ML20083P602

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs,Verifying Adequate SW Flow to Each Train of Reactor Bldg Emergency Cooling
ML20083P602
Person / Time
Site: Arkansas Nuclear 
Issue date: 05/19/1995
From:
ENTERGY OPERATIONS, INC.
To:
Shared Package
ML20083P592 List:
References
NUDOCS 9505240292
Download: ML20083P602 (26)


Text

,-..;

+

n

,. u o >

,.(,

/,

y,f

  • O' s

si

' c, e.

' e_ '

d

's

}

i

,. k '

g

' PROPOSED TECHNICAL SPECIFICATION CHANGES

. i r

I

- [

F.

9 A

e a

9505240292 950519 PDR ADOCK 05000313 PDR P

4.5.2 R, et*r Building c cling Syntems Applicability Applies to testing of the reactor building emergency cooling systems.

Objective, To verify that the reactor building emergency cooling systems are operable.

Specification 4.5.2.1 System Testa 4.5.2.1.1 Reactor Building Spray System (a) once every 18 months, a system test shall be conducted.to demonstrate proper operation of the system. A test signal will be applied to demonstrate actuation of the reactor building spray system (except for reactor building inlet

)

valves to prevent water entering nozzles).

(b) Station compressed air or smoke will be introduced into the spray headers to verify the availability of the headers and spray nozzles at least every five years.

(c) The test will be considered satisfactory if visual observation and control board indication verifies that all components have responded to the actuation signal properly.

4.5.2.1.2 Reactor Building Cooling System (a) At least once per 14 days, each reactor building emergency cooling train shall be tested to demonstrate proper operation of the system. The test shall be performed in accordance with the procedure summarized belows (1)

Verifying a service water flow rate of 2 800 gpm to each l

train of the reactor building emergency cooling.

(2)

Addition of a blocide to the service water during the surveillance in 4.5.2.1.2.a.1 above, whenever service water temperature is between 60F and 80F.

(b) At least once per 31 days, each reactor building emergency cooling train shall be tested to demonstrate proper operation of the system. The test shall be performed in accordance with the procedure summarized belows (1)

Starting (unless already operating) each operational cooling fan from the control room.

Amendment No. M,63,M3,44 95

Tho v rificaticn of carvica watsr flow reto to scch trein of rccctor building I

emerg:ncy c:oling io p:rformed to encuro that cufficient pect-cccid:nt rccctor building heat load can be removed by the coolers. The flowrate specified in the surveillance requirement corresponds to the conservative configuration of two fans and their associated cooling coils for each train of reactor building emergency cooling. The minimum flow rate which corresponds to the post-accident heat removal capability for other system configurations may be justified consistent with the bases of Specification 3.3.4 (a).

Addition of a biocide to service water is performed during reactor building emergency cooler surveillance to prevent buildup of Asian clams in the coolers when service water is pumped through the cooling coils.

This is performed when service water temperature is between 60F and 80F since in this water temperature range Asian clams can spawn and produce larva which could pass through service water system strainers.

The delivery capability of one reactor building spray pump at a time can j

be tested by opening the valve in the line from the borated water storage 1

tank, opening the corresponding valve in the test line, and starting the I

corresponding pump.

Pump discharge pressure and flow indication l

demonstrate performance.

With the pumps shut down and the borated water storage tank outlet closed, the reactor building spray injection valves can each be opened and closed by operator action. With the reactor building spray inlet valves closed, Jow pressure air or smoke can be blown through the test connections of the j

l reactor building spray nozzles to demonstrate that the flow paths are i

open.

The equipment, piping, valves, and instrumentation of the reactor building i

emergency cooling system are arranged so that they can be visually inspected. The cooling fans and coils and associated piping are located outside the secondary concrete shield.

Personnel can enter the reactor building during power operations to inspect and maintain this equipment.

l The service water piping and valves outside the reactor building are inspectable at all times, operational tests and inspections will be performeo prior to initial startup.

Two service water pumps are normally operating. At least once per month operation of one pump is shifted to the third pump, so testing will be l

unnecessary.

As the reactor building fans are normally operating, starting for testing is unnecessary for those verified to be operating.

Reference FSAR, Section 6 Amendment No. M,63,443,44 97

t-1 i

l i

i, MARKUP OF CURRENT ANO-1 TECHNICAL SPECIFICATIONS (FORINFO ONLY) l l

l

)

\\

l

g-m.y. (,

s o

T L 4.5.2 ' ; Re,eter Building caeling syntras -

j n,,

1 Os Applicability-4

' Applies'to testing of the reactor building amargency cooling systeem.

