CNTL MSTR AR0952 06 24 1
0 0
AR0954 04 24 1
0 0
AR0959 03 24 1
0 0
i instructions to the Addressee:
Please verify the document (s) received agrees with the above information. Be sure to destroy document (s) or portions of document (s) superseded by the above.
The signature indicates acknowledgment of receipt of the above document (s). Retum signed and dated transmittal to Document Control within 20 days at mail code:
NA1C Florida Power Corporation Document Control, NA1C Crystal River Energy Complex 15760 W. Power Line St.
Crystal River, FL 34428-6708 Signature of Addressee:
Date:
Independent Verification:
Date:
fg (Control Room documents only) k 9602050055 960126
' df PDR ADOCK 05000302 f
F PDR t
.(_..-
t 8
Rev. 6 Effective Date [
. ~ ~ ~. _ _. _
r$
- ' bO y
'3 1
jf
"ANNUNfiathRSSh7E ONL AR-952
%~.. !
FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 WDB ANNUNCIATOR RESPONSE THIS PROCEDURE ADDRESSES SAFETY RELATED CONP0NENTS etaikCona InJte APPROVED BY:
( 1 GNAT"RE 1 FILE) 70!@d DATE:
INTERPRETATION CONTACT: Supervisor, Nuclear Operations Administrative Shift
i TABLE OF CONTENTS O
V SECTION EME 1.0 PURPOSE............................
1
2.0 REFERENCES
I 2.1 INPLENENTING REFERENCES...............
I 2.2 DEVELOPNENTAL REFERENCES I
3.0 PERSONNEL IND0CTRINATION 1
4.0 INSTRUCTIONS 1
5.0 FOLLOW-UP ACTIONS.......................
1 ENCLOSURE 1
Annunciator Response......................
2 O
)
O AR-952 Rev. 6 Page i
1 1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the WD-WP Lampbox.
1.2 Establish operator actions for valid Annunciator alarms on the WD-WP Lampbox.
j d
1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the WD-WP Lampbox.
l
2.0 REFERENCES
11 4
2.1 INPLENENTING REFERENCES None l
2.2 DEVELOPNENTAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures rs l'd 2.2.2 Annunciator Window Engraving Drawing E-224-050.
3.0 PERSONNEL IND0CTRINATION None 4.0 INSTRUCTIONS 4
1 1
4.1 Respond to alarms on the WD-WP Lampbox as indicated on Enclosure 1, Annunciator Response.
5.0 FOLLOW-UP ACTIONS l
None O
i AR-952 Rev. 6 Page 1
ENCLOSURE 1 O
(Page 1 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-2 B-1-2 DECAY HEAT PIT SUMP LEVEL EXTRA HIGH INDICATED CONDITION:
- LEVEL OF DH SUMP 3B> 3' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- DH PIT SUMP PUMP 3B (WDP-38) AUT0-START ALARM
- DH PIT SUMP PUMP 3B RUN INDICATING LAMPS
- SUMP LEVEL INDICATION ON WD PANEL O
OPERATOR ACTION FOR A VALID ALARM:
1
(/
- CHECK THAT DH SUMP PUMP 3B IS RUNNING
- CHECK DH SUMP PUMP 3B VALVE LINEUP
- INVESTIGATE DRAINS TO DH PIT SUMP FOR ABNORMAL DRAINAGE DISCUSSION:
THIS ALARM IN CONJUNCTION WITH WDP-3B RUNNING COULD INDICATE A LARGE LEAK IN THE 'B' DH PIT. NOTIFY CONTROL ROOM OPERATOR IMMEDIATELY.
REFERENCES:
DWG 208-060 WD-10 SENSING ELEMENT: WD-134-LS O
AR-952 Rev. 6 Page 2
c l
ENCLOSURE 1 (Page 2 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-3 B-1-3 AUX BLDG SUMP PUMP 3A AUTO-START INDICATED CONDITION:
- AUX BLDG SUMP LEVEL >2.5'
- AUX BLDG SUMP PUMP 3A (WDP-4A) IS SELECTED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l
- PUMP RUN INDICATING LAMPS ON WD PANEL l
- POSSIBLE AUX BLDG SUMP LEVEL EXTRA HIGH ALARM
- PUMP DISCHARGE PRESSURE ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- NORMAL FUNCTION ALARM. IF FREQUENCY OF AUTO-STARTS IS EXCESSIVE, CHECK VALVE LINEUP OF SYSTEMS DRAINING TO SUMP AND DETERMINE SOURCE.
DISCUSSION:
IF WDP-4A RUNS FOR AN EXCESSIVE PERIOD OF TIME, THIS COULD INDICATE PUMP DEGRADATION OR A LARGE LEAK IN THE AUXILIARY BUILDING. NOTIFY CONTROL ROOM OPERATOR IF RUN TIME IS EXCESSIVE.
