ML20087J005

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs,Revising DG Fuel Oil Testing Performed on New Fuel Prior to Addition of New Fuel to Storage Tank
ML20087J005
Person / Time
Site: Millstone 
Issue date: 04/28/1995
From:
NORTHEAST NUCLEAR ENERGY CO.
To:
Shared Package
ML20087J003 List:
References
NUDOCS 9505050178
Download: ML20087J005 (4)


Text

. __,

.h ;

'u' j

t i

Docket No. 50-421-i B14783 r:

l i

i i

f Millstone Nuclear Power Station, Unit No. 3 Proposed Revision to Technical Specifications Emergency Diesel Generator Fuel Oil Sampling Requirements Marked-Up Page i

r e

i f

i t

i l

i April 1995

bN 1r wAca wasz, A,o serum:

-rarrez> esa Acceed wem ASTH 2)nu-82.

p-ELECTRICAL POWER SYSTEMS January 3,1995 SURVEILLANCE REQUIRENENTS (Continued) b)

A kinematic viscosity at 40*C of greater than or equal to 1.9 contistokes, but less than or equal to 4.1 contistokes

-(alternatively, Saybolt visc ity, SUS at 100*F of greater than or equal to 32.6, but no less than or equal to

(

40.1), if gravity was not e ined by comparison with the supplier's certification; c)

A flash point equal to or greater than 125'F; and d) clearandbrIghtappearancewithpropercolor en tested in accordance with ASTM-D4176-82.

a2 L

~yT T 2)

By verifying within 30 days of obtaining the sample that the 2

other properties specified in Table 1 of ASTM-D975-81 are met k

when tested in accordance with ASTM-D975-81 except that the j

9y analysis for sulfur may be performed in accordanc with ASTM-E D1552-79, ASIN-D2622-82 or ASTM-D4294-83.

d f.

y'V At least once every 31 days by obtainiNying tsat total particulate a samale of fuel oil in 4

accordance with ASTM-D2276-78, and ver

,i d #

9 contamination is less than 10 mg/ liter when checked in accordance Qg with ASTM-D2276-78, Method A; g

2 At least once per 18 months, during shutdown, by:

o1*fa4 1)

Subjecting the diesel to an inspection in accordance with E

procedures prepared in conjunction with its manufacturer's n

3jj$

recommendations for this class of standby service; l

jR 2) 3 Verifying the generator capability to reject a load of greater n

. i

~

$1 than or equal to 595 kW while maintaining voltage at 4160 1 420 fgg volts and frequency t 60 1 3 Hz; j

s

-3

- @f a

l 3)

Verifying the generator capability to reject a load of 4986 kW i

y without tripping. The generator voltage shall not exceed 4784 2

volts during and following the load rejection; 4)

Simulating a loss-of-offsite power by itself, and:

d a)

Verifying deenergization of the emerge cy busses and load 4

shedding from the emergency busses, and j

b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 11 seconds, energizes the auto-connected shutdown loads through the load sequencer and operates for greater than or equa to 5 minutes while its generator is t

loaded with the shutdown loads. After energization, the steady-state voltage and frequency of the emergency' busses shall be maintained at 4160 1 420 volts and 6010.8 Hz during this test.

NILLSTONE - INIIT 3 3/48-5 Amendment No. (, 3, M. U,100

    • t3JY

-.~,.

t';. i' '

2

.l Docket'No. 50-423 l

B14783 l

l t

f f.

i

>t i

s h

Attachment 2

Millstone Nuclear Power Station, Unit No. 3 Proposed Revision to Technical Specification Emergency Diesel Generator Fuel Oil Sampling Requirements Retyped Pages l

{

r t

i f

I t

i April 1995 I

-a

g:

Q '

y

?

'/

SURVEILLANCEREQUIRENENS-(Continued) b)

A kinematic viscosity at 40*C of greater than or equal to l.9 centistokes, but less than or. equal to 4.1 centistokes (alternatively, Saybolt viscosity, SUS at 100*F of greater than or equal to 32.6, but less than or equal to 40.1), if l

l 4

gravity was not determined by comparison with the supplier's certification; c)

A flash point equal to or greater than 125'F; and d)

Water and sediment less than 0.05 percent by volume when tested in accordance with ASTM-D1796-83.

l 2)

By verifying within 30 days of obtaining the sample that the other properties specified in Table 1 of ASTM-D975-81 are met when tested in accordance with ASTM-D975-81.except that:

(1) the cetane index shall be determined in accordance with ASTM-D976 (this test is an appropriate approximation for cetane l

number as stated in ASTM-D975-81 [ Note E]), and (2) the analysis for sulfur may be performed in accordance with ASTM-D1552-79, ASTM-D2622-82 or ASTM-D4294-83.

f.

At least once every 31 days by obtaining a sample of fuel oil in accordance with ASTM-D2276-78, and verifying that total particulate contamination is less than 10 mg/ liter when checked in accordance with ASTM-D2276-78, Method A; g.

At least once per 18 months, during shutdown, by:

1)

Subjecting the diesel to an inspection in accord w.e with procedures prepared in conjunction with its marafacturer's recommendations for this class of standby service; l

2)

Verifying the generator capability to reject a load of greater than or equal to 595 kW while maintaining voltage at 4160 1 420 volts and frequency at 60 1 3 Hz; 3)

Verifying the generator capability to reject a load of 4986 kW without tripping. The generator voltage shall not exceed 4784 volts during and following the load rejection; 4)

Simulating a loss-of-offsite power by itself, and:

a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses, and j

b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 11 seconds, energizes the auto-connected shutdown loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the shutdown loads. After energization, the steady-state voltage and frequency of the emergency busses i

shall be maintained at 4160 420 volts and 60 1 0.8 Hz during this test.

MILLSTONE - UMIT 3 3/4 8-3 Amendment No. J. Jp, (J 77 Jpp.

OM1

.