Responds to Request for Reliable Ventilation for B Battery & Motor Generator Room & 460-volt Switchgear Room,Per SEP Topic IX-5.New Redundant Relay W/Switch & Associated Wiring Will Be Installed by End of Next Refueling Outage
ML20095F812
Person / Time
Site: Oyster Creek
Issue date: 08/21/1984
From: Fiedler P
GENERAL PUBLIC UTILITIES CORP.
To: Crutchfield D
Office of Nuclear Reactor Regulation
References
TASK-09-05, TASK-9-5, TASK-RR NUDOCS 8408270381
Download: ML20095F812 (2)


Text

~ 'o GPU Nuclear Corporation NUCIM7 100 Interpace Parkway Parsippany New Jersey 070541149 (201)263-6500 TELEX 136-482 Wnter's Direct Dial Number:

August 21, 1984 Mr. Dennis M. Crutchfield, Chief Operating Reactors Branch #5 U.S. Nuclear Regulatory Commission Washington, D. C.

20555

Dear Sir:

Subject:

Oyster Creek Nuclear Generating Station (OCNGS)

Docket No. 50-219 SEP Topic No. IX-5 Ventilation System During the integrated assessment of the SEP topics, the NRC staff re-quested GPUN to provide reliable ventilation for the B battery and motor generator room and the 460 V switchgear room at OCNGS.

A review of the associated control circuitry for the HVAC fans has deter-mined that the ventilation system for the above mentioned rooms is started by energizing one relay (Relay K). Energization of the relay applies power to both supply and exhaust fans. Therefore, a failure of the relay would disable both the exhaust and supply fans. The power supplies to the fans are redundant.

Based on the above finding, GPU Nuclear has decided to provide a new redundant relay with a switch and associated wiring for each room. With this modification, on loss of power or loss of the existing relay, the other fan which receives power from a separate MCC can be manually started from the MCC thereby maintaining sufficient air circulation.

Loss of the Relay K will also activate an alarm in the control room.

84

Dgag70393$ooffj, ADOCK o PDR y

CPU Nuclear Corpnration is a subwtiary cf General Public Utihties Corporation

.sn. v.

2-The above modification will be implemented by the end of the.next

-refueling outage.

Very truly yours, 4

- g edler Vice-President and Director Oyster Creek m/0241e cc:

Administrator Region I U.S. Nuclear Regulatory Commission 631-Park Avenue King of Prussia, Pa 19406

- NRC Resident Inspector Oyster Creek Nuclear Generating Station Forked River, NJ 08731 I