d SUPJECT8 DPR-25 DRESDEN NUCLEAR POWER ST g,Uf
[r h
fj THIS WILL CONFIRM A C0!NERSATION WITH MR H :BANdE--C. GM pELIGL AT 114 5 HOURS THIS DATE CONCERNING TWO SEPA r
'^
ATE INCIDENTS ON UNIT 3.
_ gyer ON 9-9-72 VHILE MAKING A CALLAbATION ON EHC LOU OIL PRESSURE SCRAM SU ITCHES, THE SET POINT ON TWO SWITCHES WAS FOUND BELOW THE 900 PSIG TEC g
HNICJL SPECIFICATION LIMITS. PS-LS-1 HAD DRIFTED DOWN TO A SET POINT 0 F 895 PSIG. PS-LS-4 HAD DD f"TED DOWN TO A SET POINT OF 818PSIG.
PS-LS-1 MAS A HISTORY OF h
- TING SET POINT WHILE PS-LS-4 IS A NEW MO DEL SWITCH WITH A SUPOSIDL)
J. EATER ACCURACY. THE SET POINT ON ALL SUI TCHES HAS BEEN INCREASED TO 935PSIG. IN ADDITION A CALLABRATION CHECK WILL BE MADE ON PS-LS-4 ON A WEEKLY BASIS UNTIL THIS PROBLEM OF EXCESS t
8,.isos cuan i
IVE SET POINT DRIFT CAN BE CORR'ECTED.
~
THE SECOND INCIDENT OCCURED ON 9-10-72 AT 0300 HOURS. LTILE CONDUCTING TURBINE WEEKLY CHECKS NUMBER 4 CONTROL VALVE FAILED TO INNICIATE A HA 15 SCRAM WHEN IT WAS FAST CLOSED. FUSE #590-725H WAS PULLED TO ACCUATE A HALF SCRAM UNTIL REPAIRS COULD BE COMPLETEDM MAINTENANCE CHECKED THE FAST ACTING SOLINOID ON #4 CONTROL VALVE AND F OUND IT LIMIT SWITCH WAS LOOSE. THE LIMIT SWITCH WAS ADJUSTED TIGHTENE D AND #4 CONTROL VALVE WAS TESTED SATISFACTORILY. ALL LIMIT SWITCHES WERE INSPECTED AND TIGHTENED. IN THE FUTURE DOUBLE NUTS WILL BE USED 0 N THE MOUNTING SCREWS WHICH SHOULD PREVENT THIS TYPE OF INCIDENT FROM
(
REACCURING W P WORDEN SUPT DRESDEN NUCLEAR POWER STATION.
l DPR-25 3 1145 3 9-9-72 EHC 900 PSIG PS-LS-1 895PSIG PS-LS-4 81SPSIG P
( se-ison caen
)
S-LS-1 PS-LS-4 935PSIC PS-LS-4 9-10-72 0300 #590-725H #4 #4 (1005A).
(
(