July 12, 197h
/
x N:::
t-fir. A. Gi cmbusso
' ~
Deputy Directcr of Recctor Projects Uni ted S t a tes At oni c Energ) C cnm i s s i on DircatorcLe of Licensing Wshi n g t on, DC 20545 Oc,ar Mr. Gicmbusto:
Subject:
Abnormal Occurrence TI c follo. zing c;currence was repor ted to Mr. Tom Shedlewsky, A.E.C. Region 1 Regulatcry Operations Office en July 3, 1)/h. tir i t ten noti f icat ica was rode to Mr. Jirno s P. O 'Re i l l y, Region 1 Regulatory Operat ions Of f ice on July 3,197h.
In accordcocc with Section 6.7.2.A of the Technical Specificetions, Appendix A of DPR-44 for Unit 2 Peach Gottor Atcmic Fc,er Static,, the f ol lowing repor t is bein.) suiaitted to the Dirccterate of Licensing as an Abnorraa! Occurrence.
p,r,,,,,.._.
~.._..
.,....., ~, ~.,,,, c.. u n u,. u n t 5umver i Technica!, ecificction Table 3 1.1 Report 'J a..
50-277-74-35 Report Date:
July 12, 1974 Occurrence Date: July 2, 1974 Facility:
Peach Bottom Atomic Power Statico R.D.
1, Delta, Pennsylvania l'/314
. Identification of O_cc_urrence:
Condensor i cr. i vacuum scrcm pressure switch setpoint found to j
bc less censer vative than the limiting safety system setting.
t Condit ions Pr ion t o Occurrence:
The reactor was at 39,/, pcwer.
l Pa sc r ip t i on r Occurr'nte:
e D ur i ng a. c.o t i ne i n s t r o:ra t surveillence test of P5-2-5-ilA, main condenser le.s vacuu irip input into the reactor protectic-n system, the sub jec t switch was found to trip at 19.2 in. Hg.
Tiiis is j.8 in. tl3 less c onrcrvative than the Technical '.pec i f i ca t i on s rp 'nt of greater than or equal t o '!? i n, lig.
G401270126 740712 PDR ADOCK 05000277 e
PDR a
tot'i DENT REGIbh 'Mw
Mr. A. Giar. basso p
July 12, 1974 v'
Page 2 pesignation of Apnacent cause of crcurrence:
Se rpoi n t failure is attributed to instrument drift.
Analysis of Occurrence:
PS-2-5.llA is one channel in a one-out-of-two-twice logic arrangement. The setpoint foilure would net have preven ted t he eevice tran initiating a trip signal.
The protection p ovided by tha other three channels 0+ condenser vacuum voald have becn sat isf actory fr ea a standpoint of clant s a f e t :,. Therefore, thi., ccourrcnce Ses raininal safety implications.
Corrective Action:
Tha. subject switch was immediately recc.!ibrated, checked fur setpoint repeat ibili ty and returned t o service. The ot her thrce d tchra monitoring condenser vacuum end providing the RPS inpats were irned i a t e l y tested cr.d founa t o be s a t i s f a c t r;r y.
Foilure Data:
.This is the fourth setpoint f ailure of this type of de ice in this service.
Other occurrences are as follo',s:
PS-2-5-!!A cn w ear- ';. 1974 IS-2-5-;iD en scanuary [ ly/4 PS-2-5-i l A on Apr i l 8, 1974 After the two setpoint f ailures of PS11A. the device was rc-placed in kind. Tnis f ailure is the fir st se t p a i n t failure of the re-placement device.
'e y t r u l y ycar s,
i l.!j /]
/
4 /
/ ;/c/p,,<J v;
/
4 M. i. C oeney A s s' ' t Gen ' l S uper. iintendent Gt'ocr a t i on fii v i s i on ec: