ML20086G883

From kanterella
Jump to navigation Jump to search
Telecopy AO 75-34:on 750611,TIP Machine Detector C Failed to Close.Caused by Failure of Shield Limit Switch.Corrective Action to Be Determined After Investigation
ML20086G883
Person / Time
Site: Peach Bottom 
Issue date: 06/12/1975
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086G881 List:
References
AO-75-34, NUDOCS 8401120570
Download: ML20086G883 (1)


Text

g o

(

)

V; P!IlLADELPill A E!.ECTRIC CO.'tPANY Peach Bottoa Aconic Power Station.

Delta, Pennsylvania L

l

1731, June 12, 1975 Er. James P. O'Ecilly, Director A

Office of Inspection and Enforcerent.

ilegion 1 p

Unitec'. Staten Nuclear Regulatory Cornission :

72g4 6';l Park Avenua idug of Prussia, Pennsylvania 19405

- Mj <2c t.:

Abnormi Occurrence 24-lim 2r Nori fication Confirning W. T. Ullrich's phone conversation with Mr. L' alt Eaunack, Region 1. United Staten Nuclear Regulatory. Cor mission on Jene 12,1975...

.' License Nu ber hPb%

i

~

', ', i '.

-t i

'3

)

i

Reference:

Aechnical Specification

Reference:

4.7.D i

I i Pepart No. :

50-27b75-31.

.v.cport Date:

/ June '12', 1971 necurrence Date: June ll, 1975 Frcility:

Pea:h Lotton Atomic Power Station T U.

1, Im?rWITnnsylvnTia 17314

~

~

~~

Identification of Occurrence:

l' allure of the C" Ti? uachine ball. valve to cleso Conditions Prior to Occurrence:.

Unit 3 at 50:; power.-

Dencription of Occurrence

l During routina operation of the TIP tsachines, the "C" detector failed to stop at the-a chield linit and close the ball valve as it was being withdrawn to the shield chamber.

i Desigaatien of Apparent Cause of Occurrence:

The chield li-.it cvitch, which 'controlo detector trr.vol and ball valve oper.ition, failed to operate when the detector reached the "In chield" position. This allowed i

q the detector to continue its withdra.ral untII' It was cLanuaIIy stopped.

Lins 3:, ain sE=.cccurcr.me --- -

l

're failure oi' tl.o linit r.vitch to halt the withdrawal and closc the ball valve was incudiately obr,crved and corrected by r. witching to the nanual tode of operation aud-I t

steppin;; the nachine, The ability to close the ball valve by turning the.nachine-off

{

(de-c u rgize tu close) was verified-and would have been available if required j

Therefore, there are no aafety implications to this occurrence.

!Correctiva Action:

The detector van returned to its in-r,hield position. The e.achine was de-4ncrgized..

i r.nd the ball valve was verified to be closed. Administrative procedures were i

initiated to ensure that the TIP cachine rec.ains in this condition'until the limit I

cuitch'c( f ailure to operate can be investigated and repaired.

Failure Data:

,On6 picVioua ' failure.'of' thin ' type ' reported iri 50-278-7S*31% '

i S

. r.',

'i ? i.

Very truly yoursl-

! - ; : i 5.-

1 8.

%gggQf r.

~

a

.y

$. T.'U1'Irich. Syy rintenddnti.

d'each Patto:a Ato:iic Pcver Sta' tion 3

2 i

i.

....l

'.. ' i

  • i f.

M.

a

.. s 8401120570 750620 PDR ADOCK 05000278 S

PDR