o O

O TENNESSEE VALLEY AUTHORITY M CHA'ITANDOGA, TENNESSEE i 37401 L

/A

$NIS5UNE

"^""""S"'"

June 1, 1973

(

}'~(f JH A v' Mr. F. E. Kruesi, Director K

Directorate of Regulatory Operations U.S. Atemic Energy Commission Washington, DC 205h5

Dear Mr. Kruesi:

On May h, 1973, TVA made initial report to AEC-DRO Inspector W. S. Little of the failure of the governor on Browns Ferr" Nuclear Plant unit 1 emergency diesel-generator B.

In accordance with paragraph 50.55(e) of 10 CFR 50, we submit the following formal report of the failure.

On February 28, 1973, diesel-generator B was found to be unstable when paralleled to the system. The instability decreased some-what when the load was increased, but the load could not be raised above 1200 kW; rated continuous load capacity of the unit is 2600 kW.

A defective Zener diode was located in the power supply of the governor and replaced. The unit was run again on March 16, 1973; the problem persisted. The governor was then replaced with one from one of the other diesel-generator units. Diesel-generator B then performed satisfactorily. A replacement governor was obtained and installed. The unit operated satisfactorily with the replace-ment governor on April 2,1973 The defective governor was returned to the Woodward Governor Company on April 2h,1973.

The governor is a type EG-A.

The engine is a General Motors E!D-GM Model 999-20.

Woodward has been requested to furnish information as to the exact nature of the failure. We expect to receive this information in time to provide a final report of the incident by July 31, 1973.

Very truly yours,

.w t.b. L hic G

j, Godwin Williams, Jr.

/

Assistant Manager of Power CC:

Mr. Norman C. Moseley, Director i

Directorate of Regulatory Operations U.S. Atomic Energy Commission Region II - Suite 818 230 Peachtree Street, NW.

Atlanta, Georgia 30303 8306290166 740617 PDR ADOCK 05000259 i