REFERENCES:
DWG 208-060 WD-11 SENSING ELEMENT: WD-132-LS l
l O
AR-952 Rev. 6 Page 3
4 I
4 l
ENCLOSURE 1
()
(Page 3 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-4 B-1-4 mamme -
AUX BLDG SUMP PUMP 3A TRIP INDICATED CONDITION:
- PUMP AUTO-STOPS IF AUX BLDG SUMP LEVEL <1.5' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- NORMAL FUNCTION ALARM. INVESTIGATE VALVE LINEUP / SWITCH POSITION IF AUX BLDG SUMP LEVEL EXTRA HIGH ALARM EXISTS.
DISCUSSION:
4 THIS IS AN EXPECTED ALARM IF WDP-4A IS MANUALLY STARTED AND AUXILIARY BUILDING SUMP LEVEL <1.5'.
INVESTIGATE ANY OTHER REASON FOR PUMP TRIP.
REFERENCES:
DWG 208-060 WD-11 SENSING ELEMENT: WD-132-LS AR-952 Rev. 6 Page 4
l ENCLOSURE 1 (Page 4 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-5 B-1-5 WASTE GAS COMP SEAL LEAK DR TK LOW LEVEL INDICATED CONDITION:
- LOW LEVEL OF 8" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- POSSIBLE RMA-2(G) OR RMA-3 ALARM OPERATOR ACTION FOR A VALID ALARM:
- BLEED AIR OFF WDV-1030 TO CLOSE O
DISCUSSION:
WDV-1031 SHOULD BE USED TO MANUALLY CONTROL DRAIN POT LEVEL IF WDV-1030 FAILS TO CONTROL.
REFERENCES:
DWG 208-060 WD-135 SENSING ELEMENT: WD-357-LS2 O
AR-952 Rev. 6 Page 5
l ENCLOSURE 1 (Page 5 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-I-6 B-1-6 mumme AUX BLDG SUMP PUMP 3B AUTO-START INDICATED CONDITION:
- AUX BLDG SUMP LEVEL >2.5'
- AUX BLDG SUMP PUMP 3B (WDP-48) IS SELECTED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- POSSIBLE AUX BLDG SUMP LEVEL EXTRA HIGH ALARM
- PUMP DISCHARGE PRESSURE ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- NORMAL FUNCTION ALARM. IF FREQUENCY OF AUTO-STARTS IS EXCESSIVE, CHECK VALVE LINEUP OF SYSTEMS DRAINING TO SUMP AND DETERMINE SOURCE.
DISCUSSION:
IF WDP-4B RUNS FOR AN EXCESSIVE PERIOD OF TIME, THIS COULD INDICATE PUMP DEGRADATION OR A LARGE LEAK IN THE AUXILIARY BUILDING. NOTIFY CONTROL ROOM IF RUN TIME IS EXCESSIVE.
REFERENCES:
DWG 208-060 WD-12 SENSING ELEMENT: WD-132-LS O.
V AR-952 Rev. 6 Page 6
4 I
ENCLOSURE 1 (Page 6 of 15)
\\
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-7 B-1-7
--n AUX BLDG SUMP PUMP 3B TRIP o
INDICATED CONDITION:
- PUMP AUTO-STOPS IF AUX BLDG SUMP LEVEL <1.5' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- SUMP LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- NORMAL FUNCTION ALARM. INVESTIGATE VALVE LINEUP / SWITCH POSITION IF AUX BLDG SUMP LEVEL EXTRA HIGH ALARM EXISTS.
DISCUSSION:
THIS IS AN EXPECTED ALARM IF WDP-4B IS MANUALLY STARTED AND AUXILIARY BUILDING SUMP LEVEL <1.5'.
INVESTIGATE ANY OTHER REASON FOR PUMP TRIP.
REFERENCES:
DWG 208-060 WD-12 SENSING ELEMENT: WD-132-LS O
AR-952 Rev. 6 Page 7
l ENCLOSURE 1 (Page 7 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-1-8 B-1-8 mumm-same==me===
WASTE GAS SAMPLING ANALYZER PANEL IN ALARM INDICATED CONDITION:
- LOSS OF 120 VAC POWER TO GAS ANALYZER PANEL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- POWER INDICATING LAMP ON PANEL IS OUT
- GAS FLOW <1.5 SLPM OPERATOR ACTION FOR A VALID ALARM:
- CHECK PANEL POWER SUPPLY SWITCH
- CHECK 480 VAC SUPPLY BREAKER ON REACTOR MCC 382 O
- CHECK PUMP OPERATION AND VALVE ALIGNMENT DISCUSSION:
THIS ALARM MAY INDICATE A NEED TO PERFORM AN ALTERNATIVE MEANS OF SAMPLING.
NOTIFY CONTROL ROOM OPERATOR IMMEDIATELY.
