Advises That Eight Full Loop Tests to Demonstrate Step Loading Capability & 61 Addl HPCS Diesel Generator Tests to Demonstrate Steady State Performance Will Be Performed as Result of 840427 Meeting in Bethesda,Md
ML20092A740
Person / Time
Site: Clinton Constellation icon.png
Issue date: 06/13/1984
From: Herborn D
ILLINOIS POWER CO.
To: Schwencer A
Office of Nuclear Reactor Regulation
References
0982-L, 982-L, U-0715, U-715, NUDOCS 8406190335
Download: ML20092A740 (1)


Text

1 U 0715 0982-L L30-84 (06 -13 )L

'/LLINDIS POWER COMPANY CLINTON PCMER STATION P.O. BOX 678 CLINTON ILLINOIS 61727 June 13, 1984 J

Docket No. 50-461 Director of Nuclear Reactor Regulation Attention:

Mr. A. Schwencer, Chief Licensing Branch No. 2 Division of Licensing U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Subj ect: Clinton Power Station Unit 1 HPCS Diesel Generator Qualification Testing

Dear Mr. Schwencer:

As a result of the April 27. '9S4 meeting in Bethesda, MD on this issue, w<3 agree that the 99% relie ality of the HPCS diesel generator will be deuonstrated for the Clinton equipment in satisfaction of the requirements of Regulatory Guide 1.108 and the intent of NEDO 10905.

As agreed upon, the following combination of tests will be performed:

8 full loop tests to demonstrate the step loading capability of the HPCS diesel generator and the performance of the HPCS pump motor. (Applicable test data vill also be supplied by June 30, 1984 to substantiate the HPCS diesel generator reliability as demonstrated by prior testing).

61 additional HPCS diesel generator tests loaded to the grid at close to the HPCS pump motor load to demonstrate steady-state performance.

Please contact us if you have any questions regarding the above test plan.

Sincerely yours, k;;"

Daniel I. Herborn 846%{5840613 Director - Nuclear Licensing 05000 and Configuration A

Nuclear Station Engineering DIH/ lam DIH/DI cc:

B. L. Siegel, NRC Clinton Licensing Project Manager J. Lazevnick, NRC PSB

\\

J. E. Knight, NRC PSB NRC Resident Office j0 Illinois Department of Nuclear Safety i

--