Jump to navigation Jump to search
Telecopy Ro:On 740325,loop B Motor Valve M 2-10001-29B Failed.Valve Stem Found to Have 1/8 Inch Bow Over 24 Inch Length of Threaded Portion That Enters Motor Operator. Straightening of Mode Portion Being Attempted
ML20084L342
Person / Time
Site: Quad Cities Constellation icon.png
Issue date: 03/26/1974
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: Oleary J
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20084L335 List:
References
NUDOCS 8305200682
Download: ML20084L342 (1)


Text

,

J

!)

f a m r$

0 e

MGMMSHT HSB o

a [_

  • ICS IPMbNGZ CSP tue5 fem UniDn U ge } Q[{

i ># s 2=026813E085 03/26/.73

={

a 30965422a1 MGM TDBN CORDOVA IL 145 03=26 0340P EDT ZIP 20545 O

50-265 O

o N

p JOHN OLEARY DIRECTORATE LICENSING

/

(

O

[3 (t{,u.

US ATOMIC ENERGY COMMISSION

. e, WASHINGTON DC 20545 V

gg n w c f o/

zjnya e

O

(.

REFERENCE QUAD CITIES NUCLEAR POWER STATION UNIT TWO DOCKET O

NUMBER 50-265 DPR=30 APPENDIX A SECT!ON 1.0.A,2 AND 3.5,A,3 AT APPROXIMATELY 1600 40URS ON 3=25 74 WHILE PLACING SHUTDOWN

(

COOLING MODE OF THE RHR SYSTEM IN OPERATION TO THE B RECIRC O

LOOP MOTOR OPERATED VALVE H02=10001-29B *AS FOUND TO HAVE DUAL POSITION INDICATION SUBSEQUENT CHECKS PROVED VALYd TO BE INOPERABLE BOTM MANUALLY AND AUTOMATICALLY, VALVE WAS TAKEN OUT OF SERVICE O

AND DISASSEMBLE 0 VALVE STEM WAS FOUND TO HAVE ABOUT A 1/8 INCH S0W OVER 24 INCH LENGTH OF THREADED PORTION THAT ENTERS THE C

MOTOR OPERATOR. UNIT aAS IN COLD SHUTDO*N MODE FOR SHORT OUTAGE AND WILL REMAIN IN COLD SHUTDOWN PER TECHNICAL SPECIFICATION 3.5,F.2 UNTIL VALVE REPAIR IS COMPLETED. VALVE REPAIR BEING

(

ATTEMPTED IS TO STRAIGmTEN MODE PORTION'IN STATION SHOP, 4F N J KALIVIANAKIS COMMON *EALTH EDISON'C0 BOX 216 CORDOVA IL l