1 i
psnay je UNITED STATES l
8(-
g NUCLEAR REGULATORY COMMISSION e
)
E, W ASHINGTON. D. C. 20555 a,,
a 4...*
SAFETY EVALVAT10N iY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO.134 TO FACILITY OPERATING LICENSE NO. DPR-29 AND AMENDMENT NO.129 TO FACILITY OPERATING LICENSE NO. DPR-30 COMM0NWEAllH EDISON COMPANY A,gg N
IOWA-Itt!NOIS GAS AND ELECTRIC COMPANY CUAD CITIES NUCLEAR POWER STATION, UN115 1 AND 2 DOCKET N05. 50-254 AND 50-265
1.0 INTRODUCTION
By letter dated October 11, 1991, Commonwealth Edison Company (CECO, the licensee) proposed changes to the Technical Specifications for Quad Cities Nuclear Power Station, Units 1 and 2.
However, in its letter dated December 13, 1991, the licensee withdrew the first two proposed changes. The NRC approved the request for partial withdrawal by letter dated January 14, 1992 (57 FR 2795.) The remaining proposed change adds two new sections:
Radiation Protection Program and High Radiation Area.
2.0 EVALUATION The first of the two new sections is Section 6.11, Radiation Protection Program, which is replacing Section 6.2.B.
The new section is consistent with Section 6.11 of the Standard Technical Specifications (STS) and with the section it is replacing. Thus, the change is administrative, and we find it acceptable.
The second section being added is Section 6.12, High Radiation Area. Quad Cities Station currently complies with 10 CFR 20.263(c)(2) and (4) hy requiring that all areas greater than 100 mrem per hour be locked, except during periods of access, or by providing direct surveillance to prevent unauthorized entry.
10 CFR 20.203(c)(5) allows licensees to apply for approvalofmethodsnotincludedinparagraphs(c)(2)and(c)(4)for controlling access to high radiation areas. The staff considers Section 6.12 of the STS to be an acceptable method for controlling high radiation i
areas. CECO has nroposed a new Section 6.12 entitled "High Radiation Area,"
which is identical to the STS with two exceptions.
Section 6.12.c of STS uses the title " Health Physicist." The licensee has changed this to " Health Physics" which is the comparable function at Quad Cities Station. We find this acceptable.
9202260354 920214 PDR ADOCK 05000254 p
. The'other change from the STS involves the distance from the source for taking the dose rate measurement. The STS say 18 inches (45 cm), while the licensee proposes 30 cm (11.8 in). The licensee's proposed distance is more conservative than the distance in the S15 and is the distance specified in the revised version of 10 CFR 20, published May 21, 1991 (56 FR 23393). Thus, we find it acceptable to use this distance in Section 6.12 for Quad Cities Station.
3.0 STATE CONSULTATION
in accordance with the Commission's regulations, the Illinois State official was notified of the proposed issuance of the amendments, The State official had no comments.
4.0 ENVIRONMENTAL CONSIDERATION
The amendrents change i, requirement with respect to the installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20. The NRC staff has determined that the amendments involve no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant
-increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendments involve no significant hazards consideration, and there has been no public connent on such finding (56 FR 57693). Accordingly, the amendments meet the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). The amendments also involve changes in recordkeeping, reportirg or administrative procedures or requirements. Accordingly, with respect to these items, the amendments meet the eligibility criteria for categorical exclusion tet forth in10CFR51.22(c)(10).
pursuantto10CFR51.22(b),noenvironmentalimpact statement or environmental assessment need be prepared in connection with the issuance of the amendments.
5.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that:.(1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the commission's regulations, and (3) the issuance of the amendments will not be inimical to the common defense and. security or to the health and safety of the public.
Principle Contributor:
L. 01sian L "
Date: February 14, 1992