Forwards Request for Exemption from Branch Technical Position BTP-CMEB 9.5-1 for Control Panels C43 & C44. Use of Smoke Detection/Halon Suppression Sys for safety-related Equipment Rooms Proposed
ML20091K965
Person / Time
Site: Midland
Issue date: 05/30/1984
From: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML20091K969 List:
References
29803, NUDOCS 8406070264
Download: ML20091K965 (3)


Text

, 4

  • O

@ Consun1ers POVrer James W Cook Vice President - Projects, Engineering and Construction General offices: 1945 West Parnell Road, Jack,on, MI 49201 e (517) 788-0453 May 30, 1984 Mr Harold R Denton Office of Nuclear Reactor Regulation Division of Licensing US_ Nuclear Regulatory Commission Washington, DC 20555

' MIDLAND ENERGY CENTER PROJECT -

MIDLAND DOCKET NOS 50-329, 50-330 FIRE PROTECTION EXEMPTION REQUEST FROM BRANCH TECHNICAL POSITION BTP-CMEB 9.5-1 FILE B9.5.1, 0505.16 SERIAL 29803 REFERENCES (1) NRC October 26, 1983 MEETING

SUMMARY

DATED 11/9/83 (2) NRC January 26, 1984 MEETING

SUMMARY

DATED 3/27/84 ENCLOSURE REQUEST FOR EXEMPTION FROM BRANCH TECHNICAL POSITION BTP-CMEB 9.5-1 FOR CONTROL PANELS C43 AND C44 In meetings held between Consumers Power Company (CPCo) and the NRC Staff, documented in References 1 and 2, fire protection of control panels containing redundant safe shutdown components was discussed. These discussions encom-passed those safe shutdown pancis within the main control room, the control room peripheral rooms, and the safety-related equipment rooms. As part of the presentation of the Midland control room fire analysis, we identified that the balance of plant-engineered safety features panels, C43 and C44, contained redundant safe shutdown circuits that were susceptible to postulated fires.

Recognizing the need for a positive means to protect these panels from postu-lated fires, we presented a brief description of a smoke detection /Halon suppression system incorporating cross-zoned smoke detection for the safety-related equipment rooms and panels C43 and C44. As previously discussed, we are requesting an exemption from Branch Technical Position BTP-CMEB 9.5-1 for control panels C43 and C44. The enclosed report provides the details of the exemption request and the corresponding smoke detection /Halon suppression system for the safety-related equipment rooms and associated C43 and C44 panels.

In order to meet the guidance of Branch Technical Position (BTP) CMEB 9.5-1, separation of redundant safe shutdown trains with no intervening combustibles, separation by rated fire barriers or electrical isolation of circuits would be necessary. However, due to cabinet construction and physical constraints, the use of fire barriers or separation of cabinets is not considered practical.

t

[ OC0584-0217A-MP04 8406070264 840530 PDR ADOCK 05000329 e

F PDR

A.

2 Electrical isolation would resolve concerns associated with the output con-tacts of the C43 and C44 panel circuits. However, it would not address the concerns associated with the emergency core cooling actuation system sequenc-er, loss of offsite power sequencer and the diesel generator start logic modules. We, therefore, intend to provide a highly reliable smoke detection /Halon suppression system to protect the redundant safe shutdown equipment in the C43 and C4 cabinets.

Since the installation of a Halon system does not meet the guidelines of BTP CMEB 9.5-1, we are hereby requesting an exemption from the BTP and alternately proposing to use a smoke detection /Halon suppression system to protect the safety-related equipment rooms and associated C43 and C44 panels. The en-closed report provides the basis for our exemption request. Based on the probability of a fire in the safety

  • elated equipment rooms and the high reliability of the smoke detection /Halon suppression system, the probability of a fire damaging both redundant trains _gf the C43 and C44 cabinets has been conservatively calculated to be 2.3 x 10 per reactor year. We, therefore, believe a fire internal or external to these panels will not compromise our ability to safely shutdown the plant.

The enclosed report and exemption request is provided for the Staff's evalua-tion in preparation for future meetings. In the interim, we would be pleased to discuss any aspect of the enclosed evaluation with your Staff.

JWC/CLH/RLT/bjw CC JGKeppler, Administrator, Region II DSHood, US NRC, Licensing Branch #4 RJCook, Midland Resident Inspector OC0584-0217A-MP04

, s' .

4 CONSUMERS POWER COMPANY Midland Units 1 and 2 Docket No 50-329, 50-330 Lettar Serial 29803 Dated May 30, 1934 At the request of the Commission and pursuant to the Atomic E tergy Act of 1954, and the Energy Reorganization Act of 1974, as amended and the Commis-sion's Rules and Regulations thereunder, Consumers Power Company submits its exemption request to BTP CMEB 9.5-1, Section C5.6(2) for Safety Related Equipment Room cabinets C43 and C44.

CONSUMERS POWER COMPANY By . I L J es W Cook, Vice President '

Proj ts, Engineering and Construction Sworn and subscribed before me this 4 day of June, 1984 hMdedNotary Public ) ~

Jackson County, Michigan My Commission Expires September 8. 1984 OC0584-0217A-MP04