ML20086H026

From kanterella
Jump to navigation Jump to search
Telecopy AO 75-11:on 750214,excessive Leakage Found on Drywell Oxygen Analyzer Sample Sys Inner Isolation Valve SV-3671C.Cause Under Investigation.Valve Will Be Maintained When Plant Conditions Permit
ML20086H026
Person / Time
Site: Peach Bottom 
Issue date: 02/15/1975
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086H024 List:
References
AO-75-11, NUDOCS 8401130347
Download: ML20086H026 (1)


Text

_

_____.__-_______w lF),,G&

pgJ,,.$ Y 2* R T'Q *,

ILADELPHIA ELECTRIC COMPANY g, gg,,-p-B ggyS Peach Bottom Atomic Power Station

._._.. Delta, PennsylJania

.___n-

-1?314 February 15,.eria Mr. James P. O'Reilly, Director Office of Inspection and Enforcement Region 1 United States Nuclear Regulatory Consnission 631 Park Avenue ning of Prussim, Pennsylvania 19406

Subject:

Abnormal Occurrence 24-Hour Notification Confirming W. T. Ullrich's phone conversation with Mr. Walt Baunack, Region 1 United States Nuclear Regulatory Commission on February 14. 1975.

Reference:

License Number DPR-56 Technical Specification Reference-4.7.D.l.b(1) and Table 3.7.4 Raport No.:

50-278-75-11 Report Date:

February _14, 1975 Occurrance Date:

February 14, 1975

, Facility:

Peach Botton Atomic Power Station R.D. 1. Delta. Pennsylvania 17314 Identification of Occurrence:

P.xcessive leakage drywell 02 Analyzer Sample System Inner Isolation Valve (SV-3671C).

Conditions Prior to Occurrence:

Unit 3 at 99.5% power.

Description of Occurrence:

While performing Survaillance Test 6.2 PCIS normally open valves, this valve failed to seat.

Measured leakage was in excess of 50incfh.

Designation of Apparent Cause of Occurrence.

The cause for this valve leakage is under investigation.

Analysis of Occurrence:

The safety implications of this occurrence are minimal since the outer isolation

~

valve SV-3978C did close and seat.

Corrective Action:

T.41s valve will be maintained when plant conditions permit.

Subsequent to repa the valve will be tested to verify that the repair is satisfactory.

s Failure Data:

A previous failure was reported as an Abnormal OccurrenDe on 11/9/73.

r Very truly yours, 8401130347 750224 PDR ADOCK 05000278

  • pggJ S

PDR

_g

u. T. Ullrich, Superintendent REGULATCl?Y OPERATIONS Panch Bottom Atomic Power Station FILE @PJ

_1

.