REFERENCES:
DWG 208-060 WD-131, WD-135
'x SENSING ELEMENT: PF RELAY WD-21-FIS O
AR-952 Rev. 6 Page 8
r-'
l ENCLOSURE 1
's,S (Page 8 of 15)
/
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-1 B-2-1 AUX BLDG SUMP LEVEL EXTRA HIGH INDICATED CONDITION:
- LEVEL OF AUX BLDG SUMP >5.5' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- AUX BLDG SbMP PUMP 3A AND/0R 38 AUTO-START ALARMS
- SUMP PUMP IND1#.ATING LAMPS ON WD PANEL
- SUMP LEVEL IND1'CATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
(~'N
- CHECK THAT AUX BLDG SUMP PUMPS 3A AND/0R 3B ARE RUNNING
\\
- CHECK SUMP PUMP VALVE LINEUP
- DETERMINE SOURCE OF WATER INTO SUMP DISCUSSION:
THIS ALARM IN CONJUNCTION WITH AN AUXILIARY BUILDING SUMP PUMP ALREADY RUNNING MAY BE AN INDICATION OF EITHER PUMP DEGRADATION OR A LARGE LEAK IN THE AUXILIARY BUILDING.
NOTIFY CONTROL ROOM OPERATOR IMMEDIATELY.
1
REFERENCES:
DWG 208-060 WD-11 SENSING ELEMENT: WD-132-LS1 O
AR-952 Rev. 6 Page 9
l ENCLOSURE 1
<()
(Page 9 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-2 B-2-2 WASTE TRANSF 2
PUMP 3A AUTO-START FAILURE i
INDICATED CONDITION:
- BLEED TANK 3A SELECTED ON FEED SELECT SWITCH (AND PULLED)
- MUV-103 OPEN AND
- WASTE TRANSFER PUMP 3A (WDP-5A) NOT RUNNING I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- MUV-103 INDICATING LAMPS IN CONTROL ROOM OPERATOR ACTION FOR A VALID ALARM:
- CHECK VALVE LINEUP, SWITCH POSITIONS AND FEED PERMISSIVE CIRCUITS FOR CORRECT POSITIONS.
DISCUSSION:
THIS ALARM WILL OCCUR IF WDP-5A IS SHUT DOWN FOR ANY REASON WHILE ATTEMPTING TO ADD TO THE RCS USING WDT-5A.
NOTIFY CONTROL ROOM OPERATOR 0F LOCAL INDICATIONS CONCERNING THE REASON FOR WDP-5A SHUTDOWN.
i
REFERENCES:
DWG 208-060 WD-13 SENSING ELEMENT: 42B RELAY F1 3MUV-103
'l J
l AR-952 Rev. 6 Page 10
I ENCLOSURE 1 O
(Page 10 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-3 B-2-3 WASTE TRANSF PUMP 3A TRIP INDICATED CONDITION:
- PUMP CONTROL SWITCH IN NOR-AFT-START POSITION AND PUMP NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP MOTOR OVERCURRENT
- PUMP STARTED LOCALLY THEN SELECTED FOR FEED OPERATOR ACTION FOR A VALID ALARM:
p
- CHECK FOR PUMP MOTOR OVERLOAD TRIP CONDITION Q
- CHECK VALVE LINEUP AND SWITCH POSITION
- CALL CONTROL ROOM TO SEE IF PUMP SELECTED FOR FEED DISCUSSION:
IF WDP-5A WAS RUNNING FOR RCBT RECIRCULATION, A NEW SAMPLE REQUEST WILL HAVE TO BE GENERATED AFTER THE CAUSE OF THE PUMP TRIP IS DETERMINED AND RESOLVED.
REFERENCES:
DWG 208-060 WD-13, WD-73 SENSING ELEMENT: CS/SC+CS/0 42B O
AR-952 Rev. 6 Page 11
4 I
ENCLOSURE I O
(Page 11 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-4 B-2-4 WASTE TRANSF PUMP 3B
---l AUTO-START FAILURE INDICATED CONDITION:
- BLEED TANK 3B SELECTED ON FEED SELECT SWITCH (AND PULLED)
- MUV-103 OPEN AND l
- WASTE TRANSFER PUMP 3B (WDP-58) NOT RUNNING i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- HUV-103 INDICATING LAMPS IN CONTROL ROOM
\\
OPERATOR ACTION FOR A VALID ALARM:
- CHECK VALVE LINEUP, SWITCH POSITIONS AND FEED PERMISSIVE CIRCUITS FOR CORRECT POSITIONS.
DISCUSSION:
THIS ALARM WILL OCCUR IF WDP-58 IS SHUT DOWN FOR ANY REASON WHILE ATTEMPTING TO ADD TO THE RCS USING WDP-58. NOTIFY CONTROL ROOM OPERATOR OF LOCAL INDICATIONS CONCERNING THE REASON FOR WDP-58 SHUTDOWN.
