ML20093D435

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Leaking Check Valves.Initially Reported on 840206.Incomplete Special Instruction Sheets Added to Turnover Exception List.Traveler Procedure Revised to Clarify Methods to Identify & Track Work
ML20093D435
Person / Time
Site: Wolf Creek 
Issue date: 09/21/1984
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Hunter D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
KMLNRC-84-166, NUDOCS 8410110240
Download: ML20093D435 (2)


Text

J4 KANSAS GAS AND ELECTRIC COMPANY 6

T>4i ELECTAC COMPANY OLENN L MOESTER vKtPatsiotNt asvCLean September 21, 1984 Mr. D.R. Hunter, Chief

- f

}[

Reactor Project Branch 2

_d i

U.S. Nuclear Regulatory Commission

}(

Region IV g g p.

. ((

611 Ryan Plaza Drive, Suite 1000 a; )'

I Arlington, Texas 76011 q g

.g i

KMLNRC 84-166 Re:

Docket No. STN 50-482 Ref: Interim Report KMLNRC 84-027 dated 3/7/84 from GLKoester, KG&E, to EHJohnson, NRC Subj: Potential 10CFR50.55(e) Final Report -

Leaking Check valves

Dear Mr. Hunter:

This letter provides the final report on a potential J OCFR50.55(e) con-cerning leaking check valves at Wolf Creek Generating Station. This matter was initially reported by Mr. Otto Maynard of Kansas Gas and Electric Company (KG&E) to Mr. Michael Murphy of the Nuclear Regulatory Commission, Region IV, on February 6,1984.

While filling the primary system it was noted tha.t a check valve in the high pressure coolant injection system was leaking. An investigation into this matter revealed that previous work done on the valve had not been completed and was not identified on the Turnover Exception List. This prompted a documentation review to determine if other valves were affected in a similar manner. The documentation review of approximately 900 valves contained in the primary hydro test boundary revealed nine valves with incomplete work which were not identified on the Turnover Exception List.

Although the incomplete work was not included on the Turnover Exception List, the traveler could not have been closed until the Special Instruction Sheets were completed. Therefore, the incomplete work in question could not have remained incomplete.

'Ib remedy this situation, the following corrective actions were taken:

1.

A review of Special Instruction Sheets for ASME, ANSI B31.1 Critical and Special Scope piping travelers previously transmitt ed to the Combined Review Group for 8410110240 840921 DR ADOCK 05000 O

IQ 201 N. Market -Wichita, Kansas - Mail Address: RO. Box 208 i Wichita, Kansas 67201 - Telephone: Area Code (316) 261-6451

4*

Mr. D.R. Hunter KMLNRC 84-166 September 21, 1984 review was completed by Construction Completion.

' Incomplete Special Instruction Sheets were added to the Turnover Exception List.

2.

The Project Piping Engineer revised the traveler procedure to clarify and strengthen the methods for identification and tracking of incomplete work or documentation. Additional training was given to the engineers who prepare the Turnover. Exception List and the Traveler Turnover Record.

3.

The Construction Performance Group reviewed the inter-face between Construction Startup Support and KG&E S tartup. It was concluded that adequate procedures exist to identify, control and track incomplete work items.

These corrective actions -ensure that inec.nplete work on valves will be identified, controlled and tracked. If you have any questions concerning this subject, please contact me or Mr. Otto Maynard of my staff.

Yours very truly, DU l

Glenn L. Koester Vice President - Nuclear GLK:bb xc:RCDeYoung PO'Connor HBundy b