E

, objective JTo. verify that the reactor building emergency cooling systems are operable.

Specification 4'.5.2.1' LSystem Tests'

-l 4.5.2.1.1

. Reactor Building spray System (a) Once everyf18 months, a system test'shall'be conducted,toi denonstrate. proper operation of the system.- A test signal will be applied to demonstrate actuation of the reactor..

building spray system (except for reactor building inlet valves to prc7 ant vster entering nozzles).

(b) Station compressed air or smoke will be introduced into the spray headers to verify the availability of the headers and spray nozzles at least.every five years.

(c) The test will be considered satisfactory if visual observation and control board indication verifies that all. components have responded to the actuation signal' properly.

4.5.2.1.2 Reactor Building Cooling' System (a) At least once per 14 days, each reactor building emergency y

cooling train shall be tested to demonstrate proper operation.

of the system.

The. test shall b.. performed in accordance.with the procedure summarized belows n

(1) Verifying a service' water flow-rate of 2 1224344 gpm to each l

s train of the reactor building' emergency cooling.

(2) Addition of a biocide to the service water during the surveillance in 4.5.2.1.2.a.1 above, whenever service water temperature is between 60F and 80F.

(b) At least once per 31 days, each reactor building emergency cooling train shall be tested to demonstrate proper operation of the system. The test shall be performed in accordance with the procedure summarized below (1)

Starting (unless already operating) each operational cooling fan from the control room.-

l Amendment No. 34,43,M 3,444 95

The verification of service water flow rate to each train of reactor buildina emeroency coolina is performed to ensure that sufficient post-accident reactor buildina heat load can be removed by the coolers. The flowrate specified in the surveillance recuirement corresponds to the conservative confiauration of two fans and_their associated coolina coils for each train of reactor buildina emeroencv_coolina. The minimum flow rate which corresponds to the post-accident heat removal capability for other system conficurations may be iustified consistent with the bases of Specification 3.3.4 (a).

Addition of a biocide to service water is performed during reactor building emergency cooler surveillance to prevent buildup of Asian clams in the coolers when service water is pumped through the cooling coils.

This is performed when service water temperature is between 60F and 80F since in this water temperature range Asian clams can spawn and produce larva which could pass through service water system strainers.

The delivery capability of one reactor building spray pump at a time can be tested by opening the valve in the line from the borated water storage tank, opening the corresponding valve in the test line, and starting the corresponding pump.

Pump discharge pressure and flow indication demonstrate performance.

With the pumps shut down and the borated water storage tank outlet closed, the reactor building spray injection valves can each be opened and closed by operator action. With the reactor building spray inlet valves closed, low pressure air or smoke can be blown through the test connections of the reactor building spray nozzles to demonstrate that the flow paths are open.

The equipment, piping, valves, and instrumentation of the reactor building emorgency cooling system are arranged so that they can be visually inspected. The cooling fans and coils and associated piping are located outside the secondary concrete shield.

Personnel can enter the reactor building during power ooerations to inspect and maintain this equipment.

The service water piping and valves outside the reactor building are inspectable at all times.

Operational tests and inspections will be performed prior to initial startup.

Two service water pumps are normally operating. At least once per month operation of one pump is shifted to the third pump, so testing will be unnecessary.

As the reactor building fans are normally operating, starting for testing is unnecessary for those verified to be operating.

Reference FSAR, Section 6 Amendment No. 24,4,M G,446 97

c-o ARKANSAS NUCLEAR ONE CALCULATION COVER SHEET ICale. No.:

95-E 4046-03 Rev. No.: 0 l'

Calc.

Title:

RB Cooler Minimum Service Water Flow Unit:

1 Category:

O Requirements.

Systess (s):

RBHV, SW Calc. Type: MG Componest No(s): VCC-2A, 2B, 2C, 2D.

. Topic (s): ENVQ, ECCS, CWr, LOOP, LOCA, DB AA Pit Area:

Bldg.

IRB Elev. 374 ft-6 in Reem W all Coordinates:

Config. Checklist (per 5010.004) conspleted? (Y or N) Y Abstract (Included Purpose /Results): Purpose of this calculation is to provide design basis for minimum service water flow to the two parallel RB Coolers in each train (normal aligmnent).

Result: A total minimum flow of 800 gpm is required for each train of RB Coolers.

Pages Revised and/or Added: All new pages 15, Attachment 1, pages 1 12, Attachment 2, pages 12 Purpose of Revision: New issue laitiatina Documents Resultime Docureent(s)

Kev Desian Inout Does.

CR 195 0433 N/A Calc. 88-E-0098 16, rev 0 TM 951025 Calc. 88-E-0098-17, rev 0 Calc. 95 E 0046-01. rev 0 1

Verification Method:

Design Review X Alternate Calculation Qualification Testing Anseeds Calc (s):

88-E-0098 16, rev 0 Supersedes Cale(s):

N/A Computer Software Used:

Holtec AIRCOOL ver. 5.02a By: Roger Wilson

/ EO

/ 5/18/95 Rvw'd:

/

/

/ (9b / <!4" /or Apv'd:

Mikon Huff LD % N / T//9 Chk'd:

David MacPhee (Print Name)

(initials)

(Date) '

(Print Name)

(Initials)

(Date)

Check if Additional Revisions:

E

] ' Calculation 95-E-0046-03, rev. O Pag 2I of5 1

Purpose:

The purpose of this calculation is to provide the basis for the minimum SW flow to each train of reactor building service water cooling coils under a nonr d system configuration in support of a May,1995 proposed amendment to Technical Specification 4.5.2:

Methodology:.

a) Part A will determine the thermal performance of parallel RB coolers and associated fans for flow rates assuming a 50/50 flow split between the coolers. The resulting table will be used to document train operability at 95 'F inlet SW temperature.

b) Part B provides a sensitivity study using a conservative result from Part A for flow imbalances other than 50/50 between the two coolers.

References:

1. Calculation 88-E-0098-16, rev. 0
2. Calculation 88-E-0098-17, rev. 0
3. Calculation 95-E-0046-01, rev. O Holtec AIRCOOL runs for "C" RB Cooler
4. Calculation 95-E-0046-01, rev. O RB Cooler flow data
5. RB cooler fan test, Job Order 922118, Task 018130
6. PEAR 95-0148 response
7. Holtec AIRCOOL runs (attachment 1)
8. RB Flow resistance curves (attach. 2)
9. Ops Proc. 1104.033, rev. 52, pc-1 & pc-2 Assumptions and Given Conditions
1. Cooler design air flow is 30,000 cfm. Cooler air flow rate is conservatively taken as 27,378 acfm based upon the latest air test for "C" unit (ref. 4) which tested at the lower flow rate on the airside of the four RB coolers. This is a conservative assumption since the data was taken with flow through the normal inlet ductwork and the bypass damper closed. During accident conditions, the bypass damper will open, eliminating the inlet ductwork friction lou. Previous testing with the damper open resulted in air flows in excess of 30,000 cfm for all four eqolers (ref. 5). This assumption provides some design margin.
2. Holtec AIRCOOL will be used to model thermal performatice, with corrections to match AAF performance data, as described below.
3. The AAF design fouling factor of 0.002 is used (ref.1).
4. The required heat transfer is taken as 105% of 53.7 million btu /hr. This represents a 5% margin above the heat removal rate assumed in the design basis accident (the l By: Bold l Chk'd:

(Eb l Apyd: D % pK i

e

Calculatisn 95-E-0046-03, rev. O Page 2 cf 5 COPATTA analysis, ref. 2). Entering air is input at 286 *F,74 psia and 100% relative j

humidity (ref. 2).

S. Thermal performance of VCC-2A,2B, and 2D is the same as VCC-2C.

Part A:

The COPATTA analysis (ref. 2) is based upon heat transfer input from ref.1, which in turn is based upon performance data generated using American Air Filter (AAF) computer programs. Because of certain differences in modeling, the Holtec AIRCOOL program slightly over predicts cooler performance. To benchmark Holtec results against AAF results, benchmark cases were run (ref. 3) to determine correction factors for other AIRCOOL generated performance data.

American Air Filter determined performance data for two cases ofinterest, SW flow at 600 and 1200 gpm with inlet SW temperature of 95 *F (ref.1). Heat transfer rates for both of these cases were determined. Using the same input data, the Holtec program AIRCOOL was used to determine predicted heat transfer rates, which were expected to be higher. Results at these two conditions were used to determine corrections factors, which will be used to correct the predicted Holtec results to AAF results (ref. 3).

Three Holtec analyses are run using 95 F SW inlet temperature and flow rates that result in heat removal rates equal to or greater than 56.5 million b'.u/hr.

