,_o TENNESSEE VALLEY AUTHORITY CHATTANOOGA. TENNESSEE 37401 400 Chestnut Street Tower II April 9, 1984 U.S. Nuclear Regulatory Commission Region II ATTN: James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

INSPECTION AND ENFORCEMENT BULLETIN NOS. 80-07, BWR JET PUMP ASSEMBLY FAILURE, AND 80-13, CRACKING IN CORE SPRAY SPARGERS - BROWNS FERRY NUCLEAR PLANT The Browns Ferry Nuclear Plant unit 3, cycle 5 invessel inspection of the reactor vessel was completed on March 12, 1984. The underwater camera system used for the visual inspection was qualified by underwater viewing of a metallurgical sample with one mil cracks.

In accordance with IE Bulletin 80-13, visual inspection of the core spray sparger and piping internal to the reactor vessel was performed between February 28 and March 12, 1984. No abnormalities were found. Total exposure to personnel performing the inspection was approximately 100 mrem.

In accordance with IE Bulletin 80-07, the' jet pump beams were. ultrasonically inspected on March 6 and 7, 1984. No indications'were found. The beams were visually inspected March 10,'11, and 12, 1984, and no abnormalities were found. Exposure to personnel performing the inspection was approximately.100 mrem.

If you have any questions, please-call Jim Domer'at FTS 858-2725.

To the best of my knowledge, I declare the statements contained' herein are complete and true.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Licensing i

8405070386 840409 PDR ADOCK 05000296 G

PDR.

y.

m.m..

s,.,

ga

,e

T~

i e

,, 1 Mr. James P. O'Reilly April 9, 1984 cc:

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Division of Reactor Operations Inspection Washington, D.C 20555 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 Mr. R. J. Clark U.S. Nuclear Regulatory Commission Browns Ferry Project Manager 7920 Norfolk Avenue Bethesda, Maryland, 20014

--