q y;,e
.,v Pl!! LADE 1.PilIA ELECTRIC COMPANY Peach Lotton Atonic Power Station Delta Pennsylvania 17314
/
Juna 30, 1975 lir. Jarsen P. O'Reilly, Director Of fice of Inspection and Enforeet ent..
-~ pg4 y Ecj i2*E;1on 1.d'Ge-m % G 2 5 6 h e ry re~-<L T b
- ~ ~
p~~gQ.sC.L/piCCC N.
O 631' Park Avenue King of Pruss1o. Pennsylvania 19t.06
[ ].f. g g d j'-3c p %
Subirrt:
Abnorral Occurrenec 24-l!nur Notifiention d *-
Conf.ireing %-T.-Ullrich 4. hora.onversation with Mr Paul-I. Eelr.on _P.cgion l _ United a t
Stateu Nuclear Regulatory Cocaicsion on.hme 23, 1975..
Reference:
License Nu-ber DPR-56 Technical Specification Faference:
3.9.A.2' Report No.:
50-278-75-36
..E=2.r.*. D43 4 ? -
mt-d-. M *H _ __
Occurrence Date; June 2/u 1975 Tacil'i ty :
Peach Botton Ato ic Power Station R.D. 1, Doltn, Pennsylvania 17314 Identification of Occurrence 9ailure of the E-1 diesel breaker to the Unit
'To~EH tTE'F E S T Jecurrer.deT ~
3 c:wrgency bus to close.
~
Unit 3 r.t 507. power.
Dcocriptica of Occurrence:
Durina an electrical switching operation in preparation for de-enernizing of an offcito pouar source. E-13 diccci breaker failed to close when requested by a cuitch fa the control roon. Ti.ic breaker supplien energy fron the diesel generctor to the Unit 3 ccorcency bus 6E-13.
Designation of Apparent Cause of Occurrence:
A If nkage in the breaker cubicieldlevator - t:ce.hanism cell switch una found to be bem Analynia of Occurt ence:
This fr.ilure uould have prevented the.E-1 diesel from supplyinn energy to the 1* nit 3
E-13 energency bus under a loss of power situation. t plant safety analysin graquires' only 3 operabic diesclo to acco=plinh a safe shutdown.-
I:=.ediately a f::er chis.C occurrence, all other dicsol breakers were tested and. found to be operational. Tais f ailure, therefore, has ninitul. safety. significance.
Corrective Action:
The subject breaker was racked out and the elevator mechanism cell switch arm vr.s atrai htened c.ud the cell cwitch adjusted. The breaker was reinstalled and tested C
successfully. All other diesci breakers were successfully tested, Failure Data:
j None.
Very truly yours,Af?J, WP }
W. T. Ullrich, Superintendent
' Peach Lot ton Atosic Pcuer Station
~
s 8401120548 750630 PDR ADOCK 05000278 S