Part A Calculation:

The AAF input data are as follows (ref.1):

Table 1 Total CFM at inlet:

30,000 cfm Inlet air temperature:

286 deg F Inlet air pressure:

74 psia Inlet RH:

100 Inlet water temperature:

95 deg F Case I water flow:

1200 gpm Case 2 water flow:

600 gpm Case I heat transfer:

56,526,685 btu /hr Case 2 heat transfer:

39,601,139 btu /hr The predicted heat transfer using AIRCOOL is as follows (ref. 3)

Table 2 Case:

AIRCOOL Ratio 600 gpm:

40,145,000 0.99 l Bv: 'PR d l Chk'd:

(&

Apyd: DfSM C

1 Calculation 95-E-0046-03, rev. O.

Page 3 of 5 The input data to use in the AIRCOOL runs is as follows for all cases:

Table 3 Total CFM at inlet:

27,378 enn Inlet air temperature:

286 deg F Inlet air pressure:

74 psia Inlet RH:

100 For SW flow rates of 750, 800 and 850 gpm at 95 *F inlet SW temperature, the results are (attachment 1):

Table 4 SW Flow Heat Removal (gpm) 50 %

50 %

AIRCOOL Corrected (.99) total cooler I cooler 2 cooler I cooler 2 cooler 1 cooler 2 total 750 375 375 28776000 28776000 28488240 28203358 56691598 t

800 400 400 30216000 30216000 29913840 29913840 59827680 850 425 425 31604000 31604000 31287960 31287960 62575920 The corrected heat removal for all three cases exceeds 56.5 million btu /hr. Using 800 gpm in Part B is therefore conservative and provides margin to be applied for the flow split analysis.

Part B:

Part A determined that 800 gpm at 95 *F inlet SW temperature exceeds a conservative heat removal of 56.5 million btu /hr. Part B will split the flow between the parallel RB coolers in 10% increments to determine heat removal capability at other than a 50/50 flow split.

Part B Calculation:

Using the 800 gpm, 95 *F inlet SW temperature from Part A, the sensitivity study results are (attachment 1):

m, Bv: 66Ld l Chk'd:

(%D/

l Apyd: DMM v

s

l Calculation 95-E-0046-03, rev. O Page 4 of 5 Table 5 Heat Removal (Btu /hr)

Flow

% Flow Flow (gpm)

AIRCOOL Corrected Imbalance Imbalance Clr 1 Clr 2 Cooler 1 Cooler 2 Cooler 1 Cooler 2 Total 50/50 0%

400 400 30216000 30216000 29913840 29913840 59827680 60/40 20 %

480 320 34543000 25478000 34197570 25223220 59420790 70/30 40%

560 240 38315000 19716000 37931850 19518840 57450690 80/20 60 %

640 160 41759000 12964000 41132615 12834360 53966975 Total Heat Removal vs. Flow Imbalance m

~

\\

so0x0m

\\

N l 565@m0 Btu /hr l

/

\\

/

\\ \\

5m0mm s

l 537 mom 8* I suxxxxo

,/

o 530am00 0%

10%

20 %

30%

40%

50 %

80%

50/50 Spht 80/40 Spa Flow kv6alence 7(y30 Spa 8(V20 Spet Figurei Discussion Part A of the calculation demonstrates that, with an inlet SW temperature of 95 *F, flow rates of 750, 800 and 850 gpm provide heat removal capability in excess of 105% of design basis accident requirements.

Bv: FOA/

Chk'd:

(710 Apyd:.J)M WZ

.= ;

Calculation 95-E-0046-03, rev. O Page 5 of 5 Part B shows that 105% of design accident heat removal is met with a flow imbalance

!between the coolers where greater than 70% of the total flow is through one cooler and less than 30% total flow is through the parallel cooler.

The coolers are the same size, at the same elevation and were designed for a 50/50 flow split. Attachment 2 demonstrates that this is the case. shows that the limits for the operability of the RB coolers will be reached well before a 70/30 flow split is reached. The curves in the attachment are based on the 2

2 formula AP = K' Q or the resistance factor, K, equals AP/Q.

Baseline and acceptance resistance factors Ka and K4were determined from flow data taken during the last refueling outage (IR12) (ref. 9) when the service water system was in its Engineered Safeguards line-up Ka represents the baseline actual system resistance through parallel RB coolers and piping. K4 represents the operability limit resistance factor for two parallel coolers. The third resistance factor, Kr, was determined from recent testing with flow through one cooler completely blocked by a blind flange (ref. 6).

