AO-S2-74-07:on 740810,summator TM-2-4126 Found Drifted Allowing Overpower Setpoint to Be Approx 5% High.Cause Not Determined.Investigation Continuing & Complete Rept Will Be Submitted When Investigation Complete
ML20086S491
Person / Time
Site: Surry  Dominion icon.png
Issue date: 08/20/1974
From: Stallings C
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: Moseley N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20086S438 List:
References
AO-S2-74-07, AO-S2-74-7, NUDOCS 8403020373
Download: ML20086S491 (1)


Text

__ _

O O

VinoixiA E x.1:c rusc An n l'ows:n Coot t'ANY Itsen> oun.vt HOINI A Ofl0 Un August 20, 1974 Mr. Norman C. Moseley, Director Serial No. 248 Directorate of Regulatory Operations P0&M/JTB:clw United States Atomic Energy Commission Region II - Suite 818 Docket No. 50-281 230 Peachtree Street, Northwest License No. DPR-37 Atlanta, Georgia 30303

Dear Mr. Moseley:

Pursuant to Sitrry Power Station Technical Specification 6.6.B.1, the Virginia Electric and Power Company hereby notifies you of an abnorcal occurrence which occurred on August 10, 1974.

With Unit No. 2 operating at 100 per cent of rated power, Periodic Tese 2.1 " Reactor Coolant Temperature Protection Instrumentation" was being performed.

At approximately 1030 hours0.0119 days <br />0.286 hours <br />0.0017 weeks <br />3.91915e-4 months <br />, it una found that surmnator TM-2-4126 had drif ted allowing the overpower AT set point to be approximately five per cent high.

Af ter its removal, the sunmator could not be made to drif t or operate incorrectly in any manner under very exte' naive bench testing.

At this time, the cause of the suc=tator f ailure has not been determined.

The investigation is continuing and a complete report, designated as A0-S2-74-07, will be submitted I

when the investigation is complete.

The purpose of this notification is to satisfy the tan (10) day reporting requirement required by Technical Specification 6.6.B.l.