Telecopy AO 75-20:on 750316,refuel Area Exhaust Radiation Monitor RIS-2-17-458C Failed Downscale.Cause Under Investigation.Channel Placed in Tripped Condition
ML20086J050
Person / Time
Site: Peach Bottom 
Issue date: 03/17/1975
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
AO-75-20, NUDOCS 8401230073
Download: ML20086J050 (1)


Text

y Ir o

o YL

~

v

\\

PIIILADELPfllA ELECTRIC Colil'ANY Pench Botton Atamic Power !Itation Delta, Pennsylvania 17314 linrch 17, 1975 Mr. James P. O'Reilly, Director Office of Inspection and Enforcement

[

4A U

States Huclear Regulatory Coimnission

. hM1

\\

631 Park Avenuo King of Prur.sia, Pennsylvanin 19406

Subject:

Abnormal Occurrence 26-Ilour Not ification Coutirning J. P. Franz' phone conversation w'ith Mr. Walt Baunack, Region 1 United States Nuc1 car Regulatory Cosminuten on March 17, 1975.

Reference:

License Humber DPR-44 Technical Spectiication Refcrence:

3.2.D.2 and Table 3.2.D Report No.:

50-277-75-20 Report Date:

March 17, 1975 Occurrence Date:

March 16, 1975 Facility:

Peach Botton Atomic Power Station R.D. 1, Delta, Pennsylvania 17314 Id ptification of Occurrence: -

{RefuelAreaExhaustRadiationMonitor,RIS-2-17-458C,faileddownscale.

Conditions Prior to Occurrence:

Reactor at full power steady state.

Deccription of Occurrence:

During normal steady state operation, the 'C' refueling area exhaust radiation aceitor failed dovnocale.

Designation or Apparent Cac.se of Occurrence The apparent cauan of the occurrence is under investigation at this time.

Analysis of Occurrence Because this device is one of four arranged in a one-out-of-two twice logic (which initiates a secondary containant ventilation cystem isolation on refueling floor exhaust high radiation) such that the loss of any one device vill not defeat t',e logic, the safety imp 1*. cations are minimal.

Corrective Action:

This channel was i::::codiotely placed in the tripped condition in coc:pliance with Table 3.2.D of the Technical Specifications.

g Pa11ure Data:

Under investige. tion.

Very truly yours, hY/W8 W. T. Ullrich, Superintendent Peach Dotton Atomic Power Station 8401230073 g h 7 PDR ADOCK ppR S

.