From examination of the three resistance curves, the large difference between the one and two cooler baseline curves indicates that the assumption of a 50/50 flow split is valid.

Conclusion A calculated flow rate of 800 gpm provides ample margin for design accident heat removal and includes allowance for flow imbalances between the parallel coolers that far exceed expected flow imbalances.

w 1

Bv:

RT)LM l Chk'd:

(AW l Apyd: h% M 4'

[

6 l

l.

i l

i PROGRAM AIRCOOL REVISION 5,020 FINNED COIL HEAT EXCHANGER RATING PROGRAM Copyright 1988 by Holtec International. All rights reserved.'

This computer code is QA validated under Holtec International's QA system.

This report was created on: 5/18/1995 at 16:10: 1.24 9

4 C8 2 ME N T

.ela so.

N f-b(-o?, es,6 11.7514. /

I PAGil _l oF Q r-

/&

\\9 N

+.

t,.

n 4

' /

1 Y.

' Mode of Operation: PERFORMANCE PREDICTION' Name of Data File: ' C:VCC2C.PPI File Descripdon:

Component Identification: VCC2C Component

Description:

  • "** EQUIPMENT CONFIGURATION "*"

i Parameter Value QA Ref #

l Number of HX coil sections in parallel per unit 4

1 Number of tube rows crossed by air flow per coit 10 2

Length of finned tube exposed to air flow, in 102.000 t

J Number of tubes per row 16 1

Tube outside diameter,in

.6250 1

Tube wall thickness, in

.0490 1

Tube material (l.90/10 CuNi; 2-Copper) 1 1

Tube spacing transverse to air flow, in 1.5000 3

Tube spacing in line with air flow,in 1.5000 3

Fin thickness, in

.0100 i

L Fin material (2 Copper ; 3 Aluminum) 2 4

Number of fins per inch 6.0 1

i Serpentine (0 half; l single; 2-double) 2 1

l I

Number of coil groups per unit 2

5 Number of tube rows in group i 12 5

Number of tube rows in group 2 8

5 Note: The input for number of tube rows crossed by air 11ow per coil was not used.

Fin style AAF CORRUGATED PLATE 1 l'

hs 9I5')

3 l.&

MTACH. _/_

PAGE CF';

WP

s z.,

f Mode of Operation: PERFORMANCE PREDICTION i

Name of Data File: C:VCC2C.PPI Fils

Description:

,, r Component Idr.atification: VCC2C Component

Description:

t QA REF SOURCE DESCRIPTION.

+.

i-01 M61 A 7-4, American Air Filter Drawing M61 A 8-4, American Air Filter Drawing 02 Estimated by average of number of tube rows in all eight coils 03 Estimated as 1.5 inch pitch, which is typical of American Air Filter coils of this general geometry 04 Fin material should be CuNi. Copper was und instead since CuNi was not available in this program.

05 DRAWING 6600-M6IA-3 4 4

i 9

8

. +

i l

t t

I I

' I Y

h [*[' 9'b * [,I. / f / )

t f m.: ;

c.: i7 1

+w S gta i

6

.,---.mrr.

-ri v -- ~,

7 N:,, -,

Mode of Operation: PERFORMANCE PREDICTION Name of Data File: C:VCC2C.PPI File D:scription:

Component Identi6 cation: VCC2C Component

Description:

  • " PERFORMANCE DATA ""*

Procedure # BLIND FLANGE Date: 05/19/95 Cooling Water Hot Air Pressure Not required 74.00 psia Rel humidityin Not applicable 100.00 %

Rel humidity out Not applicable 100.00 %

Flow ratein 640.00 gpm 27378.00 acfm Temperature in 95.00 deg F 286.00 deg F (db)

Temperature out 225.26 deg F 281.25 deg F (db) l Fouling 1/(Bru/Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean) 6.03 psi Not calculated Pressure Drop (fouled) 6.03 psi Not calculated.

