Requests Temporary Relief from ASME Code Repair Requirements for Class 3 Piping,Per Generic Ltr 90-05. Calculations Concluded That Strength of Installed Clamp Exceeded Strength of pre-existent Pipe
ML20087E387
Person / Time
Site: Oyster Creek
Issue date: 01/15/1992
From: J. J. Barton
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
C321-91-2365, GL-90-05, GL-90-5, NUDOCS 9201210201
Download: ML20087E387 (2)


Text

1 e

p GPU Nuclear Corporation (y '

g Post Office Bom 388 Route 9 Soutn Forlod Rwor, New Jersey 08731 t*98 003 971 4000 Wrdet's Direct D,al Number.

4 C321-91-2365 January l'a 1992 U.S. 11uclear Regulatory Commission Attn Document Control Desk Washington, DC 20555 Dear Sir

Subject:

Oyster Crook liuclear Generating Station Docket lio. 50-219 Request for Ptlief from ASME XI Ropair-Roqujrsmonto for Class 3 piping 4

This letter is being written pursuant to 10 CFR 50.55(a)(g)(5)(iii) to request temporary relief from the ASME Code Ropair Requirements defined in Section XI for class 3 piping.

During thr, performance of excavation and inspection of underground pipe in the condensato transfer system, a section of piping was discovered which exhibited external pitting typo corrosion The pipo in this portion of the condenuato transfer system is 10 inches in diamator and constructed of aluminum.

The design pressure is 50 psig.

IIDE examinations of tha pipe in the vicinity of the pitting corrosion revealed the pipe to be at nominal thickness, except for the identified pits.

The decision was mado to. clean the corrcsion and apply a protective coating.

During'the cleaning process, a small pit started to woop water.

Isolation and draining of this portion of the system is not possible under tho Oyctor Crook Technical Specifications while at power.

A piece of gasketing metorial was placed on the pipo and secured with a stainless stool clamp.

Two additional clamps woro installed in the immediato vict.nity to provido additional strength to the section of piping.

Calculations concluded that the strength of the installed clamp excooded the strength of the pro-existent pipo.

92o1210201 970115 A

PDR AD W 00000219 py p

PDR GPU Nuclear Cotooration es a subsdary of Geno'a1 Public Util40s Corporation l

..v.

C321-91-2365 Page 2 In accordance with Generic Lotter 90-05, this leak has been dotarmined to be a "through-wall flaw", and thorofore, the temporary repair would qithilff for relief from permanent repair until the next refueling outar;o, The section of piping containing the woopage has been sebtut.'od for replacement during the next outage of sufficient dutstir.1, not to excood the next refunling outago presently scheduled for sanuary 1993.

Should you have any questions, please contact Mr. John Rogers, Oyster Crook Liconoing Engincor at 609-971-4893.

ry tr21y yours,

/

WP 1

Jot n J.

Da on V

e Presi ont and Director oyster creek JJD/JRijc cc:

Administrator, Region 1 Senior NRC Resident Inspector oyster creek NRC Project Manager j

l l