DUKE POWER GOMPm 1*.O. ISOx 33180 CIIAlt!.OTTE. N.G. 28242 HALH. TUCKER TELEPHONE vum enemment (704) 373-4531 February 29, 1984 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Attention: Ms. E. G. Adensam, Chief Licensing Branch No. 4 Re: Catawba Nuclear Station Docket Nos. 50-413 and 50-414

Dear Mr. Denton:

Ms. E. G. Adensam's letter of January 20, 1984 transmitted a summary of the fire protection site audit which was conducted on Ncvember 1-4, 1983.

Item 12 of this summary discussed compliance with NFPA Standard No. 72D in the design of the fire protection systems.

In response to this item, fire protection system valves which were equipped with tamper switches will be locked in the appropriate position since related circuitry has not been supervised per NFPA 72D.

An exception is motor operated valves which, in addition to position indication on the fire protection / fire detection system console, have position indication on the RF/RY valve control board in the Control Room.

Independent switches and circuitry are used to provide the separate means of annunciation of these valves.

Fire protection valves which are accessible during normal operation will be visually inspected at thirty day intervals.

Very truly yours, 8

Hal B. Tucker ROS/php cc: Mr. James P. O'Reilly, Regional Administrator U, S. Nuclear Regulatory Commission Region II 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303 NRC Resident Inspector Catawba Nuclear Station Oh 9403060419 840229 Ip PDR 6 DOCK 05000413 p

PDR

'%g -

lMr. Harold R. Denton, Director February 29, 1984 Page 2 cc: Mr. Robert Guild, Esq.

' Attorney-at-Law P. O. Box 12097 Charleston, South Carolina 29412 Palmetto Alliance 21351 Devine Street Columbia, South Carolina 29205 Mr. Jesse L. Riley Carolina Environmental Study Group 854 Henley Place Charlotte, North Carolina 28207 1

y w

e-vw-

-.mm-.4

--9 y

e yw+4.--e.

-eqp-.

..e- - - -

- - -m-,

a w

ww

-n+w-g y

-=ir-+

gmy

--r 9

7--.--n-