Velocity (clean) 3.38 A/sec 402.62 R/ min Thermal conducuvity of fouling layer, Btu /hr/ft^2/deg F

.00 Number of equi distant air zones along the tube length = 1 Uniform distnbution Heat duty 1000 Bru/Hr (Total / Sensible / Latent) 41759/ 308/41450 Avg overall ht coef. (Bru/Hr/SqFt/deg F) 17.18 Gross ht surface area (Sq Ft) 5663 Dew Point temperature, deg F 286.00 l.tl $ $,~

d F f~002 C!<* 0

'i7ACH. /

! PAGE L,L CP /q

[

Eof l

Q' :

^

~

Mode of Operation: PERFORMANCE PREDICTION

< Name ofDataFile: C:VCC2C,PPI File

Description:

Component identification: VCC2C Component

Description:

  • "" PERFORMANCE D ATA "*"

Procedure # BLIND FLANGE Date: 05/19/95 Cooling Water Hot Air Pressure Not req! ired 74.00. psia Rei humidity in Not appik ;ble 100.00 %

Rei humidity out Not applicable 100.00 %

Flow rate in 560.00 gym 27378.00 acfm Tempemture in 95.00 deg F 286.00 deg F(db)

- Temperature out 231.53 deg F 281.72 deg F(db)

Fouling 1/(Dtu!Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean) 4.71 psi Not calculated Pressure Drop (fouled) 4.71 psi Not calculated Velocity (clean) 2.% ft/sec 402.62 ft/ min Thermal conductivity of fouling layer, Btu /hr/ft^2/deg F

.00

. Number of equi-distant air zones along the tube length = 1 Uniform distribution Heat duty 1000 Bru/Hr (Total / Sensible / Latent) 38315/ 269/38045 Avg overall ht coef. (Btu /Hr/SqFt/deg F) 16.49 Gross ht surface area (Sq Ft) 5663 Dew Point temperature, deg F 286.00 Viuti.'1

\\ % F S u rr.. " !

l and. / !P.4G3 f CF /&,

4W 2

~

.Q Mode of Operation:

PERFORMANCE PREDICTION Name ofData File:

C:VCC2C.PPI File

Description:

Component Identification: VCC2C Component

Description:

""' PERFORMANCE DATA ""*

Procedure # BLIND FLANGE Date: 05/19/95 i

Cooling Water Hot Air Pressure Not required 74.00 psia Ret humidity in Not applicable 100.00 v.

Rei humidity out Not applicab!c 100.00 %

Flow rate in 480.00 gym 27378.00 acfm Temperature in 95.00 deg F 286.00 deg F(db)

Temperature out 238.32 deg F 282.22 deg F(db)

Fouling 1/(Bru/Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean) 3.54 psi Not calculated r

Pressure Drop (fouled) 3.54 psi Not calculated Velocity (clean) 2.54 Wsec 402.62 ' Nmin Hermal conductivity of fouling layer, Btu /hr/ft^2/deg F

.00 Number of equi-distant air zones along the tube length = 1 Uniform distribution 11 eat duty 1000 Blu/Hr (Total / Sensible / Latent) 34543/ 252/34291 Avg mtrail ht coef. (Bru/Hr/SqFt/deg F) 15.71 Gross ht surface area (Sq Ft) 5603 Dew Point temperature, des F 286.00

- _. _ =..

" <l

' % G-MM c!. Py n s

~~'.L /

rd f c /2 I

4$

4

(;j_-

,_q.' 'W 4'

i

j. -

R.

I 1

^

Mode of Operation. PERFORMANCE PREDICTION Name of Data File:' C:VCC2C ~.PPI File

Description:

Component Idenafication: VCC2C Component

Description:

....* PERFORMANCE DATA *""

Procedure # BLIND FLANGE Date: 05/19/95 f

Cooling Water Hot Air Pressure Not required 74.00 psia Ret humidityin Not applicable 100.00 %

Ret humidity out Not applicable ~ 100.00 %

Flow rate in 425.00 spm 27378.00 acfm Temperature in 95.00 des F 286.00 des F(4)

Temperature out 243.35 deg F ~ 282.59 deg F (db)

Fouling 1/(Btu /Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean) 2.83 psi Not calculated Pressure Drop (fouled) 2.83 psi Not calculated Velocity (clean).

2.25 R/sec 402.62 ft/ min

' Thermal conductivity of fouling layer, Btu /hr/R^2/ des F -.00.

i Number of equi-dastant air zones along the tube length = 1 Uniform distnbution i

Heat duty 1000 Btu /Hr (Total / Sensible / Latent) 31604/ 238/31366

" Avg overall ht coef. (Btu /Hr/SqFt/deg F) 15.04

- Gross ht surface area (Sq Ft) 5663 Dew Point temperature, deg F 286.00 4 Eh?f$.N lII 6 00 Yip /f'/pj wuca. (..

j P.4GE '2 CF /K _I w

  • =m-

'l 1

-n

-)

tz.

.s.

