ML20085F813

From kanterella
Jump to navigation Jump to search
RO 75-009:on 750804,diesel Generator 1-1 Cylinder & Exhaust Temps Rose Above Typical Operating Temps.Caused by Failure of Bellows Support Bracket Which Resulted in Decreased Exhaust Flow to Turbo Supercharger
ML20085F813
Person / Time
Site: Palisades 
Issue date: 08/14/1975
From: Bixel D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20085F815 List:
References
RO-75-009, RO-75-9, NUDOCS 8308230305
Download: ML20085F813 (2)


Text

r

~~1 O

O Consumers O

d 0

Power sf Company L

J oene, i ove,ce. si2 west u.cn.gan Avenue Jack son, Michsgan 49201 e Area Code 517 788-OS50 August 11,17/5 4

4 fL lij d'

h'b! lI dj

~

i AUG151975u h 9-u.s.wxw - m, y

Division of Reactor Licensing

  1. si y;

US Huclear Regulatory Comission g

Washington, DC 20555 A

(A DOCKET 50-255, LICENSE DPR-20, PALISADES PLANT, UE-75-9 Attached is Unusual Event Report No. 75-9 covering high cylinder and exhaust temperatures associated with the operation of a Palisades diesel generator.

Os David A. Bixel (Signed)

David A. Bixel Assistant Nuclear Licensing Administrator CC: JGKeppler, USNRC C6 ' S[ s i

p.

c>

COPY SENI REGION O

B308230305 ?] % 3 PDR ADOCK 0 PDR d b,b9 s

O O

~

O' UNUSUAL EVENT REPORT Palisades Nuclear Plant 1.

Report Number:

UE-75-9, Docket 50-255 2a. Report Date:

August 14, 1975 2b. Occurrence Date:

August 4, 1975 3

Facility:

Palisades Plant, Covert, Michigan 4.

Identification of Occurrence: Diesel Generator 1-1 high cylinder and exhaust temperatures.

5 Conditions Prior to Occurrence: Plant operating at steady-state power of 60%.

6.

Description of Occurrence: During the monthly testing of Diesel Generator -

1-1 (August 4,1975) cylinder temperatures reached approximately 1100 F after 15 to 20 minutes of operation. The diesel generator was fully loaded at 2 5 We.

Typical operating temperatures are 950 to 1000 F with temperatures as high as 1200 F considered acceptable although not desirable.

The diesel generator load test was terminated and the unit declared inoperable in accordance with Palisades Technical Specification 3 7 (1).

7 Designation of the Apparent cause of the Occurrence: Failure of a

( j bellows support bracket resulted in an exhaust manifold bellows failure.

This failure caused a decreased exhaust flow to the turbosupercharger (which regulted in a low air intake manifold pressure) and an increase of about 100 F in the cylinder temperatures.

8.

Analysis of Occurrence: The Palisades Technical Specification permits the diesel generator to be out of service for a limited period of time. In addition, if the diesel would have been required it would have been placed in service and would perform its design function.

9 Corrective Action: The bellows support bracket was repaired and new exhaust manifold bellows installed.

In addition, the diesel generator testing procedures are being reviewed with respect to acceptable cylinder wall temperatures.

i 10.

Failure Data: No previous failure of this type have been recorded.

I i

i

%.-)

l l

..