Final Deficiency Rept Re Stainless Steel Pipe Welded W/O Filler Matl.Initially Reported on 840120.Subj Piping Not Installed Where Design Hoop Stresses Would Exceed 85% of Allowable Stresses.No Further Action Necessary
ML20093C781
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 09/21/1984
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Hunter D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
IEB-79-03, KMLNRC-84-163, NUDOCS 8410100715
Download: ML20093C781 (2)


Text

_ _ _

KANSAS GAS AND ELECTRIC COMPANY THE ELECTSVC COMPANY OLENN L 8L O E S T E ft v.c s pers.ces,. seucteam s

September 21, 1984 Mr. D.R. Hunter, Chief Reactor Project Branch 2 U.S., Nuclear Regulatory Commission g

c;,y7gg Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 f)

KMLNRC 84-163 Re:

Docket No. STN 50-482 l

Ref:

Interim Report KMLNRC 84-018 dated 2/17/84 l

from GLKoester, KG&E, to JEGagliardo, NRC Subj: Potential 10CFR50.55(c) Final Report -

Longitudinal Weld Defects l

Dear Mr. Ilunter:

This letter provides the final report on a potential 10CFR50.55(e) i concerning stainless steel pipe welded without filler material. This l

matter was initially reported by Mr. liarold Chernoff of Kansas Gas and l

Electric Company (KG&E) to Mr. Michael Murphy of the Nuclear Regulatory l

Commission, Region IV, on January 20, 1984.

l The potential for weld defects in pipe welded without filler material l

was first identified in I&E Bulletin 79-03, " Longitudinal Weld Defects in ASME SA-312, Type 304 Stainless Steel Pipe...".

As a result of this Bulletin, all SA-312, Type 304 stainless steel pipe at Wolf Creek

(

Generating Station was downgraded for use only in non-safety-related f

systems. IIowever, a few instances were discovered where this material

{

had been used in safety-related applications.

{

Bulletins 79-03 and 79-03A indicated that piping of the type described could be utilized in locations where design hoop stress did not exceed l

85% of the hoop stress allowed by ASME code. An investigation into this matter revealed that none of the subject piping was installed where design hoop stresses would exceed 85% of the ASME Code allowable stresses. In addition, all Constructor procured SA-312, Type 304 stainless steel pipe was identified and removed from the !! eat Code Printout as ASME pipe class material to prevent future inadvertent use.

84101%0h 2

PDR A PDR i6 q s

201 N. Markst. -Wictuta, Kansas - Mad Address: PO. Box 208 l b%chita. Kansas 67201 - Telephone: Area Code (316) 261-6451

+.

e Mr. D.R. Hunter KMLNRC 84-163 September 21, 1984

' As a result of the aforementioned activities, KG&E deems that no further action is necessary. If you have any questions concerning this matter, please contact me or Mr. Otto Maynard of my staff.

I'-

Yours.very truly, r$N I

Glenn L. Koester Vice President - Nuclear I.

I f

l GLK bb

-)

xc RCDeYoung i

PO'Connor HBundy i