INSTRUMENTATION TABLE 3.3-7 o
SEISMIC MONITORING INSTRUMENTATION MINIMUM MEASUREMENT INSTRUMENTS INSTRUMENTS AND SENSOR LOCATIONS RANGE OPERABLE 1.
Triaxial Time-History Accelerographs System, including the following components:
a.
Reactor Building Foundation Mat 0.1 to 40 Hz Accelerometer 0.01 to 1.0g I
b.
Reactor Building Ring Girder 0.1 to 40 Hz Accelero' meter 0.01 to 1.0g 1
x c.
Reactor.Sullding Foundation Mat 1 to 10 Hz Trigger 0.005 to 0.02g la 2.
Triaxial Peak ?::: h r:;h:
1 Acc ate goGR A PM5 l
a.
, Side of Steam Generator 0-32 Hz
-5g to +5g 1
k"..;;.riar %7,. Lin b.
0-32 Hz w"vWon Sarsry Jusc riow LNs
-5 to +5g 1
c.
RHR System Heat Exchanger 0-20 Hz
-2g to +2g 1
3.
Triaxial Seismic Switches a.
Reactor Building Foundation Mat 0.1 to 30 Hz 0.01 to 0.25 g la 4.
Triaxial Response-Spectrum Recorders a.
Reactor Building Foundation Mat (1) 1*
b.
Steam Generator Support (1) 1 c.
Intermediate 81dg., Elev. 463' (1) 1 d.
Auxiliary Bldg. Foundation (1) 1
^
With control room indication and/or alarm.
(1) Range varies for the multiple elements of the instrument, i.e., 1.6g at 2 Hz, log at 5 Hz, 34g at 10 Hz, 12g at 16 Hz.
SU MER - UNIT 1 3/4 3-48 9407340298 840724 PDR ADOCK 05000395 P
,~s.
o s
_ \\
' \\ 'N
,j
.y.-
]!
INSTRUMENTATIO_N e
TABLE 4.3_-4
-SEISMICMGMITOMNGINSTRUMENTATIONSURVCILLANCEREQUIREMENTS n <
N ANALOG CHANNEL
' CHANNEL CHANNEL OPERATIONAL INSTRUMENTS AND SENS0it LOCATIONS' CHECK CALIBRATION TEST
- 1. Triaxial-Time-Hist'ory Accelerographs,-
including the following' components: '
- a. Reactor, Building Foundation Mat M
R SA Accelerometer
- b. Reactor Bui.1 ding Rir.g Girder M
R SA Accelerom'eter t
- c. Reactor Bd 1 ding Foundation Mat M
R SA Trigger *-
- 2. Triaxial Peak Accelerographs
- a. Side of Steam Generator NA R
NA "ra NA R
NA
- b. Accum:;arim' Nr;;c !.in-umron smTv bec rnow lips
- c. RHR Systen, Neat Exchanger NA R
NA
- 3. Triaxial Seismic Switches
- a. Reactor Building Foundation Mat
- M R
- 4. Triaxial Response-Spectrum Recorders
- a. Reactor Building Foundation Mat
- M R
- b. Steam Generator Support NA R
NA
- c. Intermediate Bldg. Elev. 463' NA R
NA
- d. Auxiliary Bldg. Foundation NA R
NA With control room indications and/or alarm.
l SUMER - UNIT 1 3743-49 i