I Mode of Operation: PERFORMANCE PREDICTION Name of Data File:

C:VCC2C.PPI l

File Descripdon:

CcmponentIdentiAcatiori: VCC2C' 5

Component

Description:

"*" PERFORMANCE DATA "*"

Procedure # BLIND FLANGE Date: 05/19/95 Cooling Water Hot Air Pressure Not required 74.00 psia Rei humidity in Not applicable 100.00 %

Ret humidity out Not applicable 100.00 %

Flow ratein 400.00 gpm 27378.00 acfm Temperature in 95.00 deg F. 286.00 deg F(db)

Temperature out 245.74 deg F 282.77 deg F(db)

Fouling 1/(Btu /Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean) 2.53 psi Not calculated Pressure Drop (fouled) 2.53 psi Not calculated Velocity (clean) 2,12 A/sec 402.62 A/ min Thermal conductivity of fouling layer, Btu /hr/A^2/deg F

.00 l

Number o(equi distant air zones along the tube length = 1 Uniform distribudon Heat duty 1000 Btu /Hr (Total /Sensibic/ Latent) ' 30216/ 229/29986 Avg overall ht coef. (Btu /Hr/SqFt/deg F) 14.70 Gross ht surface area (Sq Ft) 5663 r

Dew Point temperature, deg F 286.00 l '.5l E' h

@[I{~ W Oflesyj t

jum.AL iam f c7!t a w

l t

,p

~.

  • ~

.i c.

r

' Mode of Operation: PERFORMANCE PREDICTION

. Name of Data File: C:VCC2C.PPI 4

File

Description:

C=mt Identification: = VCC2C.

Component

Description:

I

....' PERFORMANCE DATA "*"

Procedure # BLIND FLANGE.

Date: 05/19/95 i

Cooling Water Hot Air Pressure Not required 74.00 psia Rei humidityin Not applicable. 100.00 %

Ret humidity out '

Not applicable 100.00 %

Flow ratein 375.00 gym 27378.00 acfm Temperature in

' 95.00 des F 286.00 deg F(A)

Temperature out -

248.23 des F 282.94 deg F(db)

Fouling 1/(Btu /Hr/SqFt/degF)

.0020-

.0000 Pressure Drop (clean) 2.24 psi Not calculated Pressure Drop (fouled) 2.24 psi Not calculated Velocity (clean) 1.99 R/sec 402.62 N min Thermal conductivity of fouling layer, Bru/hr/A^2/deg F

.00

'I Number of equi-distant air zones along the tu% length = 1 Unifoim distribution Heat duty 1000 Btu /Hr (Total / Sensible / Latent) 28776/ 221/ 28555 Avg overall ht coef. (Btu /Hr/SqFt/deg F) 14.34 Gross ht surface area (Sq Ft) 5663 Dew Point temperature, deg F 286.00

. ' k I' $ M T-U-ooyf rp fe,9)

, m z./.

.a.9 mn w

e NQ' i

~

l J

q l

. Mode of Operation: PERFORMANCE PREDICTION N.une of Data File: C:VCC2C.PPI j '.

File

Description:

i Component Identification:. VCC2C Component

Description:

'"" PERFORMANCE DATA *""

(

l l

Procedure # BLIND FLANGE Date: 05/19/95 l

\\

l Cooling Water Hot Air Pressure Not required 74.00 psia l

l Rei humidityin Not applicable 100.00 %

L Rei humidity out Not applicable 100.00 %

l Flow rate in 320.00 gym 27378.00 acfm l

Temperature is 95.00 deg F 286.00 des F(db)

Temperature out 253.87 deg F 283.33 deg F(db)

Fouling 1/(Btu /Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean) 1.68 psi Not calculated Pressure Drop (feuled) 1.68 psi Not calculated Velocity (clean) 1.70 ft/sec 402.62 ft/ min 1

Thermal conductivity of fouling layer, Bru/hr/ft^2/deg F

.00

)

Numbcr of equi distant air zones along the tube length = 1

\\

\\

l Uniform distnbution

- Heat duty 1000 Btu /Hr (Total / Sensible / Latent) 25478/ 176/25302 Avg overall ht coef. (Btu /Hr/SqFt/deg F) 13.49 Gross ht surface area (Sq Ft) 5663 Dew Point temperature, deg F 286.00 l

s g

, m 19 -;- n

- 1 l

l

nu

'r

~7

.ec

,,7 l :.

