ML20095F774

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in Insp Repts 50-327/84-11 & 50-328/84-11.Corrective Actions: Personnel Reinstructed on Importance of Checking Limiting Condition for Operations Prior to Mode Change
ML20095F774
Person / Time
Site: Sequoyah  
Issue date: 07/16/1984
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20095F764 List:
References
NUDOCS 8408270370
Download: ML20095F774 (7)


Text

-_...

Li3 f..

TENNESSEE VALLEY AUTHORITY CHATTANOOGA. TENNESSEE 374ot 400 Chestnut Street Tower II July'16, 1 4 2*l6 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator

'101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323

Dear Mr. O'Reilly:

SEQUOYAH NUCLEAR PLANT UNITS 1 AND 2 - NRC-0IE REGION II INSPECTION REPORT 50-327/84-11 AND 50-328/84 RESPONSE TO VIOLATIONS The subject OIE inspection report dated June 14, 1984 from R. C. Lewis to H. G. Parris cited TVA with five Severity Level IV Violations. Enclosed is the response to the items of violation in the subject inspection report.

If you have any questions, please get in touch with R. H. Shell at FTS 858-2688.

To the best of my knowledge, I declare the statements contained herein are complete and true.

Very truly yours, TENNESSEE VALLEY AUTHORITY L..M. Mills, Manager Nuclear Licensing Enclosure oc (Enclosure):

Mr. Richard C. DeYoung, Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Records Center Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 8408270370 840727 PDR ADOCK 05000327 G

PDR 1983-TVA 5OTH ANNIVERSARY An Equal Opportunity Employer

.p

' ENCLOSURE n

P' RESPONSE - NRC DMSPECTION REPORT NOS.

50-327/84-11 AND 50-328/84-11 R. C. LEWIS'S LETTER TO H. G. PARRIS DATED JUNE 14, 1984 Item 1 (327/84-11-01 Technical specification 3 0.4 requires that entry into an operational mode or other specified' condition shall not be made unless the conditions for

-the limiting condition for operation (LCO) are met without reliance on

provisions contained' in the action requirements.

I Contrary to the above, entry into an operational mode was made on two different occasions When the LCOs were not met without reliance on provisions contained in the action requirements. On April 13,1984, unit 1 entered mode 3 with instrument 1-LT-3-38 inoperable. LCO 3 3 2.1 was not met for steam generator level channels. On April 15,1984, unit 1 entered mode 2 with instrument 1-LT-68-320 inoperable. LCO 3 3 3 7 was not met for

. pressurizer level channels. The licensee immediately complied with the applicable action requirements until the instruments were returned to service.

'This -is a Severity Level IV violation (Supplement I).

This violation applies to unit 1 only.

TVA Response 1.

Admission or Denial of the Alleged Violation

' TVA admits the violation occurred as stated.

2. - Reasons for the Violation if Admitted With unit ~ 1 in mode 4 during startup after refueling, the technical specifications were consulted to determine the requirements to change modes with steam generator level transmitter 1-LT-3-38 inoperable.

^

Limiting condition for operation (LCO) 3 31.1 items 14 and 15 were LCO applicable for mode 2, therefore allowing entry into mode 3 3 3 2.1 item 5 was applicable to mode 3, but operation and mode change were not prohibited. ' The unit entered mode 3 at 0905 CST on 04/12/84 with the level transmitter out of service, but personnel had overlooked LCO 3 3 2.1 item-6e which required the transmitter to be operable for entry into mode 3 At 1500 CST on-04/15/84 with unit 1 in mode 3 and diluting to criticality, sampling of the reactor coolant system (RCS) was initiated using procedurs RTI-3, " Initial Criticality." During the previous refueling outage, a modification to the RCS sampling configuration was made which routed the sample line to the low side tap of pressurizer level transmitter 1-LT-68-320. This modification had been performed on unit 2 with no adverse effect on the operation of the transmitter.

Sampling was being performed at twenty-minute intervals with the sample lines being continuously purged.

O-At 1630 CST, mode 2 was achieved, and at 1715 CST, the operator discovered the level transmitter 1-LT-68-320 inoperable.

Investigation. revealed that the sampling had made the instrument inoperable while in mode 3.

3.

Corrective Steps Which Have Been Taken and the Results Achieved The bistables for steam generator level transmitter 1-LT-3-38 were tripped as required by technical specifications upon discovery of the overlooked LCO 3.3.2.1 item 6c.

1-LT-3-38 was returned to service on 04/13/84.

