Proposed Tech Specs Modifying Limiting Condition for Operation Action Statement for Fire Barriers to Reflect Guidance Provided in STS for GE BWRs
ML20087H513
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 03/16/1984
From:
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20087H467 List:
References
NUDOCS 8403210063
Download: ML20087H513 (3)


Text

y

< vy Unit 2 PBAPS LIMITING CONDITIONS FOR OPERATION -SURVEILLANCE REQUIREM,ENTS 3.14.D Fire Barrier Penetrations 4.14.D Fire Barrier Penetrations

-1. Fire barrier penetrations including 1. Visual inspection of pene-cable penetration barriers, fire tration fire barriers doors and fire dampers, protecting chall be performed following the following areas shall be repairs or maintenance end functional *: at least once per 18 months.

1) Cable Spreading Room
2) Emergency Switchgear Rooms
3) Diesel Generator Rooms
4) Battery Rooms
5) Control Room
2. All fire barrier penetrations including cable penetration barriers, fire doors and fire dampers separating portions of safety related systems, required to ensure safe shutdown capability shall be functional.**
3. If the requirements of 3.14.D.1 or 3.14.D 2 cannot be met, within one hour establish a continuous fire watch on at least one side of the affected fire barrier, or verify the operability of fire detectors on at least one side of the inoperable fire barrier and establish an hourly fire watch patrol. . Reactor startup and continued reactor operation is permissible.
  • Delete when the provisions of 3.14.D.2 become effective.
    • Effective upon return to power following the Unit 2 refueling outage commencing in 1984.

8403210063 840316 PDR ADOCK 05000277 P PDR

-240j-

v4 v7 Unit 3 PBAPS' LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS 3.14.D Fire Barrier Penetrations 4.14'.D Fire Barrier ' Penetrations

1. Fire barrier penetrations including 1. Visual inspection of pene- '

cable penocratien barriers, fire tration fire barriers doors and fire dampers, protecting shall be performed following the following areas-ahall be repairs or maintenance and functional *: at least once per 18 months.

1) Cable Spreading Room
2) Emergency Switchgear Rooms
3) Diesel Generator Rooms '

~4) Battery Rooms

5) Control Room 2.-All fire barrier penetrations including cable penetration barriers, fire doors and fire dampers separating portions of safety related systems, required

-to ensure safe shutdown capability

'shall be functional.**

3. If the requirements of 3.14.D.1'or 3.14.D.2 cannot be met, within one hour establish a continuous fire watch on at least one side of'the~affected fire barrier, or verify the-operability of fire detectors on at least one side'of the inoperable fire barrier and establish an hourly fire watch patrol. Reactor startup and continued reactor operation is permissible.
  • Delete when the provisions of 3.14.D.2 become effective.
    • . Effective on Unit 3,upon completion of licensee's fire barrier upgrade program, or September 15, 1984, whichever comes first.

i i

l

-24o3 .

- , .- - . _ , . _ . . _ . . . , _ . _ , . , , . , , _ - . . - . . _ , - . . - - . _ , _ _ . , _ _ _ . _ - . _ _ ~ . . . . . . . _ _ _ , _ . _ . . _ _ _ _

V~

^

y..a . v. , - ..:

  • ~*

CERTIFICATE OF SERVICE

{

I certify that service of the foregoing Application was made upon'the Commonwealth of Pennsylvania, by mailing

~

'a :Lcopy _thereof, via first-class mail, to Thomas R. Gerusky, Director,' Bureau of'Radlological Protection, P. O. Box 2062,

-'Harrisburg, PA~ 17120; all this.16thday of March, 1984.

.c 1

Eu noJ/Bradley Attorney for \

Philadelphia Electric Company

(