1 Cp&L Carolina Power & Light Company SERIAL: NLS-84-302 JIE.101984 Director of Nuclear Reactor Regulation Attention:

Mr. D. B. Vassallo, Chief Operating Reactors Branch No. 2 Division of Licensing-United States Nuclear Regulatory Commission Washington, DC 20555 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2 DOCKET NOS. 50-325 & 50-324/ LICENSE NOS. DPR-71 & DPR-62 REQUEST FOR ADDITIONAL INFORMATION NUREG-0737 ITEMS II.F.1.4/5/6

Dear Mr. Vassallo:

In a telephone conversation with your staff on May 15, 1984, Carolina Power &

Light Company (CP&L) was asked to provide additional information concerning our submittal of March 9, 1984 on NUREG-0737 Items II.F.1.4/5/6.

Specifically, historical calibration data for the new Brunswick-1 containment hydrogen and oxygen monitors was requested for the purpose of determining instrument setpoint stability (i.e., long-term drift). Attached is CP&L's response to this request. Should you have any further questions, please contact Mr. John S. Dietrich at (919) 836-6154.

Yours very truly,

/

^

tidenec w

l S. R mmerman Manager Nuclear Licensing Section MAT /cfr (309 MAT)

Attachment cc:

Mr. D. O. Myers (NRC-BSEP)

Mr. J. P. O'Reilly (NRC-RII)

Mr. M. Grotenhuis (NRC) 8407190335 840710 PDR ADOCK 05000324 P

PDR k

~.,.-r

(mADC output)

INST 6 DATE STATUS 1

3 4

4409-40 17-Sep-S3 LEFT 4.11 19.47 10.18 18.41 02-(div 1) 21-Dec-83 FOUND 3.94 18.83 9.92 17.86 DATA INST 4 DATE STATUS 1

2 3

4 4409-32 17-Sep-83 LEFT 4.09 19.11 9.03 19.02 H2 (div 1) 21-Dec-83 FOUND 4.10 19.38 9.14 19.49 DATA INST 6 DATE STATUS 1

2 3

4 4410-40 29-Dec-83 LEFT 4.11 19.36 10.14 18.38 02 (div 2) 14-Mar-84 FOUND 3.92 19.36 10.14 18.55 DATA INST 4 DATE STATUS 1

2 3

4 4410-32 29-Dec-83 LEFT 4.14 19.21 9.08 19.33 H2 (div 2) 14-Mar-84 FOUND 4.13 19.20 9.08 19.34 DATA INST 6 DATE STATUS 1

2 3

4 4409-40 21-Dec-83 LEFT 3.98 19.35 10.13 18.44 02 (div 1) 09-Feb-84 FOUND 4.01 19.05 10.02 18.07 DATA INST 6 DATE STATUS 1

2 3

4 4409-32 21-Dec-83 LEFT 4.05 19.04 9.01 19.00 H2 (div 1) 09-Feb-84 FOUND 4.10 18.99 9.00 18.99 I

1


,---,w

~-.--,--,,,----~~----,-----en, w

r o

% DRIFT E(found)-(left)3/.16 INSIt l'

2 3

4 4409-40 U2 (div 1)

-1.063

-4.000

-1.62d

-4.438 ZUHit !

INSit 1

2 4

4 440Y-32 H2 (div 1) 0.062 1.687 0.688 2.937

% DRIFT INST 4 1

2 3

4 4410-40 02 (div 2)

-1.188 0.000 0.000 1.063

% DRIFT INST 4 1

2 3

4 4410-32 H2 (div 2)

-0.062

-0.063 0.000 0.063

% DRIFT INST 4 1

2 3

4 4409-40 02 (div 1) 0.187

-1.875

-0.688

-2.313

% DRIFT INST 4 1

2 3

4 4409-32 H2 (div 1) 0.312

-0.313

-0.062

-0.063

AVG

% DRIFT INSTt DRIFT DAYS MONTHS PER MONTH 4409-40

-02 (div 1)

-2.531 95 3.17

-0.799 AVG

% DRIFT

' INST #

DRIFT DAYS MONTHS PER MONTH 4409-32 H2 (div 1) 1.344 95 3.17 0.424 AVG

% DRIFT INST 4 DRIFT DAYS MONTHS PER MONTH 4410-40 02 ('div 2)

-0.031 76 2.53

-0.012 AVG

% DRIFT INST 4 DRIFT DAYS MONTHS PER MONTH 4410-32 H2 (div 2)

-0.016 76 2.53

-0.006 AVG

% DRIFT INST #

DRIFT DAYS MONTHS PER MONTH 4409-40 02 (div 1)

-1.172 50 1.67

-0.703 AVG

% DRIFT INST #

DRIFT DAYS MONTHS PER MONTH 4409-32

-H2 (div 1)

-0.031 50 1.67

-0.019 i

i I