ML20086K387
| ML20086K387 | |
| Person / Time | |
|---|---|
| Site: | Peach Bottom |
| Issue date: | 08/22/1974 |
| From: | Ullrich W PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| Shared Package | |
| ML20086K380 | List: |
| References | |
| AO-74-40, NUDOCS 8401270057 | |
| Download: ML20086K387 (1) | |
Text
..
CJWs
- o,c
~
sa x
^g
=
v>
17314 r.g,R,7
""~
~
at 22, 1974 p.^
' United States Atomic Energy Commission Jg., '
,g e d'g'
,'g
< gg g,,.
6
,ur. James F. O'.
Illy, Director e j )[(J
"?.4 9
S Directorate of Regulatory Operations 9
~
631 Park Avenue 7 30 N3
~ ji N d?
l Riz.s of Prussia. Fannsylvania 19406
(:
Subj ect:
Abnormal Occurrence 24-Hour Notification
- Q
~e, C m
y
{,
?.
Confirming Mr. R. S. Fleischmann's phone conversation with Mr. W. Emunack, f]
'i.
A.E.C. Region 1 Regulatory Operations Office on August 22, 1974.
p 7
~ 1-
.2 e
N
Reference:
License Number DPR-44 Amendment Number i
?!/
rT [~
~
j Technical Specification Table 3.2.B Q
3 q(
a e
y
$,To
?
-b Report No.:
50-277-74-40 c
d Report Date:
August 22, 1974 M=i
~
m
~
1.
- ==~.==
==== nA ??i
~
Facility:
Feach Bottom Atomic Fower Station R. D. 1. Delta. Pennsylvania 17314 r
Identification of Occurrence:
I Static inverter power supply in the Reactor Core Isolation Cooling System (kCIC) tripped during the start of a Unit 3 recirculation pump.
D L
Conditions Prior to Occurrence:
The reactor was operating at 100% power.
i 3
Description of Occurrences f
During a restart of a Unit 3 recirculetion pump following a surveillsace test, j
the Unit 2 RCIC inverter failure alara annuncasted in the mein control room.
}
The inverter was imeediately reset.
1 L
g~
Designation of t.pparent Cause of Occurrence:
A high
'the cause of the trippings of the static inverter has not been found.
speed memory type recorder connected to the inverter input displayed a negative going spike just prior to the inverter tripping. An analysis of this 7
transient is now in progress.
bv fI Analysis of Occurrence:
At the time of the inverter tripping, all other Unit 2 Emergency Core Cooling Systems vere operable. Due to this and the short tima that the inverter vss tripped, this occurrence has minimal safety significance.
[
f.
Corrective Actions The trippings of the inverter are currently under investigation by the i.
Philadelphia Electric Company Engineering and Research Department.
Failure Data:
h i
Four other trippings of the RCIC inverter have been reported as A0-50-277-74-14 A0-50-27,7-74-20 A0-50-277-74-37 and AO-50-277-74-39.