. - _ _ _ _ _

g.

Entegy Opecations,Inc.

~= ENTERGY o

u W. T. C ottle l'e b rua r y 13, 1992 U.S. Nuclear Regulatory Commission Mail Station P1-137 Washington, D.C.

20555 Attention:

Document Control Desk

Subject:

Grand Gulf fluclear Station Unit 1 Docket No. 50-416 License No. NPF-29 Monthly Operating Report GNRO-92/00015 Gentlemen:

In accordance with the requirement of Technical Specification 6.9.1.10, Entergy Operatiens is providing the Monthly Operating Report for Grand Gulf Nuclear Station Unit I for January 1992 (attachment).

If you have any questions or require additional inforn'ation, please contact this office.

Yours truly, w4

' Csuu, WlC/TKM/cg attachments: 1.

Operating Status 2.

Average Daily Power Level 3.

Unit Shutdowns and Power Reductions cc:

(See next page)

M00PJAN i i g

9202190189 920131 PDR ADOCK 05000416 R

pon

february 13. 1992 i

GNRO-92/00015 Page 2 of 3 cc:

Mr. D. C. Hintz (w/a)

Mr. J. L. Mathis (w/a))

Mr.R.B.McGehee(w/a Mr. N. S. Reynolds (w/a)

Mr.H.L. Thomas (w/o)

Mr. Stewart D. Ebneter (w/a)

Regional Administrator U.S. Nuclear Regulatory Comission Region 11 101 Marietta St., N.W., Suite 2900 Atlanta, Georgia 30323 Mr.P.W.O'Connor,ProjectManager(w/a)

Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Comission Mail Stop 13H3 Washington, D.C.

20555 i

M00PJAN-1

(

' to GNRO-92/00015 DOCKET NO.

50-416 s

DATE 01/0T/V2 COMPLETED BY L. F. Daughtery TELEPHONE (601)437-2334 OPERATING STATUS 1.

Unit Names GGNS UNIT 1 lotes:

2.

Reporting Period:

January 1992 3.

Licensed Thermal Power (IGT): 3833 MWT 4.

NameplateRating(GrossMWE): T372.5 MWE 5.

Design Electrical Rating (Net RR~e): 1250 MWE 6.

Maximum Dependable Capacity (Gross MRe): IT9TRWE

11WC, MaximumDependableCapacity(NetMWe)(: Items Number 3 Through 7) Since Last Report.

7.

If Changes Occur in Capacity Ratings 8.

Give Reasons:

N/A 9.

Power Level To Which Restricted, In Any (Net HWe):

N/A

10. Reasons for Restrictions, if Any:

N/A This Month

,Yr to Date Cumulative

11. Hours in Reporting Period 744 744 63,826
12. Number of Hours Reactor Was Critical 571 571 50,768.1
13. Reactor Reserve Shutdown Hours 0

0 0

14. Hours Generator On-Line 520 520 48,570.4
15. Unit Reserve Shutdown Hours 0

-D 0

16. Gross Thermal Energy Generated (MWH) 1,869,517~

1,869,517 IF'59W

17. Gross Electrical Energy Generated (MWH) 600,275' 600,275 53.170,385
18. Net Electrical Energy Generated (MWH) 572.500 572,500 50.833,215
19. Unit Service Factor 69.9 69.9 78 8
20. Unit Availability Factor 69.9 69.9 78.8
21. Unit Capacity Factor (Using MDC Net) 6 7. 3__

67.3 74.9

22. Unit Capacity factor.(Using DER Net) 61.6 61.6 67.9
23. Unit forced Outage Rate 30.1 10 3 6.8
24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

8egin Refuelino Outage - 5 on 04/17/92 for an estimated duration of 46 days.

25. TfTiv:~Down At End of Report Period.

Estimated Date of Startup:

NA

26. Units in Test Status (Prior to Commercial Operation).

Forecast Achieved INITIAL CRITICALITY 08/18/82 INITIAL ELECTRICITY T07707BT COMMERCIAL OPERATION 07/01/85 M00PJAN/SCMPFLR J

' to GNRO-92/00015 DOCKET NO.

50-416 UNIT 1

DATE 01/07/92 1

3 MONTH January 1992 DAY AVERAGE DAILY POWER LEVEL OAY AVERAGE DAILY POWER LEVEL (MWe-Net)

(MWe-Net) 1 0

17 1205.6 2

0 18 1201.2 3

0 19 1208.9 4

0 20 1204.7 5

0 21 1199.2 6

0 22 1184.8 7

0 23 1190.5 8

0 24 1197.5 9

0 25 1153.5 10 204.1 26 1192.1 11 840.6 27 1192.2 12 888.9 28 1189.2 2

13 712 29 1187.5 14 1088. 1 30 1189.8 15 1174.6 31 1186.4 16 1210.9 M00PJAN/SCMPFLR

Attach:::ent 3 to GNRO-92/00315' l

UNIT SHUTDOWNS AND P7 DER REDUCTIDNS DOCKET NO.

50-416 UNIT MAME 1

DATE 01/07/92 COMPLETED BY L. F. Daughtery TELEPHONE 601-437-2334 REPORT MONTH January 1992 l

l l

l l

l Method of j Licensee l l

l Cause & Coriective l

l No. J. Date l Type jDuration) Reason l Shutting Downl Event l System lCoc:ponent i Action To l

l' l

l (1) l Hours l

(2) l Reactor l Report #

l Code l Code l

Prevent Recurrence l

I l

I l

l l

(3) l l

(M l

(5) l (C&CA)

I l

I I

I i

l I

I i

i I

l91-101/01/92[

F l 224 l

A l

4 l

N/A l

AD l P

l Continued outage fro::; last month. l l015 l l

l l

l

[

l l

iForced shutdown for Recirc Pump l

l l

l l

l l

l l

l l *B' shaft replace:nent.

1 1

I I

i i

i i

i i

i i

l 1

i I

i i

I i

i i

i UNIT SHUTDOWNS AND POWER REDUCTIONS 1

2 3

4

-F: Forced Reason:

Method:

Fxhibit G - Instructions 5:-Scheduled

.A-Equipment Failure 1-Manual for.% ration of Data (Explain) 2-Manual Scram Entry Weets for Licensee B-Maintenance or Test 3-Automatic Scram Event Report (LER)

C-Refueling 4-Continued File (NUREG-0161)

D-Regulatory Restriction 5-Reduced load E-Operator Training &

6-Other Licensing Examination F-Administrative 5

Exhibit 1-Same Source G-Operational Error (Explain)

H-Other (Explain)

MOOPJAN/SCMPFLR L--