Preliminary AO-50-219/74-60:on 741122,during Surveillance Test,Sensor 1B11A2 on Isolation Condenser a Actuated at Value Exceeding Tech Spec Limit.Caused by Sensor Repeatability.Setpoint Accuracy Under Investigation
ML20090D841
Person / Time
Site: Oyster Creek
Issue date: 11/25/1974
From: Carroll J
JERSEY CENTRAL POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
AO-50-219-74-60, NUDOCS 8303030234
Download: ML20090D841 (4)


Text

- ,

t

,73 L, . ' ..J g % ,'

J To: James P. O'Reilly Directorate of P,cgulatory Operations -

Region I ' 'i 631 Park Avenue "'t _,

King of Prussia, Pennsylvania 19406

f From
Jersey Central Power S Light Company Oyster Creek Nuclear Generating Station Docket #50-219 Forked P.iver, New Jersey 08731

Subject:

Abnorrral Occurrence Report No. 50-219/74/60 The following is a preliminary report being submitted in compliance with the Technical Specifications, paragraph 6.6.2.

Preliminary Approval:

/

l h/t - ' ,f/ d7 11/25/74

[J.T. Carroll,Jr.[/ Date i

cc: Mr. A. Cianbusso,

$0fK050IIES sis 4 COPY SENT REGION. <a

y Initial Telephone \ . Date of '#

Repprt Yate: 11/22/74 Occurrence: 11/22/74 Initial Written Time of -

Report Date: 11/25/74 Occurrence: 1045 J

OYSTER CREEK NUCLEAR GENERATING STATION FORKED RIVER, NEN JERSEY 08731 Abnortal Occurrence Report No. 50-219/74/ 60 IDENTIFICATION Violation of the Technical Specifications, Tabic 3 . 1 . 1 .11. 2 ,

OF OCCURRE.NCE:

isolation condenser condensate high flow line. break sensor 1B11A2 was found to actuate at a value in excess of the Tech-nical Specification limit of 27 inches !! 20.

This event is considered to be an abnormal occurrence as de-fined in the Technical Specifications, paragraph 1.15B.

CONDITIONS PRIOR x Steady State Power Routine Shutdown TO OCCURRENCE: llot Standby Operation Cold Shutdown Load Changes During Refueling Shutdown Routine Power Operation Routine Startup Other (Specify)

Operation .

Power: Reactor,1903 ?Mt Electric, 665 MWe Flow: Recirc., 15.3 X 104 gpm Feed., 7.13 X 106 lb/hr Reactor Pressure: 1020 psig Stack Gas: 22,100 pCi/sce DESCRIPTION OF On Friday, Novedber 22, 1974, at approximately 1045, while CCCURRENCE:

perforning routine surveillance testing on the isolation condenser condensate high flow line break sensors, it was ob-served that sensor IB11A2 (located on the A isolation condenser) actuated at a value in excess of the Technical Specification limit of 27 inches !! 20. Tne complete condensate line break sensor surveillance results 5:ere as follows:

/

(,,)

(m..)

Abnormal.0ccurrence Page 2 Repc(t No. 50-219/74/60 Isolation Condenser A i Trip Reset Sensor (inches II20) (inches if20) 1B11A1 27 25 IB11A2 29 25 Isolation Condenser B Trip Reset Sensor (inches !!20) (inches II20)

IB11B1 26.5 25.5 1B11B2 27 26.5 The IB11A2 sensor was recalibrated and retested. The surveil-larce retest yicided a trippoint of 27 inches 1120.

APPARENT CAUSE Design Procedure OF OCCURRENCE: Manufacturer Unusual Service Condition Installation / Inc. Environnental Construction Component Failure Operator x Other (Specify)

The cause of this occurrence is sensor repeatability which is a recognized problem.

This event is considered to have no safety significance. Ilad ANALYSIS OF OCCU'IRENCE :

a condensate line high flow condition occurred requiring isolation of the A isolation condenser, the redundant sensor, IB11A1, would have actuated at the Technical Specification limit of 27 inches !! 20.

CORRECTIVE Setpoint accuracy and tolerante in not only these instruments ACTION:

but others as well is under investigation by Company and GPU personnel with the General Electric Company.

,n. (\

Abnormal Occurrence (,,,/ *

\)

Report ?;o. 50-219/74/60 ' Page 3 1

FAILURE DATA: A previous abnomal occurrence involving these switches was reported in Abnormal Occurrence Report No. 74/23.,

Portinent nanufacturer data:

Type: Barton Differential Pressure Switch Range: 0-60 inches 1120 Pressure Rating: 1500 psig Serial No.: IB11A2 - 278-965 l

I l

(

1 l

l l

l Prepared by:

\ -_x.

\ \4: 3. , . , Date: 11/25/74

\

- - - .-