Mode of Operauon-PERFORMANCE PREDICTION Name of Data File: C:VCC2C.PPI '

File

Description:

I Component Idenuficatiou: VCC2C Component

Description:

3

"*** PERFORMANCE DATA "*"

Procedure # BLIND FLANGE Date: 05/19/95 Cooling Water Hot Air Pressure Not required 74.00 psia Ret humidityin Not applicable 100.00 Rel humidity out Not applicable 100.00 %

Flow rate in.

240.00 gym 27378.00 acfm Temperature in.

95.00 des F 286.00 des F(db)

Temperature out 259.09 deg F 283.99 deg F(db)

Fouling 1/(Blu/Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean)

.99 psi Not calculated Pressure Drop (fouled)

.99 psi Not calculated i

Velocity (clean) 1.27 ft/sec. 402.62 Nmin Thermal conductivity of fouhng layer, Btu /hr/A^2/deg F

.00

. Number of equi <iistant air zones along the tube leng,th = 1 Uniform distribution l

Heat duty 1000' Btu /Hr (Total / Sensible / Latent) 19716/ 127/ 19589 Avg overall ht cc:f. (Bru/Hr/SqFt/deg F) -

10.82 Gross ht surface area (Sq Ft) 5663 Dew Point temperature, deg F 286.00

,p 3 11 i lk i

/r/f,-

y',:,

s; Mode of Operation:

PERFORMANCE PREDICTION Name of Data File: C:VCC2C '.PPI File

Description:

Component Identification: VCC2C Component

Description:

""* PERFORMANCE DATA *""

Procedure # BLIND FLANGE Date: 05/19/95 Cooling Water Hot Air Pressure Not required 74.00 psia Ret humidityin Not applicable 100.00 %

Rel humidity out Not applicable 100.00 %

Flow rate in 160.00 gym 27378.00 acfm Temperature in 95.00 deg F 286.00' deg F (db)

Temperature out 257.07 deg F 284.72 deg F(db)

Fouling 1/(Btu /Hr/SqFt/degF)

.0020

.0000 Pressure Drop (clean) 48 psi Not calculated Pressure Drop (fouled)

.48 psi Not calculated Velocity (clean) -

.85 Wsec 402.62 W min Thermal conductivity of fouling layer, Btu /hr/A^2/deg F

.00 Number of equidistant air zones along the tube length = 1 Uniform distribution Heat duty 1000 Bru/Hr (Total /Sensibic/ Latent) 12964/ 97/ 12867 Avg overall ht coef. (Btu /Hr/SqFt/deg F) 6.86 Gross ht surface area (Sq Ft) 5663 Dew Point temperature, deg F 286.00

._G.y~f)C&OIh,?,f "X

. ' : h,A l<

j w

~

RB COOLER FLOW RESISTANCE CURVES 250 Curve for one cooler plugged

/

\\

2M

\\

/

\\

/

\\

/

l Unacceptable Region l

^g

\\

/

m 1 /

D 150

/

- - - Kbaseline

/

/

p

+Kacceptance m

h

/

/

Kplugged

/

/'

g too.._

/

J '

.-j A

/

/

g;[!!)-j A

2 w

lje ii

55

/

/

9

/

/

p

/

/

g x 50

/

/

y; $

9

.a e

p f

/

/

.nk.

%r:W p

a s

  1. 1er=

p4 0

N.

Ils,

8 0

500 1000 1500 2000 2500 3000 3500 4000 4

FLOW (GPM)

~ ' " +

a The fe5 ewing table provides d;ta for these ctrves:

3f Mew DP DP DF Forsamlas for curves:

i Kbaseline Kacceptance Kplugged 0

0 0

0 Kb=

7.78E-06

  • gym ^2
g 250 0

1 1

Ka=

9.60E-06 a gpam^2

[

500 2

2 4

Kp=

1.63E-05 a gpsm^2 i

g p)

. y l

750 4

5 9

y my g

1000 8

10 16 A

1100 9

12 20 1200 11 14 23 l

1350 14 17 30-

- - r/

j 1400 15 19 32 M

1500 18 22 37

$T f i

- 1600 20 25 42 1700 22 28 47 l

1800 -

25 31 53 l

1982 31 38 64 2000 31 38 65 j

2200 38 46 79 j

2400 45 55 94 l

2600 53 65 110 2800 61 75 128 3000 70 86 147 3200-80 98 167 3400 90 til

- 188 3600 101 124 211 1

4 9

I:

4 m.~

- a a

T D

-eww we

-e

= * * * *

-C+1

-p-

-A1 er a

  • - uA

--