REFERENCES:
DWG 208-060 WD-14 SENSING ELEMENT: 42B RELAY F2 3MUV-103 O
AR-952 Rev. 6 Page 12
l ENCLOSURE 1
]
(Page 12 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-5 B-2-5 WASTE TRANSF PUMP 38 TRIP INDICATED CONDITION:
- PUMP CONTROL SWITCH IN NOR-AFT-START POSITION AND PUMP NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP MOTOR OVERCURRENT
- PUMP STARTED LOCALLY THEN SELECTED FOR FEED OPERATOR ACTION FOR A VALID ALARM:
- CHECK FOR PUMP MOTOR OVERLOAD TRIP CONDITION pv
- CHECK VALVE LINEUP AND SWITCH POSITION
- CALL CONTROL ROOM TO SEE IF PUMP SELECTED FOR FEED DISCUSSION:
IF WDP-5B WAS RUNNING FOR RCBT RECIRCULATION, A NEW SAMPLE REQUEST WILL HAVE TO BE GENERATED AFTER THE CAUSE OF THE PUMP TRIP IS DETERMINED AND RESOLVED.
REFERENCES:
DWG 208-060 WD-14, WD-73 SENSING ELEMENT: CS/SC+CS/0 42B AR-952 Rev. 6 Page 13
ENCLOSURE 1 (Page 13 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-6 B-2-6 WASTE TRANSF PUMP 3C AUTO-START FAILURE INDICATED CONDITION:
- BLEED TANK 3C SELECTED ON FEED SELECT SWITCH (AND PULLED)
- MUV-103 OPEN AND
- WASTE TRANSFER PUMP 3C (WDP-5C) NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP RUN INDICATING LAMPS ON WD PANEL
- MUV-103 INDICATING LAMPS IN CONTROL ROOM OPERATOR ACTION FOR A VALID ALARM:
- CHECK VALVE LINEUP, SWITCH POSITIONS AND FEED PERMISSIVE CIRCUITS FOR CORRECT POSITIONS.
DISCUSSION:
THIS ALARM WILL OCCUR IF WDP-5C IS SHUT DOWN FOR ANY REASON WHILE ATTEMPTING TO ADD TO THE RCS USING WDP-5C. NOTIFY CONTROL ROOM OPERATOR OF LOCAL INDICATIONS CONCERNING THE REASON FOR WDT-5C SHUTDOWN.
REFERENCES:
DWG 208-060 WD-15 SENSING ELEMENT: 42B RELAY F3 3MUV-103 O
AR-952 Rev. 6 Page 14
l ENCLOSURE 1
()
(Page 14 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-7 B-2-7 EASTE TRANSF PUMP 3C TRIP INDICATED CONDITION:
- PUMP CONTROL SWITCH IN NOR-AFT-START POSITION AND PUMP NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- PUMP MOTOR OVERCURRENT
- PUMP STARTED LOCALLY THEN SELECTED FOR FEED OPERATOR ACTION FOR A VALID ALARM:
- CHECK FOR PUMP MOTOR OVERLOAD TRIP CONDITION O
- CHECK VALVE LINEUP AND SWITCH POSITION
- CALL CONTROL ROOM TO SEE IF PUMP SELECTED FOR FEED DISCUSSION:
.IF WDP-5C WAS RUNNING FOR RCBT RECIRCULATION, A NEW SAMPLE REQUEST WILL HAVE TO BE GENERATED AFTER THE CAUSE OF THE PUMP TRIP IS DETERMINED AND RESOLVED.
REFERENCES:
DWG 208-060 WD-15, WD-74 SENSING ELEMENT: CS/SC+CS/0 42B O
AR-952 Rev. 6 Page 15
4 l
ENCLOSURE 1
(
(Page 15 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WP-2-8 B-2-8 i
MISC RAD WASTE TRANSF PUMP 3A TRIP INDICATED CONDITION:
- PUMP CONTROL SWITCH IN NOR-AFT-START POSITION AND WDP-6A NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i
- PUMP RUN INDICATING LAMPS ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
0'
- CHECK VALVE LINEUP AND DETERMINE CAUSE OF PUMP MOTOR OVERLOAD TRIP CONDITIONS DISCUSSION:
THIS PUMP DOES NOT AUTO SHUT DOWN ON LOW MISCELLANE0US WASTE STORAGE TANK (MWST) LEVEL.
IF PROCESSING TO THE ECST'S, CARE SHOULD BE TAKEN TO PREVENT RUNNING WDP-6A WITH NO LEVEL IN THE MWST.
