ML20087J627

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Synchronization Between Standby Diesel Generator & Alternate Preferred Power Source. Initially Reported on 840216.Evaluation of as-designed Condition Underway.Next Rept by 840430
ML20087J627
Person / Time
Site: Perry  
Issue date: 03/16/1984
From: Edelman M
CLEVELAND ELECTRIC ILLUMINATING CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
(RDC-97(84)), NUDOCS 8403230011
Download: ML20087J627 (2)


Text

%

.n

.)/7) 0

o a

b n,,, n 9 1i i it h ?

t, t b I l (,, o l

m,,,

c,

-_ p 7,,.., [...,., y nL U in n i A j iil t; co ov r

g,l Li L ;;,,,f; i ~

I

i P O Box 5000 - ctEVELAND. OH
o 44101 - TELEPHcNE (216) 622-980C - ILLUMINATING BLDG-

- 55 PUBLIC SQU ARE Serving The Best Location in the Nation MURRAf R. EOELMAN EC',$',*"'

March 16, 1984 ct Mr. James C. Keppler Regional Administrator, Region III Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission 799 Roosevcit Road Glen Ellyn, Illinois 60137 RE:

Perry Nuclear Power Plant Docket Nos. 50-440; 50-441 Synchronization Between Standby Diesel Generator and Alternate Preferred Power Source [RDC 97(84)]

Dear Mr. Keppler:

This letter serves as the interim report pursuant to 10CFR50.55(e) on the design deficiency concerning synchronization of the standby diesel generator and the 61 ternate preferred power source. Mr P. R. Pelke of your office was notified on February 16, 1984, by Mr. B. D. Walrath of The Cleveland Electric Illuminating Company (CEI) that this problua was being evaluated. This discrepancy was identified during a safety system fur.ctional capability review being performed for CEI by CDS Associates.

This report contains a description of the deficiency, planned corrective action and the date for filing of the next report on this subject.

D-acription of Deficiency FSAR Section 8.3.1.1.3.2.7d states that the standby diesel generator cannot be synchronized with the alternate preferred power source from the diesel generator room.

The design allows for this synchronization, but does not provide for local frequency indication of the alternate preferred source.

If synchronization was attempted between the alternate preferred power source and the standby diesel generators when they are out of sync, resultant loss of diesel generator supplied class IE power could occur.

840316 Uh 05000 S

MAR 191984 h

$.6V

2-March 16, 1984 Mr. Jamme G. Keppler Corrective Action Gilbert Associates, Incorporated, our Architect / Engineer, is currently nvaluating the as-designed condition which allows the synchronization between the alternate preferred power source and the standby diesel generator. They will determine if design and/or FSAR changes are necessary to effect safe systen operation and obtain consistency.

We wi!1 subnit our next report on this subject ay April 30, 1984.

Please en11 if there are any questions.

Sincerely, Murrey R. Edelman Vice President Nuc1 car Group MRE:pab cc:

Mr. M. L. Gildner NRC Site Office Dire-tor Of fice of inspection and Enforcement U.S. Nuc1 car Regulatory Commission Washington, D.C.

20555 U.S. Nuclear Regulatory Commission c/o Document Management Branch Washington, D.C.

20555 Records Center, SEE-IN Ins titutet of Nuclear Power Operations 1100 circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339

___--__mm____---_-__m