L.

(.

50-237 50-249

.c Commonwealth Edison Company 72 WEST ADAMS STREET

AMreen Reply tes POST OPPICE toX 767

  • C H I C A G O, ILLINOIS 60690 WPW Ltr.#253-73 Dresden Nuclear Power Station R. R. #1 Morris, Illinois 60450
c. ' I N D
,9, 9' March 30, 1973

~ -o., p %

h

.* ;3 A

- mi g} ; -M )s.,

[*;

7.}

o g

Mr. A. Giambusso

( s.;

$ p '.-"/

Deputy Director for Reactor Projects

\\,f LW d 4,g'/}/,

}

Directorate of Licensing U. S. Atomic Energy Commission

,g o.

Washington, D. C.

20545 VO

SUBJECT:

LICENSE DPR 19-25, DRESDEN NUCLEAR POWER STATION, UNITS 2 AND 3, SECTION 6.6.B.3 0F THE TECHNICAL SPECIFICATIONS.

Dear Mr. Giambusso:

This is to report a condition relating to the operation of the station in which on March 21 and 23,1973, Radwaste above ground storage tanks were found to contain 4.05, and 1.00 curies respectively, which exceeds the Technical Specification limit as stated in Section 3.8.D.

PROBLEM AND INVESTIGATION The following circumstances led to the "C" Waste Sample Tank content of 4.05 curies on March 21, and the Waste Surge Tank content of 1.00 curies on March 23, 1973:

The Waste Collector Tank was processed to "C" Waste Sample Tank through "B" Waste Collector Filter bypassing the demineralizer due to the high conductivity of the water. The high conductivity water was apparently tha result of water carryover from the Waste concentrator.

On March 21, 1973, at 2055, the sample on "C" Waste Sample Tank indicated 7

an activity of 3.6x10 uucuries/ liter which corresponds to 4.05 curies.

The "C" Waste Sample Tank was then pumped to an underground tank, "B" Waste Neutralizer, on March 22 at 1730. By March 23 at 0710, the entire "C" Waste Sample Tank had been pumped to the Waste Neutralizer for processing through the Waste Concentrator.

-(. '

,y 1

6r (5'

\\

V 8304120249 730330 PDR ADOCK 05000237 S

PDR 2181

p_

,)

Mr. A. Giambusso March 30, 1973 On March 23, the Waste Collector Tank was processed to "C"

  • Waste Sample Tank and sampled.

The sample analysis showed the tank activity to 6 uuCi/ liter which corresponds to less than the Technical Speci-be 1.56x10 fication limit of.7 curies. However, the conductivity of this water was unacceptable for storage.

"C" Waste Sample Tank was then pumped to the Waste Surge Tank. It appears that residual on the bottom of the Weste i Surge Tank caused the total activity of this tank to be 1.00 curies when the sample was analyzed at 1730 hours0.02 days <br />0.481 hours <br />0.00286 weeks <br />6.58265e-4 months <br /> March 23.

A portion of the water in the Waste Surge Tank was processed through a filter and demineralizer which reduced the tank curie content to 0.27 curies as shown by the sample analysis on March 24, 1973 at 1715.

The presence of 4.05 and 1.00 curies in the "C" Waste Sample Tank and Waste Surge Tank at different times did not present a hazard to the public since the contents of the tanks were not released to the river and radioactivity was reduced to less than Technical Specification limits within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following collection and analysis of the samples. Had a failure of the above ground tanks occurred, as described in Admendment #9,Section V.C.1 of the S.A.R., and the radioactivity contained in the tanks been released to the aquatic environment, the litnits as specified in 10 CFR 20.106 would not have been exceeded when averaged over one year.

CORRECTIVE ACTION In order to minimize the potential for future incidents of this nature, a procedure will be issued by April 3,1973, requiring sample analysis and calculations of curie content prior to processing to above ground radwaste storage tanks without the use of either a vaste collector filter or the radwaste demineralizer.

Sincerely, M.. WM W. P. Worden Superintendent WFW:do ec: WFW Ltr. File