REFERENCES:
DWG 208-060 WD-16 SENSING ELEMENT: CS/SC+CS/0 42B O
AR-952 Rev. 6 Page 16 (LAST PAGE)
Rev. 4
!- h ~
Effective Date Document S$ih N FORM ATION ObjL f C. R. Nucicar t
ANNUNCIATOR RESP 6NSE AR-954 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 Ol WDD ANNUNCIATOR RESPONSE THIS PROCEDURE ADDRESSES SAFETY RELATED COMPONENTS APPROVED BY:
Inte pret on on act j
IGNAT N FILE) f/20/0//
DATE:'
INTERPRETATION CONTACT: Supervisor, Nuclear Operations Administrative Shift
TABLE OF CONTENTS SECTION PEE 1.0 PURPOSE............................
1
2.0 REFERENCES
1 2.1 IMPLEMENTING REFERENCES...............
I 2.2 DEVELOPMENTAL REFERENCES 1
3.0 PERSONNEL Ile0CTRINATION 1
4.0 INSTRUCTIONS 1
5.0 FOLLOW-UP ACTIONS.......................
1 ENCLOSURES 1
Annunciator Response......................
2 1
l i
I AR-954 Rev. 4 Page i
~
1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the WD-WR Panel Lampbox.
1.2 Establish operator actions for valid Annunciator alarms on the WD-WR Panel Lampbox.
1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the WD-WR Panel Lampbox.
2.0 REFERENCES
2.1 INPLEMENTING REFERENCES 2.1.1 OP-415, Waste Disposal Evaporators 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INP0 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-050.
3.0 PERSONNEL INDOCTRINATION None 4.0 INSTRUCTIONS 4.1 Respond to alarms on the WD-WR Panel Lampbox as indicated on, Annunciator Response.
5.0 FOLLOW-UP ACTIONS None O
AR-954 Rev. 4 Page 1
ENCLOSURE 1 (Page 1 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-2 0-1-2 mamme-NEUTRALIZER TANK MIXER TRIP INDICATED CONDITION:
- MIXER (WDMX-1) TRIPPED OUT ON OVERLOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- MIXER RUN INDICATING LAMPS ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- DETERMINE CAUSE OF OVERLOAD CONDITION O
DISCUSSION:
THE MIXER IS NO LONGER USED.
REFERENCES:
DWG 208-060 WD-31 SENSING ELEMENT: SWGR 49 CONTACTS O
AR-954 Rev. 4 Page 2
\\
ENCLOSURE 1 (Page 2 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-3 0-1-3 WASTE GAS DECAY TK 3A PRESS HIGH INDICATED CONDITION:
- TANK PRESSURE >83 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- TANK PRESSURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- ASSOCIATED WASTE GAS DECAY TANK IS FULL. LINEUP TO TANK WITH <80 PSIG IN IT.
DISCUSSION:
CONSIDER REDUCING PRESSURE IN WASTE GAS DECAY TANK 3A BY USING RECYCLE VALVES PER OP-412A, WASTE GAS DISPOSAL SYSTEM.
REFERENCES:
DWG 208-060 WD-05 SENSING ELEMENT: WD-204-PS2 O
AR-954 Rev. 4 Page 3
ENCLOSURE 1 O
(Page 3 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-4 D-1-4 WASTE GAS DECAY TK 3B PRESS HIGH INDICATED CONDITION:
- TANK PRESSURE >83 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- TANK PRESSURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- ASSOCIATED WASTE GAS DECAY TANK IS FULL. LINEUP TO TANK WITH <80 PSIG IN IT.
O DISCUSSION:
CONSIDER REDUCING PRESSURE IN WASTE GAS DECAY TANK 3B BY USING RECYCLE VALVES PER OP-412A, WASTE GAS DISPOSAL SYSTEM. CONSIDER GOING TO THE 'C' TANK AS THE 'A' TANK IS USED FOR SAMPLING.
REFERENCES:
DWG 208-060 WD-05 SENSING ELEMENT: WD-205-PS2 i
O AR-954 Rev. 4 Page 4
ENCLOSURE 1
)
(Page 4 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-5 D-1-5 l
WASTE GAS DECAY TK 3C PRESS HIGH INDICATED CONDITION:
- TANK PRESSURE >83 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- TANK PRESSURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- ASSOCIATED WASTE GAS DECAY TANK IS FULL. LINEUP TO TANK WITH <80 PSIG IN IT.
DISCUSSION:
CONSIDER REDUCING PRESSURE IN WASTE GAS DECAY TANK 3C BY USING RECYCLE VALVES PER OP-412A, WASTE GAS DISPOSAL SYSTEM. CONSIDER GOING TO THE 'B' TANK AS THE 'A' TANK IS USED FOR SAMPLING.
REFERENCES:
,DWG 208-060 WD-05 SENSING ELEMENT: WD-206-PS2 O
AR-954 Rev. 4 Page 5
ENCLOSURE 1 f
(Page 5 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-6 D-1-6 LIQUID WASTE DRUM FILL LEVEL HIGH INDICATED CONDITION:
- DRUM LEVEL >2.5' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- VALVE WDV-653 INDICATING LAMPS ON WASTE DRUM PANEL l
OPERATOR ACTION FOR A VALID ALARM:
- ENSURE VALVE WDV-653 CLOSES
- CHECK FOR IMPROPER DRUM MIX
- CHECK FOR POSSIBLE HIGH FLOW RATE Og
- CHECK FOR POSSIBLE LEAKING DRUM INLET MANIFOLD DISCUSSION:
THIS EQUIPMENT IS NO LONGER USED.
