ML20084B688
| ML20084B688 | |
| Person / Time | |
|---|---|
| Site: | Fort Saint Vrain |
| Issue date: | 05/10/1995 |
| From: | PUBLIC SERVICE CO. OF COLORADO |
| To: | |
| References | |
| FPOR-7, NUDOCS 9505310315 | |
| Download: ML20084B688 (4) | |
Text
s.
Public rORT ST, VRAIN NUCLEAR GENERATING STATION
$9fVICge PUBLIC SERVICE COMPANY OF COLORADO D'O DOCUMENT TRANSMITTAL TO
.Lontmspt Control Desk DATE May 23. 1995 FROM _DShbie Russell Fort St. Vrain
_16E05 WCIL194 Pinttev111e. CO 80651 THE FOLLOWING MATERIAL IS TRANSMITTED HEREWITH:
1 copy of each:
Fire Protection Operability Requirements Index, dated 5-10-95, Issue 25 FPOR 7 Issue 5 O
9505310315 950510 ADOCK0500g7 PDR O
'\\
PLEASE RETURN YOUR SIGNED ACKNOWI EDGEMENT INDICATING RECEIPT OF THE ABOVE MATERIAL (SiONE DI t D AT E)
Form tC) 372 22 3374 IMTIATOR - Forward White Copy to Rec 6pient. Retam Yellow Copy RECIPIENT - Retum Acknowledged White Copy to initiator
DFPP 05-10-95 4-Issue 25 SECTION DFP.S.1 FIRE PROTECTION OPERABILITY REQUIREMENTS TABLE OF CONTENTS NUMBER TITLE ISSUE EFFECTIVE DATE FPOR-0 Fire Protection Operability 4
12-07-92 FPOR-1 Emergency Diesel Generator Carbon 4
12-07-92 Dioxide System FPOR-2 Carbon Dioxide Hose Reels -
4 12-07-92 DELETED FPOR-3 Halon Systems 5
12-07-92 FPOR-4 Deluge Spray Systems 3
12-07-92 FPOR-5 Fixed Water Spray Systems 4
12-07-92 FPOR-6 Plant Yard Hydrants 4
02-15-95 l
FPOR-7 Fire Extinguishers 5
05-10-95 FPOR-8 Breathing Air System - DELETED 3
12-07-92 FPOR-9 Fire Hose Stations 4
12-07-92 FPOR-10 Fire Water Pumps 5
02-15-05 FPOR-11 Fire Water Headers and Mains 3
12-07-92 FPOR-12 Fire Detectors 04-12 95 FPOR-13 Fire Barriers
?
13-0*-92 FPOR-14 Fire Doors 9
11-08-94 FPOR-15 Fire Dampers 5
12-07-92 FPOR-16 Fire Protection Cooldown Trains -
5 12-07-92 DELETED FPOR-17 Alternate Cooling Method (ACM) 5 12-07-92 DELE *ED FPOR-18 Ladders - DELETED 4
12-07-92 FPOR-19 Cable Wraps - DELETED 3
12-07-92 FPOR-20 Emergency Lighting - DELETED 4
12-07-92 FPOR-21 Site Fire Brigade - DELETED 2
12-07-92 FPOR-22 Storage of Activated Graphite -
2 10-12-94 DELETED FPOR-23 Fire Water Makeup System 3
10-12-94
FPOR-7 I
Iccus 5
^
4..
Pcg3 1 of 2 i
(
FIRE PROTECTION OPERABILITY REQUIREMENTS Fire Extinguishers FPOR-7 Operable Fire Extinguishers shall be in their designated locations.
APPLICABILITY: At all times.
ACTIONS:
If a Fire Extinguisher is found inoperable or missing from its designated
- location, it shall be replaced by an equivalent / alternate extinguisher within one (1) hour.
SURVEILLANCE REOUIREMENTS:
Each Fire Extinguisher shall be determined operable:
a.
At least once per 31 days, by verifying:
1)
Located in designated place.
2)
No obstruction to access or visibility.
[]
3)
Operating instructions on nameplate legible and facing
'V outward.
4)
Safety seals and tamper indicators not broken or vissing.
5)
Fullness determined by weighing or " hefting."
6)
Examined for obvious physical
- damage, corrosion, leakage, or clogged nozzle.
7)
Pressure gauge reading or indicator in the operable range or position.
8)
For wheeled units, the condition of the tires, wheels, carriage, hose, and nozzle checked.
b.
At least once per 12 months, by performing:
1)
A thorough examination of the mechanical elements of the fire extinguisher.
hose assemblies.
2)
Conductivity test of CO2 3)
Check that each extinguisher has been hydrostatically p
tested within its required frequency.
V
FPOR-7
/
Page 2 of 2 Inzus 5 e
O l
BASIS FOR FPOR-7:
To suppress incipient fires, dry chemical,
- Halon, and Carbon Dioxide portable fire extinguishers are provided throughout the station in potential fire hazard areas.
NFPA 10, Portable Fire Exinguishers, is used as guidance for the location, selection,
(
maintenance, and testing of these extinguishers.
These extinguishers are also approved by Underwriters Laboratories.
The extinguishers are inspected periodically to verify their presence in the designated location, that they are fully charged, l and are operable.
This will ensure they are available and contain l
sufficient capacity should their use be required.
I O