Personnel have been reinstructed on the importance of checking all applicable LCOs prior to mode change. Licensee Event Report (LER) SQR0 327/84024 was submitted on this event.

The bistables for pressurizer level transmitter 1-LT-68-320 were tripped as

. required by technical specifications upon discovery of the inoperable instrument.

1-LT-68-320 was returned to service on 04/15/84.

In an attempt to prevent the pressurizer level transmitter from becoming inoperable during sampling, the sample isolation valve will be throttled during sampling. Chemical Laboratory procedures have been changed to require the shift engineer to be notified before and after samples are taken. Licensee Event Report SQRO-50-327/84025 was suomitted on this event.

0 4.

Corrective Steps Which Will Be Taken To Avoid Further Violations Technical Instruction (TI) 59, " Listing of Teahnical Specification Instru-ments", will be revised to indicate steam generator level transmitter 1-LT-3-38 to be required for entry into mode 3.

The RCS sample line will be modified to restrict flows being used for samples before startup from the next unit I refueling outage.

5.

Date When Full Compliance Will Be - Achieved Full compliance was achieved on the first event when the histables to 1-LT-3-38 were tripped on 04/13/84. Full compliance was achieved on the second event when the bistables to 1-LT-68-320 were trlpped on 04/15/84.

Item 2 (328/84-11-01) 10 CFR 50, Appendix B, Criterion III as implemented by the licensee's approved QA program (Topical Report TVA-TR75-1) section 17.2.3, " Modification Control",

requires that modifications to critical structures, systems, and components (CSSC) shall be coatrolled to assure that "as-built" quality is not degraded.

Contrary to the above, modifications to CSSC were not controlled in that ECN 22-78, implementing Engineering Design non-conforming report NCR FEB 79-10, which addressed the need to rewire pressurizer PORV control circuitry and committed to do so bJfore unit fuel loading, did not get implemented on a unit 2 PORV control circuit (PS68-337 which affects PCV 66-332) until April 1984.

This is a Severity Level IV Violation (Supplement 1). This violation applies to unit 2 only.

r TVA Response 1.

Admission or Denial of the Alleged Violation TVA admits the violation occurred as stated.

2.

Reasons for the Violation if Admitted The control circuitry modification was scheduled to be performed on-the unit 2 pressurizer power operated relief valves before an operating license being issued. The cause of this violation is considered to be either failure to follow the applicable construction procedures or inadequate contruction procedures, but the exact cause has not been identified because of the approximate three-year time period since construction procedures have been used (unit 2 received a low power testing license in June 1981).

3.

Corrective Steps Which Have Been Taken and the Results Achieved The PORVs were properly rewired and satisfactorily tested upon discovery of the error.

4.

Corrective Steps Which Will Be Taken To Avoid Further Violations Since unit 2 has received an operating license, all modifications are controlled by Administrative Instruction (AI) 19, " Plant Modifications".

This condition is considered an isolated case and, since the construction procedur.cs are no longer utilized for plant modifications, no additional corrective action is deemed necessary.

5.

Date When Full Compliance Will Be Achieved Full compliance was achieved on 04/05/84 when the FORVs were satisfactorily tested.

Item 3 (328/84-11-03) 10 CFR 50, Appendix B, Criterion XVII, " Quality Assurance Records", as implemented by the licensee's approved QA program (Topical Report TVA-TR75-1) section 17.2.17 requires that records of modifications and tests be compiled, stored, and retrievable.

Contrary to the above, the licensee failed to retrieve records showing evidence of modification (required by NCR MEB 79-10. " Control Loop Bistables Fail to Undesirable Po'ition on Loss of Power", and implemented by modification ECN 22-78) s or post-modification testing on a unit 2 PORV control circuit (PS68-336 which affects PCV 68-340).

This is a Severity Level IV Violation (Supplement I). This violation applies to unit 2 only. - -

< 3.;

c -

TVA Response.

.j 1.

Admission or Denial of the Alleged Violation u

TVA admits the violation occurred as stated.

2.

Reasons for'the Violation if Admitted.

The controlIcirctiitry modification was _ scheduled to be performed on the

-unit 2 pressurizer: power operated relief valves.before.an operating -

~

license being' issued.. The as-constructed drawings were used as documentation of the plant <i"stillation when systems, components, or equipment were.

