Provides Info to Support Util Use of 1 H fire-rated Cable & Clarifies Provisions of Automatic Fire Suppression & Detection Capability in Areas Where Cable Installed.Cable Routed in Cable Trays or in Free Air
ML20096E696
Person / Time
Site: Comanche Peak Luminant icon.png
Issue date: 05/13/1992
From: William Cahill
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
TXX-92232, NUDOCS 9205190321
Download: ML20096E696 (2)


Text

1 id Z,-

.o

-2 1.

Log

  1. TXX-92232 File # 909.5

-'~~

TUELECTRIC May 13, 1992 Williaan J. Cahill, Jr.

Crasp Vke Prrsidrat U. S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, DC 20555

SUBJECT:

COMANCHE PEAK STEAH ELECTRIC STATION (CPSES) - UNIT 2 DOCKET NO. 50-446 g

ROCKBESTOS CABLE Gentlemen:

-Per discussions with the NRC, the following information is being provided to I

support TU Electric's use of one hour fire rated cable at CPSES.

This information clarifies provisions of automatic fire suppression and detection capability in areas where-this. cable is installed.

Additionally, information regarding design adequacy of'the cable support mechanisms under fire conditions is provided.

TV Electric has identified in the FSAR that one hour fire rated cable is an acceptable one hour fire rated barrier.

One hour fire rated cable which is oucside of Containment satisfies the separation requirements f or redundant

-fire safe shutdown equipment cabling when the relative fire hazards, automatic fire suppression and fire detection capabilities are taken into account. Where one hour fire rated cables are used outside of Containment, both detection and automatic suppression are provided except for three-areas', consistent with Unit 1. which do not have automatic suppression.

These areas are:

1.

Auxiliary Building (790') - Laundry Holdup area, 2.

Safeguards Building (790') - Valve Room 066, and

-3.

Safeguards.Bui ding (790') - Stairwell.

The. potential hazards in each of these areas have been evaluated accordingly in the Fire Hazards Analysis and found acceptable.

One hour' fire rated cable at CPSES is either routed in cable trays or in free air with individual supports.

The ability of exposed steel cable trays and' cable supports to adequately supr--t the cable in the event of a fire whilezsupporting design basis dead weight loads has been included in the Fire Hazards Analysis.

Where automatic suppression coverage is not provided fr alternatively,:for the three areas identified above, administrative controls on the maximum permissible fire loading established by the Fire Hazards Analysis ensures fire induced temperatures do not exceed he critical temperature of steel as defined by NFPA.

This is consistent with the AISC guidelines used in the design for cable trays and supports at CPSES.

60 9205190321 920513 3

PDR ADOCK 05000446 400 N. otive street Ls.si Dalias, Texas 7520i 1

F.

PDR 2

<, r-TXX-92232 Page 2 of 2 The appropriate areas of the Fire Protection Report are being revised to reflect the above information.

If you should have any questions. please call Mr. J. D. Seawright at (214) 812-4375.

a.

Sincerely.

William J. Cahill, Jr.

~

Bv:--.-

~

f. S. Marshali Generic Licensing Manager JDS/tg c - Mr. R. D. Martin, Region IV Resident Inspectors, CPSES (2)