I.' it i ni Tel q..cr.::
Date of I.c,>o rt Date:
ft-20-75 Occurrcncc:
G-17-75 -- 8-2 0- 75 Initia! Mritten Tir.e of l.'cport Dr.t e :
8-21-75 Occurrence:
OYCEa C'. T.X NUCLCJt CP;HaTI :G STATICN I C:b:LD 1:1VEP., E' JEMEY 03731 Abnort:n1 0: ur rence Report No. 50-219/7$23 IDE?.TIFICATICN e
r OF OCCURRENCE:
Failuro to monitor' the stack offluen"t foi i~odincts 6nd particulates for a period of three (3) days during routine power operations.
This event is considered to be an abnornal occurrence as de-fined in the Technical Specifications, paragraph 1.15 G CONDITIONS PRIOR TO OCCURRENCE:
I Steady State Pcwer Routino Shutdown
!!ot Standby Operation CoId Shutdown
_X Load Changes During Refueling Shutdown Routine Pcucr Operation Robtine Startup Other (Specify)
Operation DESCRIPTION On August 17, 1975'at about 0840 hours0.00972 days <br />0.233 hours <br />0.00139 weeks <br />3.1962e-4 months <br /> the stack gas low OF OCCURRENCE:
flow alara sounded in the control room.
The shift forc=an investigated and found the particulato and charcoal filters in the "A"
filter train required replaccuent due to normal loading.
Assuming that there were new filters already installed in "0" filter train, the foreman put "D" train in service.
Ile then notified the radiation technician, who came down inmediately to replace the filters in "A"
train.
Af ter the filters had been changed the technician failed to notice that "B"
train was still in service and therefore did not change the flow
~ path back thre:::h the filters in "A" train.
Th~is condition existed undetected until OS2S on August 20, 197S, when it was discovered ' during a routine filter change.
Procedures had been prepared and approved by the Plant Operations Review Coccittee to cover any changes made in the stack sampling flow path or filter changes.
These had not been finally typed or distributed prior to this occurrence.
e p
a
.$ runt occurronec Page 2 art, h*o. 50-210/73/g f.C.'T C/,USE DeSirn X
Proredure "CCUIN_'.CE :
- r.uft:cture Unusual Service Cer.dition h.'> ir.110 t i cn/
Inc. Linvirc:. -ental Cc..st.rnctiLn Co: p.:.c.t Vr.::urc Operator Other (Specify]
{
f 1.YSIS OF JRPJJ:CE:
During the period of time that the iodine and particulate setivity vac not sampled no plcnt operations were conducted which vculd be exp<eted to increase the activity :*oove nornal,
levels 7.r.d the rcologes activity showed no unusual fluctuation..
l As 1cvels of iodine and particulate activity prior to this occurrence were only about 2-40 of technical specification requirenents the safety significance of this occurrence appears to be sinimal.
l
/
PICTIVE
?ON:
' Immediate corrective action was to install a filter in the operating stack gas sampling train.
Procedures will be distributed to preclude this happening in the future.
ISRE DATA:
N/A I
e n i
I i
i
~
i i
. /** s?../ j -[ 7,..,.,,.
,.-se Date:
Yf.* //7.t ~
ysea by:
e I
l 9
e v
w-
. - r e
~)
s
(~d e
s
_l i
TO:
J tas P. O'P.ellly Dirt:tornte of Regulatory Operations Pe-ita I 631 i':rk Avenve Kir;: of Prussia ' Per.n,ylvania 19*06 i
FI n t:
Jersey Central Pcwer & Light Co::pany Oyster Creek NucIcar Ceneratir.g Station Docket #50-2 i
Forled River. New Jorsey 03731 1
SUBJECT:
Abnormal Occurrence Report No. 50-219/75/ 23 1
/
1
'the following is a prelininary report being i
submitted in cogliance with the Technical e
Specifications, paragrcph 6.6.2.
J Pre 33n3 nary Approval:
Q-f
/21*f$
A b'// I S <
3 VJ. T. Carroll, Jr.
Date CC:
Mr. A. Clasbusso N$b b _
.8-
- p. s ' M i
i e
e l
.,