ML20086J011

From kanterella
Jump to navigation Jump to search
AO 75-23:on 750324,setpoint Shift Found on ECCS High Drywell Pressure Initiation Switch PS-2-10-101D.Caused by Setpoint Shift.Switch Reset to Value within Tech Spec Limits
ML20086J011
Person / Time
Site: Peach Bottom Constellation icon.png
Issue date: 04/03/1975
From: Cooney M
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Anthony Giambusso
Office of Nuclear Reactor Regulation
References
AO-75-23, NUDOCS 8401230043
Download: ML20086J011 (2)


Text

gd

]

PHILADELPHIA ELECTRIC COMPANY I N tA

,f

$,*\\

2301 M ARKET STREET

D j '..

PHILADELPHIA. PA.19101

~

lllJg*.,

?}l

/

.[y (21518414000

'<, 2xQp]. g(V 3

April 3, 1975 p

Mr. A. Giambusso Director Division of Reactor Licensing Of fice of Nuclear Reactor Regulations United States Nuclear Regulatory Commission Washington, DC 20555

Dear Mr. Giambusso:

l

Subject:

Abnormal Occurrence The following occurrence was reported to Mr. Walt Baunack, Region 1, Office of Inspection and Enforcement, United States Nuclear Regulatory Commission on March 25, 1975 Written notification was made to Mr. James P. O'Reilly, Director, Region 1, Office of Inspec-tion and Enforcement, United States Nuclear Regulatory Conmission on March 25,1975 In accordance with Section 6 7 2.A of the Technical Specifications, Appendix A of DPR-44 for Unit 2 Peach Botton f.tomic Power Station, the following report is being submitted to the Director-ate of Reactor Licensing as an Abnormal Occurrence.

Reference:

License Number DPR-44 Technical Specification

Reference:

Table 3 2.B Report No.:

50-277-75-23 Report Date:

April 3,1975 Occurrence Date: March 24, 1973 Facility:

Peach Bottom Atomic Power Staticn R.D. 1, Delta, Pennsylvania 17314 Identification of Occurrence:

Setpoint shif t on ECCS hi drywell pressure initiation switch PS-2-10-101D.

Conditions Prior to Occurrence:

Unit 2 at full power.

Description of Occurrence:

M}

+

During routine instrument surveillance testing, PS-2-10-101D y

was.found to trip at 2.03 psig. The Technical Specification limit is less than or equal'to 2 psig.

8401230043 75d403 3 /"C E PDR ADOCK 05000277 S

PDR

[

cnov RENT REGIONw

~

t O

o

~

50-277-75-23 Mr. A. Giambusso April 3,1975 Page 2 Designation of Apparent Cause of Occurrence:

Setpoint shift.

Analysis of Occurrence:

Because the setpoint shif t was only slight and this switch operates in a anc-out-of-two twice logic, the safety implications of this occurrence are minimal.

Corrective Action:

The switch _was checked to determine the cause of the setpoint shift. No specific cause was identified. The switch was reset to a value within the. Technical Specification limits, using the appropriate surveillance test and returned to service. The companion devices were tested satisfactorily.

Failure Dato:

Oneprevious. occurrence on this type of instrument in this service was reported as Abnormal Occurrence 50-277-74-51.

Very truly ycure, M.

. Cooney Ass' t Gen'l Superintendent Generation Division p