] one First Natiorti Plaza. ChicJgo. Ilknois

/

Commonwealth Edison

/

/

('

,/ Chicago, minois 60690 O ] Addr;ss Reply to. Post Offica Box 767 May 8, 1984 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

Quad Cities Station Unit 1 Proposed Amendment to Technical Specification for Facility Operating License DPR-29 Calibration / Functional Test Frequency for Analog Trip Units NRC Docket No.50-254 Reference (a):

G.E. Licensing Topical Report NEDO-21617-A dated December, 1978.

Dear Mr. Denton:

Pursuant to 10 CFR 50.59, Commonwealth Edison proposes to amend Appendix A, Technical Specification, to Facility Operating License DPR-29.

This amendment requests a change in calibration / functional test frequency for specific instrumentation.

During the current Quad Cities Unit 1 outage certain equipment will be replaced to fully comply with 10 CFR Part 50.49 (Environmental Qualification of Electrical Equipment).

The following instrumentation will be modified into analog trip systems:

Reactor Low Water Level Instrument 1-263-57A and B Reactor Low Water Level Instrument 1-263-58A and B hoactor Water Level Instrument 1-263-73A and B HPCI High Steam Flow Instrument 1-2389A through D HPCI Steam Line Low Pressure Instrument 1-2352 and 1-2353.

The analog trip system consists of an analog sensor (transmitter) and a master / slave trip unit setup which ultimately drives a trip relay.

The frequency of calibration and functional testing for instrument loops of the analog trip system has been estabilished in Licensing Topical Report NEDD-21617-A (December, 1978).

With the one-out-o f-two-taken-twice logic NED0-12617-A states that each trip unit be subjected to a calibration / functional test of one month.

The proper calibration /

surveillance test interval for the respective transmitter is once per operating cycle.

The only material change that exists with this This calibration frequency has g%

amendment is that the channel calibration will be performed at the transmitter once per operating cycle.

been found acceptable by the NRC in the referenced Topical Report.

T' 1

8405160226 840500

@tLY N W ff 00Q

H. R. Denton May 8, 1984 1

The proposed change is enclosed in Attachment 1.

The attached change has been received both Onsite and Offsite review and approval.

We have reviewed this amendment request and find that no significant hazards consideration exists.

Our review is documented in Attachment 2.

Common-aealth Edison is notifying the State of Illinois of our request of this amendment by transmittal of a copy of this letter and its attachments to the designated. State Official.

We have determined that this request is a 10 CFR 170, Class III amendment request.

As such a fee remittance of $4,000.00 is enclosed.

This change will be required at the time of Unit 1 startup from its current refueling outage.

The expected startup is currently mid-July 1984.

Therefore your prompt review and approval is requested.

Please direct any questions you may have concerning this matter to this office.

Three (3) signed originals and thirty-seven (37) copies of this transmittal and its attachments are provided for your use.

Very truly yours, l

(

B. Rybsk Nuclear Licensing Administrator 1m Attachments (1):

Technical Specification Change to DPR-29 (2):

Evaluation of Significant Hazards. Consideration cc:

Region III Inspector - Quad Cities R. Bevan - NRR G. Wright - Ill.

SUBSCRIBED'and SWORN to befo5 me this f g day 1984 of aLr setb 0'.

Lt -tr-J Notary Public 8565N

ATTACHMENT 1 4

Proposed Change to Appendix A Technical Specifications to 3

Operating License DPR-29 Revised pages:

3.1/4.1-6 3.1/4.1-7 1

3.1/4.1-12 3.1/4.1-13 3.1/4.1-14 3.2/4.2-10 3.2/4.2-10a 4

j 3.2/4.2-16 3.2/4.2-17 1

4 r'

i 8565N f

e l

..