REFERENCES:
DWG 208-060 WD-127 SENSING ELEMENT: WD-142-LS 4
O AR-954 Rev. 4 Page 6
ENCLOSURE 1
(
(Page 6 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-7 D-1-7 mes==-
samm RC EVAP CONCENTRATOR LEVEL HIGH INDICATED CONDITION:
- CONCENTRATOR LEVEL >20" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- RC EVAP FEED TANK PUMP WDP-16A/B INDICATING LAMPS ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- ENSURE PUMP (WDP-16A/B) TRIPS
- SECURE RC EVAP COND COOLING WATER, STEAM SUPPLY, AND VACUUM PUMP O
DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-143 SENSING ELEMENT: WD-174-LS O.,
V AR-9S4 Rev. 4 Page 7
~
l ENCLOSURE 1 (Page 7 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-8 D-1-8 1
RC EVAP FEED TANK LEVEL HIGH l
INDICATED CONDITION:
- TANK LEVEL >92%
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- TANK LEVEL INDICATION ON WD PANEL l
1 OPERATOR ACTION FOR A VALID ALARM:
- CHECK LINEUP FOR CAUSE OF ALAP,M
- IF LEVEL CONTINUES TO INCREASE, OPEN DRAIN VALVE DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-137 SENSING ELEMENT: WD-161-LS2 AR-954 Rev. 4 Page 8
ENCLOSURE 1 (Page 8 of 15) l RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-1 D-2-1 RC EVAP FEED TANK DENSITY HIGH INDICATED CONDITION:
- FEED TANK SPECIFIC GRAVITY >1.2 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- TANK DENSITY INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- DETERMINE CAUSE OF HIGH DENSITY AND RESOLVE
- TRANSFER WATER TO CONC. WASTE STORAGE TANK OR TO CONC. BORIC ACID STORAGE TANK.
DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-137 SENSING ELEMENT: WD-162-PSA O
AR-954 Rev. 4 Page 9
ENCLOSURE 1 O
(Page 9 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-2 D-2-2 RC EVAP DISTILLATE RESERVOIR LEVEL HIGH INDICATED CONDITION:
- TANK LEVEL AT 30" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- RESERVOIR LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- SECURE STEAM SUPPLY AND COOLING WATER FLOW TO EVAPORATOR O
DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-137 SENSING ELEMENT: WD-160-LSI l
O AR-954 Rev. 4 Page 10
ENCLOSURE 1 (Page 10 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-3 D-2-3 RC EVAP DISTILLATE CONDUCTIVITY HIGH INDICATED CONDITION:
- DISTILLATE CONDUCTIVITY >2 #MHOS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- DISTILLATE REJECT / DISCHARGE VALVE INDICATION ON WD PANEL j
- DISTILLATE CONDUCTIVITY INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- ENSURE AUTO ACTION INITIATED (SEE DISCUSSION)
O
- DETERMINE CAUSE OF ALARM AND RESOLVE
- CHECK FEED TANK CONCENTRATION AND FOR F0AMING IN TANK DISCUSSION:
THE AUTO ACTION WILL OPEN THE DISTILLATE REJECT VALVE (WDV-722)/(WDV-719) AND SHUT THE DISTILLATE DISCHARGE VALVE (WDV-721)/(WDV-720) IF RC DISTILLATE PUMP 3A (WDP-17A) OR 3B (WDP-17B) IS RUNNING. THE ALARM COULD BE DEFEATED PER OP-415.
REFERENCES:
DWG 208-060 WD-143 SENSING ELEMENT: WD-159-CS O
AR-954 Rev. 4 Page 11
ENCLOSURE 1 (Page 11 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-4 D-2-4 RC EVAP CONCENTRATOR VACUUM LOW INDICATED CONDITION:
- CONCENTRATOR VACUUM <15" HG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CONCENTRATOR VACUUM INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- CHECK SEAL WATER, VACUUM WATER SEPARATOR, AND STEAM SUPPLY, AND FOR POSSIBLE COOLING WATER FLUCTUATIONS.
DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-143 SENSING ELEMENT: WD-164-PSA O
AR-954 Rev. 4 Page 12
ENCLOSURE 1 (Page 12 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-5 D-2-5 RC EVAP FEED TANK LEVEL LOW INDICATED CONDITION:
- TANK LEVEL <14" 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- TANK LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- DETERMINE REASON FOR LOW LEVEL BY CHECKING VALVE LINEUP AND RESTORE.
DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-143 SENSING' ELEMENT: WD-161-LSI O
AR-954 Rev. 4 Page 13
4' e
- f-ENCLOSURE 1 (Page 13 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-6 D-2-6 l
RC EVAP FEED TANK TEMP LOW l
INDICATED CONDITION:
- FEED TANK TEMPERATURE <150 DEG F REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- FEED TANK HEATER INDICATING LAMPS (WDHE-2) ON WD PANEL
- FEED TANK TEMPERATURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- IF RC EVAPORATOR PACKAGE IS IN OPERATION:
f)
- ENSURE FEED TANK LEVEL >29.2%
x_-
- MANUALLY CONTROL HEATERS IF DESIRED
- CHECK OUT OPEPATION OF HEATER CONTROL CIRCUITRY DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-50 SENSING ELEMENT: WD-163-TE O
AR-954 Rev. 4 Page 14
I8 4
ENCLOSURE 1 O
(Page 14 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-7 D-2-7 RC EVAP DISTILLATE i
RESERVOIR LEVEL LOW INDICATED CONDITION:
- TANK LEVEL <10" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- SELECTED RC EVAP DISTILLATE PUMP INDICATING LAMPS ON WD PANEL
- RESERVOIR LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
]
- CHECK VALVE LINEUP, STEAM SUPPLY, AND COOLING WATER 1
1
- ENSURE AUTO ACTION INITIATED (SEE DISCUSSION) i DISCUSSION:
THE AUTO ACTION TRIPS SELECTED RC EVAP OISTILLATE PUMP (WDP-17A/178). ALARM COULD BE DEFEATED PER OP-415.
l
REFERENCES:
DWG 208-060 WD-143 i
SENSING ELEMENT: WD-160-LS3 O
AR-954 Rev. 4 Page 15
ENCLOSURE 1 gg (Page 15 of 15)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-8 D-2-8 BORIC ACID STOR TNK TEMP HI/LO INDICATED CONDITION:
- BORIC ACID STORAGE TANK 3A OR 3B TEMP >164 OR <152 DEG F REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- STORAGE TANK HEATER INDICATING LAMPS ON WD PANEL
- TANK TEMPERATURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:
- INVESTIGATE HEATER CONTROL CIRCUITRY FOR MALFUNCTION.
O DISCUSSION:
ALARM COULD BE DEFEATED PER OP-415
REFERENCES:
DWG 208-060 WD-52, WD-53 SENSING ELEMENT: WD-80-TS, WD-83-TS O
AR-954 Rev. 4 Page 16 (LAST PAGE)
I Rev. 3 O'
Effective Date /I f- [7 Do;ument Secilan l
l NFORM ATIOM ONLN l-C. R. !?uckwr
=:
.m.y m -
AR-959 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3
(
WDI ANNUNCIATOR RESPONSE THIS PROCEDURE ADDRESSES SAFETY RELATED CONPONENTS l
1
/
APPROVED BY:
Int, pre on o act
/IGNATURFONTILE)
DATE:
' 20 6
/
INTERPRETATION CONTACT:
Nuclear Operations Superintendent
+
TABLE OF CONTENTS
/
SECTION PAGE 1.0 PURPOSE............................
1
2.0 REFERENCES
I 2.1 IMPLEMENTING REFERENCES...............
I 2.2 DEVELOPMENTAL REFERENCES 1
3.0 PERSONNEL IND0CTRINATION 1
4.0 INSTRUCTIONS 1
5.0 FOLLOW-UP ACTIONS.......................
1 ENCLOSURES 1
Annunciator Response.......................
2 AR-959 Rev. 3 Page 1
1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the WD-WW Lampbox.
1.2 Establish operator actions for valid Annunciator alarms on the WD-WW Lampbox.
1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the WD-WW Lampbox.
2.0 REFERENCES
2.1 IMPLEMENTING REFERENCES None 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-050 3.0 PERSONNEL INDOCTRINATION None
-s s
4.0 INSTRUCTIONS 4.1 Respond to alarms on the WD-W Lampbox as indicated on Enclosure 1, Annunciator Response.
5.0 FOLLOW-UP ACTIONS None O
AR-959 Rev. 3 Page 1 l
Ol ENCLOSURE 1 (Page 1 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-1-1 I-1-1 mumm-m--mm -
LAUNDRY & SHOWER MONITORING TANK WDT-11A LEVEL LOW INDICATED CONDITION:
- LOW LEVEL IN LAUNDRY TANK REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- WD-271-LR OPEPATOR ACTION FOR A VALID ALARM:
- CHECK LAUNDRY & SHOWER TANK MONITOR PUMP A, WDP-23A DISCUSSION:
THIS IS AN EXPECTED ALARM FOR A LAUNDRY AND SHOWER MONITORING TAKK RELEASE, AT WHICH TIME WDP-23A/B WILL TRIP ON LOW LEVEL IN WDT-11A/B.
