Text
. _...
TABLE 4.3-1 ou e my g REACTOR TRIP SYSTEM INSTRUMENTATION SURVEILLANCE REQUIREENTS
>$ U 3Q TRIP 0
ACTUATING.
NODES FOR l
nN CHANNEL DEVICE WHICH CHANNEL CHANNEL OPERATIONAL OPERATIONAL-ACTUATION SURVEILLANCE og.
FUNCTIONAL UNIT CHECK CALIBRATION TEST TEST LOGIC TEST IS REQUIRED o-g on
- 13. Steam Generator Water Level-
$0". 51 Low-Low mN*
e.
a.
R 0
N.A.
N.A.
- 1. 2 m
Water Level-Low-Low b.
RCS Loop aT N.A.
R 0
N.A.
N.A.
1, 2 t
- 14. DELETED
- 15. Undervoltage-Reactor Coolant N.A.
R N.A.
Q N.A.
I Pumps w
a
- 16. Underfrequency-Reactor N.A.
R N.A.
O N.A.
1 wg Coolant Pumps
- 17. Turbine Trip a.
Low Fluid Oil Pressure N.A.
N.A.
N.A.
S/U(1. 9)
N.A.
I b.
Turbine Stop Valve N.A.
N.A.
N.A.
S/U(1. 9)
N.A.
1 Closure Ng
- 18. Safety Injection Input from N.A.
N.A.
N.A.
R N.A
- 1. 2 g
ESF A
- 19. Reactor Coolant Pump Breaker M.A.
N.A.
N.A.
R N.A.
1 y
Position Trip ID
- 20. Reactor Trip System Interlocks a.
Intermediate Range N.A.
R(4)
R N.A.
N.A.
2N Neutron Flux. P-6 Sg b.
Low Power Reactor Trips Block. P-7 N.A.
R(4)
R N.A.
N.A.
1 W
c.
Power Range Neutron Flux P-8 N.A.
R(4)
R N.A.
N.A.
I
.h I