ML20096H400
| ML20096H400 | |
| Person / Time | |
|---|---|
| Site: | Cooper (DPR-46-A-173) |
| Issue date: | 01/24/1996 |
| From: | NRC (Affiliation Not Assigned) |
| To: | |
| Shared Package | |
| ML20096H403 | List: |
| References | |
| NUDOCS 9601290040 | |
| Download: ML20096H400 (6) | |
Text
_.. _. _ _. _ _ _. _ _ _. _. _. _ _ _
NOTES FOR TABLE 3.1.1 l
1.
There shall be two OPERABLE or tripped TRIP SYSTEMS for each function.
If the minimum number of OPERABLE INSTRUMENT CHANNELS for a TRIP SYSTEM cannot be met, the affected TRIP SYSTEM shall be placed in the safe (tripped) condition, or the appropriate actions listed below shall be taken.
i A.
Initiate insertion of OPERABLE rods and complete insertion of all OPERABLE rods l within four hours.
B.
Reduce power to less than 30% of RATED POWER.
l t
i C.
Reduce power level to IRN range and place Reactor Mode Selector Switch in the i
STARTUP position within eight hours and depressurize to less than 1000 psig.
1 D.-
Reduce turbine load and close Main Steam Isolation Valves within eight hours.
2.
Permissible to bypass, with control rod block, for Reactor Protection System reset in REFUEL and SHUTDOWN positions of the Reactor Mode Selector Switch.
3.
This note deleted.
4.
Permissible to bypass when turbine first stage pressure is less than 30% of full load.
5.
IRMs are bypassed when APRMs are onscale and the Reactor Mode Selector Switch is in the RUN position.
6.
The design permits closure of any two lines without a full scram being initiated.
7.
When the reactor is suberitical, fuel is in the vessel, and the reactor water temperature is less than 212*F, only the following trip functions need to be OPERABLE:
A.
Reactor Mode Selector Switch in SHUTDOWN.
B.
Manual scram.
C.
IRM high flux at 120/125 indicated scale.
D.
8.
Not required to be OPERABLE when PRIMARY CONTAINMENT INTEGRITY is not required.
9.
Not required to be OPERABLE while performing low power physics tests at atmospheric pressure during or after refueling at power levels not to exceed 5 MW(t).
- 10. Not required to be OPERABLE when the reactor pressure vessel head is not bolted to l the vessel.
i 9601290040 960124 gDR ADOCK 05000298 PDR Amendment No. 73,**,15*,173 N.
-. ~. - - - - - -.
_ ~,
LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.4 STANDBY LIOUID CONTROL SYSTEM 4.4 STANDBY LIOUID CONTROL SYSTEM i
Anolicabilitv!
Annlicability
\\
Applies ts the operating status of Applies to the surveillance require.
I l
the Standby Liquid Control (SLC) ments of the Standby Liquid Control System.
(SLC) System.
l Obiective:
obi.etive:
q To verify the OPERABILITY of the SLC l i
To assure the OPERABILITY of a sys-
- System, ten with the capability to SHUTDOWN the reactor and maintain the SHUT-DOERI condition without the use of-control rods.
Specification:
Snecification lA.
Normal System Operation A.
Normal System Operation l
l'1.
During periods when fuel is in the The OPERABILITY of the SLC System l reactor and prior to startup from a shall be shown by the performance of Cold Condition,' the Standby Liquid the following tests:
Control System shall be operable, except.as specified in 3.4.8 below.
1.
At least once each 3 months each This system need not be operable subsystem shall be tested for OPERA-when the. reactor is in the Cold BILITY by recirculating domineral-Condition and all control rods are ized water to the test tank and fully inserted and Specification verifying each pump develops a flow 3.3.A is set, rate 2 38.2 gpm at a discharge pres-sure 2 1300 psig.
2.
At least once during each OPERATING CYCLE:
a.
Check that the settings of the sub-system relief valves are 1450 < P
< 1680 psig and the valves will reset at P 2 1300 psig.
b.
Manually initiate the system, except explosive valves, and pump boron solution from the SLC Storage Tank l through the recirculation path.
Verify each pump develops a flow rate 2 38.2 gpm at a discharge pressure 21300 psig. After pumping boron solution the system will be flushed with demineralized water.
l l
Amendment No. t,123,152,173
-107-
LIMITING CONDITIONS FOR OPERATION SURVEILIANCE REQUIREMENTS 3.4 4.4.C C.
Sodium Pentaborate Solution C.
Sodium Pentaborate Solution At all times when the SLC System is The following tests shall be per-required to be OPERABLE the follow-formed to verify the availability of ing conditions shall be met:
the liquid control solution:
l 1.
The net volume versus concentration 1.
Volume:
Check and record at least of the liquid control solution in once per day.
the SLC Storage Tank shall be main-tained as required in Figure 3.4.1.
2.
The temperature of the liquid con-2.
Temperature:
Check and record at trol solution shall be maintained least once per day.
above the curve shown in Fig-ure 3.4.2.
3.
Concentration: Check and record at least once per month.
Also check concentration anytime water or boron is added to the solution or solution temperature is below the temperature required in Figure 3.4.2.
l D.
It specification 3.4.A through C cannot be met, the reactor shall be placed in a Cold Shutdown Condition with all operable control rods fully inserted within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
Amendment No. 173
-109-
-