REFERENCES:
DWG 208-060 WD-185 SENSING ELEMENT: WD-271-LS O
AR-959 Rev. 3 Page 2
l ENCLOSURE 1 mQ (Page 2 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-1-2 1-1-2 LAUNDRY & SHOWER MONITORING TANK WDT-11B LEVEL LOW INDICATED CONDITION:
l
- LOW LEVEL IN LAUNDRY TANK REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- WD-271-LR OPERATOR ACTION FOR A VALID ALARM:
- CHECK LAUNDRY & SHOWER TANK MONITOR PUMP B, WGP-238 O
DISCUSSION:
THIS IS AN EXPECTED ALARM FOR A LAUNDRY AND SHOWER MONITORING TANK 1
RELEASE, AT WHICH TIME WDP-238/A WILL TRIP ON LOW LEVEL IN WDT-11B/A.
REFERENCES:
DWG 208-060 WD-186 SENSING ELEMENT: WD-272-LS O
AR-959 Rev. 3 Page 3
I ENCLOSURE 1 O
(Page 3 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-1-3 I-1-3 LAUNDRY & SHOWER MONITORING PUMP WDP-23A TRIP INDICATED CONDITION:
- RED TARGET WITH PUMP 0FF REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- WD-275-PI OPERATOR ACTION FOR A VALID ALARM:
- CHECK WDP-23A DISCUSSION:
THIS IS AN EXPECTED ALARM FOR A LOW LEVEL IN WDT-11A/B.
REFERENCES:
DWG 208-060 WD-185 SENSING ELEMENT: CS/SC CS/0 42B i
i O
AR-959 Rev. 3 Page 4
.'=
Ol ENCLOSURE 1 (Page 4 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-1-4 I-1-4 mumme -
me -
nummi LAUNDRY & SHOWER MONITORING PUMP WDP-23B TRIP INDICATED CONDITION:
- RED TARGET WITH PUMP OFF REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- WD-276-PI OPERATOR ACTION FOR A VALID ALARM:
- CHECK WDP-23B C
DISCUSSION:
THIS IS AN EXPECTED ALARM FOR A LOW LEVEL IN WDT-11A/B.
REFERENCES:
DWG 208-060 WD-186 SENSING ELEMENT: CS/SC CS/0 42B '
AR-959 Rev. 3 Page 5
l ENCLOSURE 1 (Page 5 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-2-1 I-2-1 LAUNDRY & SHOWER MONITORING TANK WDT-11A LEVEL HIGH INDICATED CONDITION:
- HIGH LEVEL IN LAUNDRY TANK REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- WD-271-LI OPERATOR ACTION FOR A VALID ALARM:
- CHECK LAUNDRY TANK LEVEL t
DISCUSSION:
A HIGH LEVEL IN WDT-11A/B WILL TRIP THE LAUNDRY AND SHOWER SUMP PUMP WDP-22A/B.
REFERENCES:
DWG 208-060 WD-187 SENSING ELEMENT: WD-271-LS3 O
AR-959 Rev. 3 Page 6
..s ENCLOSURE 1
'O (Page 6 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-2-2 I-2-2 LAUNDRY & SHOWER MONITORING TANK WDT-11B LEVEL HIGH INDICATED CONDITION:
- HIGH LEVEL IN LAUNDRY TANK REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- WD-272-LI OPERATOR ACTION FOR A VALID ALARM:
- CHECK LAUNDRY TANK LEVEL DISCUSSION:
A HIGH LEVEL IN WDT-11B/A WILL TRIP THE LAUNDRY AND SHOWER SUMP PUMP WDP-22B/A.
REFERENCES:
DWG 208-060 WD-180 s
SENSING ELEMENT: WD-272-LS3 l
i 1
l AR-959 Rev. 3 Page 7 i
1 l
ENCLOSURE 1 (Page 7 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-2-3 I-2-3 LAUNDRY & SHOWER SUMP LEVEL EXTRA HIGH INDICATED CONDITION:
- HIGH LEVEL IN LAUNDRY SHOWER SUMP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- WD-36-LI j
OPERATOR ACTION FOR A VALID ALARM:
- CHECK OPERATION OF WDP-22A/B.
DISCUSSION:
REFERENCES:
DWG 208-060 WD-180 SENSING ELEMENT: WD-135-LS2 O
AR-959 Rev. 3 Page 8
,et l
ENCLOSURE 1
[
(Page 8 of 8)
RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WW-2-4 I-2-4 ULTRA FILTRATION TRIP INDICATED CONDITION:
- TRIP 0F ULTRA FILTRATION PUMP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:
- INVESTIGATE ULTRA FILTRATION SYSTEM DISCUSSION:
gg THIS EQUIPMENT IS NO LONGER USED.
REFERENCES:
SENSING ELEMENT:
OV AR-959 Rev. 3 Page 9 (LAST PAGE)