Ltransferred from the Construction organization to the, Nuclear Power organi-zation. >The cause of this violation may have been a failure to include

? adequate details-in the as-constructed drawings, but the exact cause has S

not been. identified because,of the approximate three-year-time period since contruction proceduresihave been used (unit 2 received a low power testing 1

license,in June 1981).

'3.'

Corrective Steps Which Have Been Taken and the Results Achieved

-The PORVs' ere' properly rewired and satisfactorily tested upon discovery of the error.

- i

.4.. Corrective Steps Which Will Be Taken*To Avoid Further Violations

~

.Since unit 2 has received an operating license, all modifications are controlled ~by Administrative Instruction (AI) 19, " Plant Modifications".

This condition is. considered an isolated case and, since the construction procedures are no longer utilized, no additional corrective actions are

deemed'necessary.

1 5

Date When Full Compliance Will Be Achieved

Full: compliance was achieved on 04/05/84 when the PORVs.were satisfactorily tested.

Item 4 (328/84-11-04).

E1O CFR 50, Appendix B, Criterion XI as implemented by the licensee's approved QA' program '(Topical Report TVA-TR75-1) section 17.2.11, " Test Control", requires that. testing be performed to demonstrate that critical structures, systems,-

and components (CSSC) will perform satisfactorily in' service a'nd that modifi-

. cations be' tested in'accordance.withithe original design and testing' require-

.ments or acceptable alternatives.'

Contrary to the' above, a CSSC modification was not tested for satisfactory -

. performance.in that an Engineering Design modification-(ECN 22-78) on the pressurizer. power operated relief valve (PORV) ' control circuit was not required -

to be tested for the fail-safe' portion of the modification by the preoperational' i test procedure W-1.2A, " Reactor Coolant System Functional Test".

~

- This fis _a Severity Level IV Violation (Supplement I). This violation applies

to unit;2 only.

4.

i

~

MN e-m

~

o C

.' /*

TVA Response 1.

Admission or Denial of the Alleged Violation TVA admits the violation occurred as stated.

2.

Reasons for the Violation if Admitted The cause of this violation has been determined to be personnel failing to incorporate these additional test requirements into the preoperational test.

3.

Corrective Steps Which Have Been Taken and the Results Achieved Preoperational test personnel have been instructed in the importance of ensuring all test requirements are included in future post-modification tests.

4.

Corrective Steps Which Will Be Taken To Avoid Further Violations Since the preoperational test will not be utilized further and this condition is considered an isolated case, no further corrective action is deemed necessary.

5.

Date When Full Compliance Will Be Achieved Full compliance was achieved on 04/06/84 when the PORVs were satisfactorily tested and when personnel were reinstructed.

Item 5 (328/84-11-02) 10 CFR 50, Appendix B, Criterion V as implemented by the licensee's approved QA program (Topical Report TVA-TR75-1) section 17.2.5, " Instructions, Procedures, and Drawings", requires that activities affecting quality be accomplished in accordance with documented drawings of a type appropriate to the circumstances.

Drawings 45N668-1 and D8059895B are two drawings showing the wiring of the power operated relief valve (PORV) bistable, pressure switches associated with the auxiliary control loops.

Contrary to the above, on March 31, 1984, activities affecting quality were not accomplished in accordance with appropriate documented drawings in that maintenance on the auxiliary control loop PORV bistable pressure switches was performed using only drawing 45N668-1, resulting in miswiring correctly wired pressure switches.

This is a Severity Level IV Violation (Supplement I). This violation applies to both units.

e e

TVA Respwse 1.

Admission or Denial of the Alleged Violation TVA admits the violation occurred as stated.

2.

Reasons for the Violation if Admitted The cause of this violation has been determined to be a personnel error in failing to obtain and review all applicable available drawings.

3.

Corrective Steps Which Have Been Taken and the Results Achieved Training was conducted to remind Instrument Maintenance personnel to obtain and review all available applicable drawings during maintenance and modifications.

4.

Corrective Steps Which Will Be Taken To Avoid Further Violations Instrument Maintenance procedures were revised to provide details on the PORV wiring configuration to prevent future confusion. An additional requirement was included in AI-25, " Drawing Control After Unit Licensing",

to require that all discrepancies found between as-constructed drawings and plant features be brought to the attention of the shift technical advisor as soon as practical. The STA will evaluate the discrepancy and notify plant management of those differencies which are determined to have safety tmpact.

5.

Date When Full Compliance Will Be Achieved Full compliance was achieved on 04/12/84 when Instrument Maintenance personnel were reinstructed on the importance of reviewing all applicable drawings.

..