ML20092M518

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Improper Installation of 3 H Rated (Class a) Hollow Metal Fire Door Frames.Initially Reported on 840525.Existing Combustible Caulking Replaced on All Class a Hollow Metal Fire Door Frames W/Approved Sealant
ML20092M518
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 06/21/1984
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Johnson E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
KMLNRC-84-097, KMLNRC-84-97, NUDOCS 8407020280
Download: ML20092M518 (1)


Text

P KANSAS GAS AND ELECTRIC COMPANY THE ELECTAiC COMPANY CLENN L.MOES'ER voce ratsioENT muCLEAR June 21, 1984 Mr. E.H. Johnson, Acting Chief Reactor Project Branch 2 h @ ))]7] )

U.S. Nuclear Regulatory Commission j

Region IV 611 Ryan Plaza Drive, Suite 1000 JN 2 5884 Arlington, Texas 76011 j

KMLNRC 84-097 Re:

Docket No. 50-482 Subj: Final 10CFR50.55(e) Report - Hollcw Metal Fire Door Frame Installation

Dear Mr. Johnson:

The purpose of this letter is to provide a final report pursuant to 10CFR50.55(e) concerning the installation of three-hour rated (Class A) hollow metal fire door frames at Wolf Creek Generating Station.

This matter was initially reported to Mr. William Johnson of the

~

Nuclear Regulation Commission, Region IV, by Mr. Otto Maynard oi Kansas

';as and Electric Company (KG&E) on May 25, 1984.

During a routine inspection of smoke detectors, a damaged seal was discovered between a Class A fire door frame and a three-hour rated fire wall. Further investig Lion revealed that the frame was sealed to the wall with two beads of combustible caulking (Peacoa Unicrylic 60 or GC9).

It was later determined that the same caulking had been used on other Class A fire doors. The Architect / Engineer evaluated this concern and determined that this caulking did not represent a significant safety concern. However, KG&E has elected to replace the existing combustible caulking surrounding all Class A hollow metal fire door frames with an approved flame retardent adhesive sealant (Dow Corning RTV 96-081). This activity will be completed prior to fuel load.

If you have any questions concerning this subject, please contact me or Mr. Otto Maynard of my staff.

Yours very truly, MA[

b 8407020280 840621 PDR ADOCK 05000482 S

PDR GLKabb xc: PO'Connor HBundy ll/

RCDeYoung 0

201 N. Market ~ WicNta, Kansas - Mail Address: RO. Box 208 I Nchita, Kansas 67201 - Telephone: Area Code (316) 261-6451