AO 74-2:on 740729,refueling Floor Exhaust High Radiation Detector RIS-3-17-458D Found W/Trip Point in Excess of Tech Spec.Caused by Device Being Conservatively Set.Device Set to Trip at More Conservative Indicated Value
ML20086J520
Person / Time
Site: Peach Bottom Constellation icon.png
Issue date: 08/08/1974
From: Cooney M
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20086J521 List:
References
AO-74-2, NUDOCS 8401240052
Download: ML20086J520 (2)


Text

m J

_ s",..m,N

.! ~

,;Q(

-h e

s.

x; 1

? (l.y( g,. \\,\\ j ig 7 /,,

- i PHILADELPHIA ELECTRIC COMPANY

/

l 2301 MARKET STREET p5.

h1974

- t j

4 e

PHILADELPHIA. PA.19101

, %,7 azisi 84i-4ooo 4

/ /*

.W August 8, 1974 E~ #

Mr. A. Giambusso Deputy Director of Reactor Projects United States Atomic Energy Corgnission Directorate of Licensing 50-278 Washington, DC 20545

Dear Mr. Giambusso:

Subject:

Abnormal Occurrence The following occurrence was reported to Mr. R. A. Feil, A.E.C.

Region 1 Regulatory Operations Of fice on July 29, 1974. Written noti-fication was made to Mr. James P. O'Reilly, Region 1 Regulatory Opera-tions Of fice en, July 29, 1974.

In accordance with Section 6.7.2.A of tha T.,-hnic.=1 % cificu<nne, n,n,n-,4ix A of DPD-56 f ar Vai t 3 Deee sottom atomic rcwer station, tne rollowing report is being submitted to the Directorate of Licensing as an Abnormal Occurrence.

Reference:

License Number DPR-56 Technical Specification Table 3 2.D Report No.:

50-278-74-2 Report Date:

August 8, 1974 Occurrence Date:

July 29,1974 Facility:

Peach Bottom Atomic Power Station R.D. 1, Delta, Pennsylvania 17314 Identification of Occurrence:

RIS-3-17-4580 refueling floor exhaust high radiation detector l

was found to have a trip point in excess of the Technical Specification value during instrument calibration Conditions Prior to Occurrence:

h Fuel loading of initial core in progress.

{p. [

' Q L/ [l Description of Occurrence:

\\

l R IS-3-17 l SPD refueling floor exhau.st high radiatien monitor i

[

was ' found t o h we a t-io point of about 24 FP/P actual during instra-

[

ment calibration. Technical Specification required setpoint is 16 mR/HR.

8401240052 740000 PDR ADOCK 05000278

~ 8 J, O g S

PDR COPY SIMP REGION 2

k

-O

r-w O

o M'r. A. Giambusso

"' " August 8, 1974 Page 2 Designation of Apparent Cause of Occurrence:

The device had been conservatively set to trip at 10 mR/HR indicated value. During the calibration of the device with an ex-ternal source, it was discovered that actual 16 mR/HR yicided an in-dicated value of 7 mR/HR. The device is a four-decade log device and this reading is within the instrument accuracy in percent of equivalent linear full scale. No problem exists with the instrumentation.

Analysis of Occurrence:

This device is one instrument in a.one-out-of-two-twice logic 3

1 which initiates a ventilation system isolation on refueling floor ex-haust high radiation. Since there is no irradiated fuel in Unit 3, there j

is no situation which could create the initiating signal. There are no safety implications associated with this trip point deviation.

Corrective Action:

All four devices which monitor refueling floor exhaust high radiation were set to trip at a more conservative indicated value. This indicated value, when compared to the actual calibration trip value, is i

significantly below the required actual 16 mR/HR in all cases.

Toilure Data:

This same problem occurred on a similar detector on Unit 2 and was reported as an Abnormal Occurrence on October 29, 1973 Very truly'yours, l['$ ~

/ 6 ll l {g $,/

/

A.

C6one'y j

Ass t Gen't Superintendent Generation Division 3