KANSAS GAS AND ELECTRIC COMPANY THE ELECTRIC COMPANY OLENN L NOESTER v%E pets @EM? NUCLEAR March 30, 1984 Mr. J.E. Gagliardo, Acting Chief Reactor Project Branch 2 i

i U.S. Nuclear Regulatory Commission

' ]hh Region IV

[

l 611 Ryan Plaza Drive, Suite 1000 t

Arlington, Texas 76011 1

APR - 31984

,N KMLNRC 84-052 Re:

Docket No. STN 50-482 Subj: Final 10CFR50.55(e) Report - Load Shedder Emergency Load Sequencer

Dear Mr. Gagliardo:

This latter provides the final 10CFR50.55(e) Report concerning missing wires on the Load Shedder Emergency Ioad Sequencer (LSELS). This matter was initially reported by Mr. Harold Chernoff of Kansas Gas and Electric Company (KG&E) to Mr. William Johnson of the Nuclear Regulatory Commission, Region IV, on February 27, 1984.

During component testing it was discovered that vendor wires werc missing from tw logic rack assemblies (NF173-1, NF173-2) of the LSELS. The subjcct wires are located between sequencer "A" (Slot #11, Pin #90) and the relay driver (Slot #17, Pin #86). These wires should have been installed during fabrication by the vendor, Consolidated Controls. The missing wires could possibly have prevented relays which deenergize the feeder bus from properly actuating on an under-voltage signal.

Once this condition was identified, Consolidated Controls was contacted in order to facilitate resolution of this matter. Subsequently vendor representatires installed the two missing wires in the logic rack assemblies. This work was controlled and documented by a Construction Work Permit (CWP). As a result of the aforementioned activities, KG&E deems that no further corrective action is necessary.

Please contact me or Mr. Otto Maynard of my staff if you have any questions concerning this subject.

Yours very truly, 8404090343 840330 PDR ADOCK 05000482 fjfh GLK:bb cc: RCDeYoung NSchum rIbd]

1 201 N. Market - Wichita, Kansas - Man Address: RO. Box 208 I Nchita, Kansas 67201 - Telephone: Area Code (316) 261-6451 l

b