_ _ _ _ _ _ _.
O O
FBILADELPHIA ELECTRIC COMPANY !
Peach Lotion Atomic Power Station D<alta, Pennsylvania 17314 June 23, 1975 M b I - P. O'Reilly. Director;
....p Office of Inspection and Enforcement >.
M.2f.Jg..
. Region 1 Un'.ted States Nuclear Reguimtory Comatission-631 Park Avenue
.s King.cf Prussia. Fenvylvacia. 19406,
Su'irett Abnorm 1. Occurrence 24-Hour Notiff cation I
b
..Confirmin,t W T. U11 rich's phone conversation-with Mr. Jiza Partlow, Region 1,
' United States Nuclear. Regulatory Ctnaission on June 22. 1975.
Referencer License Number DPR-44
.- 7
'~' Technical Specification:2eferences' 3. 8 A',--
Repore No.:
50-277-75-50 Report Datet-June 22.1975
.Occu~rr'ence Datet June 21, 1975 Facility:
Peach Botton Atomic Power Station R.D. 1. Delta, Pennsylvania 17314
--Identification of c a m.e ca.
, Unplanned release of cont *Linated watergte the discharge canal.:
Conditions Prior to Occurrences.
Unit 2 shutdown..
Description of Occurrencet During investigation.of a suspected tube leak in the.. "D" RHR heat exchanger thage was apparently some v.igration of reactor water into the High Pressure Service Water ;
System side of the heat exchanger. As soon as a Icak was positively identified -
the heat exchanger was removed from service and isolated.
Designation of Apparent. Cause-of Occurrence:
Tube leak in
'D' RER beat exchanger.
Analysis of occurrence:
There was mininal safety significance associated with this tube failure. Initial water analysis indicates.a low value of microcuries released.
Corrective Action:
Beat evenanger undergoing tube xepair.
Failure Date:
None previous - liquid release.
Very truly yours, fNNIY U. T. Ullrich, Superintendent-Feach Bottom Atomic Power Station S