3/4.7 PUWIT SYSTEMS 3/4.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION i

3.7.6.1 The Control Room Emergency Ventilation System shall be OPERABLE with:

a.

Two filter trains, b.

Two air conditioning units, c.

Two isolation valves in each Control Room outside air intake

duct, d.

Two isolation valves in the common exhaust to atmosphere duct.

and

~

e.

One isolation valve in the toilet area exhaust duct.

APPLICABILITY: MODES 1, 2, 3 and 4.

ACTION:

a.

With one filter train inoperaple, restore the inoperable train to OPERABLE status within 7 days or be in at least NOT STANDBY d

within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SNUTD0WN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With one air conditioning unit inopergble, restore the inoperable unit to 0PERABLE status within 7 days or be in at least NOT d

STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SNUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With one isolation valve per Control Room outside air i ike duct inoperable, operation may continue provided the other isolation valve in the same duct is maintained closed; otherwise, be in at least NOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SNUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

During the No. 21 emergency diesel generator upgrade in the 1995 Unit 2/

refueling outage, the time to restore No.12 filter train or air 5 conditioning unit to OPERABLE status may be extended to (for

/

loss of emergency power only) if the following is perfo

(

1.

A temporary diesel generator shall be demonstrated available by

(

starting it at least once per 7 days.

/

i 2.

If ACTION 1 is not met, restore compliance with the ACTION within I 7 days or be in at least NOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in s

COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

CALVERT CLIFFS - UNIT 1 3/4 7-16 AmendmentNo.297 j

i

(

M 3/4.7 PUWT SYSTDe$

3/4.7.6 CONTR01 ROOM EMERGENCY VENTILATION SYSTEM LIMITIM CONDITION FOR OPERATION 3.7.6.1 The Control Room Emergency Ventilation System shall be OPERABLE i

with:

a.

Two filter trains, b.

Two air conditioning units, c.

Two isolation valves in each Control Room outside air intake

duct, d.

Two isolation valves in the conson exhaust to atmosphere duct, i

and j

e.

One isolation valve in the toilet area exhaust duct.

APPLICABILITY: MODES 1, 2, 3 and 4.

ACTION:

I a.

With one filter train inoperaple, restore the inoperable train to OPERABLE status within 7 days or be in at least NOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SMTDOW within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With one air conditioning unit inopergble, restore the inoperable unit to OPERABLE status within 7 days or be in at least NOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SMTDOW within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With one isolation valve per Control Room outside air intake duct inoperable, operation may continue provided the other isolatim:

valve in the same duct is maintained closed; otherwise, be in at least NOT STAND 8Y within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i During the No. 21 emergency diesel generator upgrade in the 1995 Unit 2 refueling outage, the time to restore No.12 filter train or air i

conditioning unit to OPERABLE status may be extended to 45 days (for l loss of emergency power only) if the following is performed:

1.

A temporary diesel generator shall be demonstrated available by starting it at least once per 7 days.

2.

If ACTION 1 is not met, restore compliance with the ACTION within 7 days or be in at least NOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SMTDOW within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

CALVERT CLIFFS - UNIT 1 3/4 7-16 Amendment No. 202