ll l
Duke Tower Compny D L Raw Catawba Nuclear Generation Department
%ce hesident j
4800ConcordRoad (803)8313205Oflice f
' York,SC2974)
(803)8313C6Far
)
{
DUKEPOWER
(
July 11,1995 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 l
i
Subject:
Catawba Nuclear Station, Unit 1 Docket No. 50-413 Special Report Vibration and Loose Parts Monitoring System l
On June 8,1995, Channel 13 (S/G 1B Manway) was declared inoperable.
Trending of bias voltage and background RMS was evaluated to conclude that the channel was experiencing periodic failures. Problem Investigation i
Process (PIP) 1-C95-0883 has been initiated for tracking purposes; work request 95025569 (WO 95045842-01) has been initiated to perform corrective maintenance on this instrumentation. This work will be performed during 1EOC9 outage.
Redundant monitoring is afforded by Channels 12 (S/G 1B l
Secondary) and 14 (S/G 1B Hot Leg).
i Since this channel has been inoperable for 30 days; it is reportable pursuant to Technical Specification 3.3.3.9.
i Very truly yours, A _ - __ -
D. L. Rehn KEN /SR071195. LPM i
Attachment xc: S. D. Ebneter, Regional Administrator R. E.. Martin, ONRR R. J. Freudenberger, SRI 9507180046 950711
/
i PDR ADDCK 05000413 i}0 S
PDR t
I+snod w ra.yJed parn
,, --. - -, -,. -