Provides Results of Supplemental Environ Testing Completed for Cable Mfg by Brabd Rex & Supplied to Util Under Contract 80K6-825419.Results Demonstrate That Installed Cable Capable of Performing Intented Safety Function
ML20095E467
Person / Time
Site: Browns Ferry  
Issue date: 04/21/1992
From: Zeringue O
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9204270451
Download: ML20095E467 (3)


Text

a-m _

1 e

sn.we va w,uu% n w~ e a 3 mu

+.axn APR 211992 4

O J 'ne'Zeangue fg 7c we nes *

%, r em e, v o r gy 4

?:y f*- A *J V

U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Vashington, D.C.

20555 Gentlemen:

In the W tter of

)

Dcektt Nos. 50-259 Tecnesnee calley Authority

)

50-260 L

50-296 BROWNS FERRY NUOLEAR PLANT (BFN) - UNITS 1, 2, and 3 - BRAND REX CABLE.-

ENVIRONMENTALLY QUALIFIED LIFETIME K

Re"crencea*

1.

TVA to NRC letter date<1 October 4, 1990, " Revision to the Cable Xnsta11ation Issues Supplemental Report -

Cable Pr11by" 2.

TVA to NRC letter dated November 21, 1991, " Watts Bar Nuclear Plant, Units 1 and 2 - Cable Issues Corrective Ac. tion Plan (CAP) - Transmi;tal of University of Connecticut Report for the Resolution of the Pullby 18849" 3.

7VA to NRC letter dated January 23, 1991, " Brand Rex Caale" This letter provides NRC with the results of supplemental environmental testing which has been completed for cable manufacturw by Brand Rex and supplied to TVA undst contract T.,.1mber 80K6-825419. Cable supplied under e

this cont.cact has been Installed in-10 CFR 50.49 circuits at DFN. The a

results of this testing deruonstrate that the installea cable is capable of performing-its intended safety function for the 40-year design life of r

the plant, e

8 92C42704bi 920421 PDR.ADCCK 05000239

.),

P' pon

{

b kh

~

-- ~.

- - - = -..-

l 2

't U. S. Nuclear Regulatory Commleaton AF9 2 t 1992 DAGX919MH2 1

As part of the resolution of cable installation issues at BFN, in situ DC high potential tests were conducte6 on a number of cables. During the performance of these tests which are described in Reference 1, one Brand Rex cable failed the test acceptance criteria. Subsequent to thu BFN tests, cables from the aame contract at Watts Bar Nuc. lear Plant experienced siini'.ar failures. The ialled BFN cable was sent to the University of Connecticut's (UCONN) Electrical Insulation Research Center for furthe evaluation. The UCONN analysis of this cable indicated that the hi-pot test failure was isolated in nature and was due to the presence of stypically large inorganic contaminants in the cable insulation. The UCONK test report was provided to NRC by Reference 2.

In Referenne 3 TVA providt:d NRC with the results of an engineerin; evaluation which concluded that the BrarA 1:ex cable in question van capable of performing its intended safety function for at least one cycle. We also stated that additional testing would be per formed to verify the qualification of the Brand Rex cable for the life of the plant.

SUPPLEMENTAL TEST RE ElJE t

The environmental qualification of this cable is based upon generic

- IEEE-383, 1974 parameters. TVA has completed additional tenting to verify _the qualliication of Brand Rex cable fcr the design liie of the plant. Environmental parameters were chosen which bound the application of these cables at BFN. The cable maintained its rated current and voltage during the 30-day accident simulation test (LOCA) after the cable hsd been preconditioned to the equivalent of 40 years life plus accident radiation. The qualification of this cable is documented in the Environmental Qualificattor. Documentation Package.

EtRREX Based on the results of the tests performed, the ab-ility of the cables to perform their intended safety function for a quallfled life of 40 yects is unaffected by the insuletion anomalica peeviously identified.

-m

3 g

U.S. Nuclear hegulatory Commission

  • kPR 21 1992

~

If you have any questions, please telephone R. R. Baron, BFN Site Licensing Manager, et (205) 729-7566.

Sincerely, 3

-l

^Y hk(fbb ]

0.0 Zeringue cca NRC Resident Inspector Browns Ferry Nuclear Plant Route 12, Box 637 Athens, Alabama 35611 Mr. Thierry M, Ross, Project Manager U.S. Nuclear Regulatory Commission One White Flint, North 11555 Rockville Pike Fockville, Tarfland 20852 tir. B. A. Wilson, Project Chief U.S. Nuclear Regulatory Commission Region II 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323 6

k

.